| 2007-07-05 08:38:16 | BUILDING PLAN REVIEW |
| | PERMIT: 07060741 |
| | ADD: 400 N FLAGLER DR. |
| | CONT: BRANCH CONSTRUCTION INC. |
| | TEL: (561)833-6206. |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 1ST |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)FBC:1203.4.2.1 BATHROOMS . |
| | ROOMS CONTAINING BATHTUBS, SHOWERS, SPAS AND SIMILAR |
| | BATHING FIXTURES SHALL BE MECHANICALLY VENTILATED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL |
| | . |
| | |
| | |
| | 3)FBC: TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION BASED ON INTERIOR |
| | FINISH REQUIREMENTS BASED ON OCCUPANCY. |
| | |
| | 4)1207.3THE FLOOR/CEILING ASSEMBLY SHALL HAVE AND |
| | IMPACE INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WITH ASTM E 492. PROVIDE THE |
| | INFORMATION MEETING THIS REQUIREMENTS. BE SPECIFIC. |
| | |
| | 5)WPB AMENDMENTS 106.1.3THE BUILDING OFFICIAL MAY |
| | ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR |
| | PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| | CONFORMITY TO ITS RECORD RETENTION PROGRAM.PROVIDE A |
| | WALL DETAIL DRAWING OF EACH NEW WALL AND THE INFILLS |
| | WALLS INDICATING ALL MATERIALS. |
| | |