| Date |
Text |
| 2008-01-25 09:08:21 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED 2ND TIME: |
| | |
| | **PREVIOUS PLAN REVIEW COMMENTS NOT ADDRESSED** |
| | |
| | 1. **COMMENT NOT ADDRESSED** |
| | THERE WAS NOT A PERMIT APPLICATION SUBMITTED FOR THE |
| | PROPOSED WORK WHICH IS REQUIRED BY A LICENSED |
| | CONTRACTOR. PER *FS489.113 PERMIT APPLICATION CAN NOT |
| | BE SUBMITTED BY A CORPORATION OR OWNER BUILDER. |
| | |
| | 2. **COMMENT NOT ADDRESSED** |
| | THERE WAS NO VALUATION FOR THE PROPOSED WORK. PER |
| | *108.3 VALUATION MUST BE ON THE REQUIRED PERMIT |
| | APPLICATION FOR THE PROPOSED WORK. |
| | |
| | 3. **COMMENT NOT ADDRESSED** |
| | ONLY ONE SET OF PLANS WERE SUBMITTED. |
| | PER *106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS, |
| | SPECIAL INSPECTION AND |
| | STRUCTURAL OBSERVATION PROGRAMS, AND |
| | OTHER DATA SHALL BE SUBMITTED IN TWO OR |
| | MORE SETS WITH EACH APPLICATION FOR A |
| | PERMIT. |
| | |
| | 4. **COMMENT NOT ADDRESSED DUE TO ONLY ONE SET OF |
| | PLANS BEING SUBMITTED** |
| | SUBMITTED PLANS WERE NOT SEALED BY ENGINEER OF RECORD. |
| | PER *FAC-61G15-23.002 ANS *FS 471.025, SEAL SIGNATURE |
| | AND DATE SHALL BE AFFIXED. |
| | |
| | 5. **COMMENT NOT ADDRESSED** |
| | PER FBC PLUMBING TABLE 403.1, R-4: A DRINKING FOUNTAIN |
| | (1 PER 100) AND 1 SERVICE SINK ARE REQUIRED FOR AN |
| | R-4. |
| | |
| | 6. **COMMENT NOT ADDRESSED, SEE NOTE BELOW COMMENT** |
| | SHEET A-5 SANITARY ISOMETRIC RISER DIAGRAM: THE |
| | RELOCATED WASHING MACHINE MUST DISCHARGE DOWNSTREAM OF |
| | THE WET VENTED BATHROOM GROUP. PER * 909.1, WET VENT |
| | PERMITTED. |
| | NOTE: THE RESUBMITTED PLAN HAS DELETED THE REQUIRED |
| | SANITARY RISER DIAGRAM FOR THE RELOCATED WASHING |
| | MACHINE, ALSO THE REQUIRED DRINKING FOUNTAIN AND |
| | SERVICE SINK WILL NEED TO BE ON THE SANIATRY RISER |
| | DIAGRAM. |
| | |
| | 7. **COMMENT NOT ADDRESSED** |
| | PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3, PLUMBING: |
| | AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS REQUIRED |
| | FOR THE PROPOSED WORK (WASHING MACHINE AND THE REQUIRED |
| | DRINKING FOUNTAIN AND SERVICE SINK PER TABLE *403.1 |
| | R-4) FOR BOTH THE HOT AND COLD WATER INDICATING THE |
| | PIPE SIZES, VALVE LOCATIONS, LOCATION OF THE WATER |
| | SUPPLY LINE WITH BACKFLOW PREVENTER **608, THERMAL |
| | EXPANSION CONTROL FOR THE WATER HEATER **607.3, AND |
| | LOCATION OF THE WATER-HAMMER ARRESTORS WHERE QUICK |
| | CLOSING VALVES ARE UTILIZED (EXAMPLES=WASHING MACHINES, |
| | DISHWASHERS, ICE MAKERS) **604.9. |
| | |
| | 8. **COMMENT NOT ADDRESSED, ELEVATION DETAILS REQUIRED |
| | AND CLEAR FLOOR SPACE NEEDS TO INDICATED ON THE FLOOR |
| | PLAN AS WELL AS WHEELCHAIR TURNING SPACE** |
| | THE FOLLOWING ARE REQUIRED FOR THE ACCESSIBLE FIXTURES |
| | PER CHAPTER 11 FLORIDA ACCESSIBILTY CODE: **NOTE: |
| | BACKING SHALL BE INDICATED FOR GRAB BARS ON THE |
| | REQUIRED ELEVATION DETAILS. |
| | |
| | **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS |
| | (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING |
| | INFORMATION) |
| | 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET |
| | MAXIMUM. |
| | 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN |
| | TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT |
| | OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN |
| | ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3" |
| | OF THE FRONT OF FOUNTAIN. |
| | 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE |
| | MOUNTED NEAR FRONT EDGE. |
| | 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR |
| | SPACE. |
| | 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS |
| | PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| | WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| | IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE |
| | TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS |
| | CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR |
| | BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED |
| | ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). |
| | |
| | **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH |
| | THE FOLLOWING INFORMATION) |
| | 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.3 |
| | HEIGHT. 17" TO 19". |
| | 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C |
| | 36" LONG. |
| | 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44" |
| | HIGH. |
| | 11-4.16.6 DISPENSERS. SEE FIGURE 29(B). |
| | |
| | **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL |
| | REQUIRED WITH THE FOLLOWING INFORMATION) |
| | 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR |
| | COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE |
| | FIGURE 31) |
| | 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND |
| | A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE |
| | 32) |
| | 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO |
| | PROTECT AGAINST CONTACT. |
| | 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND |
| | ELECTRONICALLY CONTROLLED ARE EXAMPLES. |
| | 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F. |
| | |
| | **11-4.21 SHOWER STALLS (ELEVATION DETAIL REQUIRED WITH |
| | THE FOLLOWING INFORMATION) |
| | 11-4.21.2 SIZE AND CLEARANCES. (SEE FIGURES 35(A) OR |
| | (B) AND FIGURES 57 (A) OR (B) |
| | 11-4.21.3 SEAT. REQUIRED IN A 36" X 36" (17"-19" |
| | HIGH) |
| | 11-4.21.4 GRAB BARS. REQUIRED (SEE FIGURE 37) |
| | 11-4.21.5 CONTROLS. REQUIRED (SEE FIGURE 37) |
| | 11-4.21.7 CURBS. 36" X 36" MAXIMUM 1/2" CURB (NO CURB |
| | REQUIRED IN MINIMUM 30" X 60" STALLS) |
| | |
| | **THE FOLLOWING ARE NEW ITEMS THE ARE REQUIRED TO BE |
| | ADA COMPLIANT** |
| | |
| | ** 11-4.20 BATHTUBS (ELEVATION DETAIL REQUIRED WITH |
| | THE FOLLOWING INFORMATION) |
| | 11-4.20.2 FLOOR SPACE. (SEE FIGURE 33) |
| | 11-4.20.3 SEAT. REQUIRED. (SEE FIGURE 33 & 34) |
| | 11-4.20.4 GRAB BARS. REQUIRED. (SEE FIGURE 33 & 34) |
| | 11-4.20.5 CONTROLS. (SEE FIGURE 34) |
| | 11-4.20.6 SHOWER UNIT. SHOWER SPRAY UNIT WITH A HOSE |
| | MINIMUM 60" LONG USED BOTH AS A FIXED OR HAND HELD |
| | SHALL BE PROVIDED. |
| | |
| | **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE |
| | FOLLOWING INFORMATION) |
| | 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR |
| | COUNTER. |
| | 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE, |
| | AND 19" DEEP.(NO CABINET DOORS) |
| | 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP. |
| | 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR |
| | SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE |
| | SINK. |
| | 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO |
| | PROTECT AGAINST CONTACT. |
| | 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR |
| | ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS. |
| | |
| | **11-4.23 BATHROOMS, BATHING FACILITIES AND SHOWER |
| | ROOMS. |
| | 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR |
| | SPACE |
| | 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE |
| | SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR |
| | SPACE (PER 11-4.2.3) |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |