Plan Review Notes
Plan Review Notes For Permit 07060731
Permit Number 07060731
Review Stop P
Sequence Number 2
Notes
Date Text
2008-01-25 09:08:21PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 **PREVIOUS PLAN REVIEW COMMENTS NOT ADDRESSED**
  
 1. **COMMENT NOT ADDRESSED**
 THERE WAS NOT A PERMIT APPLICATION SUBMITTED FOR THE
 PROPOSED WORK WHICH IS REQUIRED BY A LICENSED
 CONTRACTOR. PER *FS489.113 PERMIT APPLICATION CAN NOT
 BE SUBMITTED BY A CORPORATION OR OWNER BUILDER.
  
 2. **COMMENT NOT ADDRESSED**
 THERE WAS NO VALUATION FOR THE PROPOSED WORK. PER
 *108.3 VALUATION MUST BE ON THE REQUIRED PERMIT
 APPLICATION FOR THE PROPOSED WORK.
  
 3. **COMMENT NOT ADDRESSED**
 ONLY ONE SET OF PLANS WERE SUBMITTED.
 PER *106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS,
 SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A
 PERMIT.
  
 4. **COMMENT NOT ADDRESSED DUE TO ONLY ONE SET OF
 PLANS BEING SUBMITTED**
 SUBMITTED PLANS WERE NOT SEALED BY ENGINEER OF RECORD.
 PER *FAC-61G15-23.002 ANS *FS 471.025, SEAL SIGNATURE
 AND DATE SHALL BE AFFIXED.
  
 5. **COMMENT NOT ADDRESSED**
 PER FBC PLUMBING TABLE 403.1, R-4: A DRINKING FOUNTAIN
 (1 PER 100) AND 1 SERVICE SINK ARE REQUIRED FOR AN
 R-4.
  
 6. **COMMENT NOT ADDRESSED, SEE NOTE BELOW COMMENT**
 SHEET A-5 SANITARY ISOMETRIC RISER DIAGRAM: THE
 RELOCATED WASHING MACHINE MUST DISCHARGE DOWNSTREAM OF
 THE WET VENTED BATHROOM GROUP. PER * 909.1, WET VENT
 PERMITTED.
 NOTE: THE RESUBMITTED PLAN HAS DELETED THE REQUIRED
 SANITARY RISER DIAGRAM FOR THE RELOCATED WASHING
 MACHINE, ALSO THE REQUIRED DRINKING FOUNTAIN AND
 SERVICE SINK WILL NEED TO BE ON THE SANIATRY RISER
 DIAGRAM.
  
 7. **COMMENT NOT ADDRESSED**
 PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3, PLUMBING:
 AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS REQUIRED
 FOR THE PROPOSED WORK (WASHING MACHINE AND THE REQUIRED
 DRINKING FOUNTAIN AND SERVICE SINK PER TABLE *403.1
 R-4) FOR BOTH THE HOT AND COLD WATER INDICATING THE
 PIPE SIZES, VALVE LOCATIONS, LOCATION OF THE WATER
 SUPPLY LINE WITH BACKFLOW PREVENTER **608, THERMAL
 EXPANSION CONTROL FOR THE WATER HEATER **607.3, AND
 LOCATION OF THE WATER-HAMMER ARRESTORS WHERE QUICK
 CLOSING VALVES ARE UTILIZED (EXAMPLES=WASHING MACHINES,
 DISHWASHERS, ICE MAKERS) **604.9.
  
 8. **COMMENT NOT ADDRESSED, ELEVATION DETAILS REQUIRED
 AND CLEAR FLOOR SPACE NEEDS TO INDICATED ON THE FLOOR
 PLAN AS WELL AS WHEELCHAIR TURNING SPACE**
 THE FOLLOWING ARE REQUIRED FOR THE ACCESSIBLE FIXTURES
 PER CHAPTER 11 FLORIDA ACCESSIBILTY CODE: **NOTE:
 BACKING SHALL BE INDICATED FOR GRAB BARS ON THE
 REQUIRED ELEVATION DETAILS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.3
 HEIGHT. 17" TO 19".
 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C
 36" LONG.
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE
 FIGURE 31)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F.
  
 **11-4.21 SHOWER STALLS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.21.2 SIZE AND CLEARANCES. (SEE FIGURES 35(A) OR
 (B) AND FIGURES 57 (A) OR (B)
 11-4.21.3 SEAT. REQUIRED IN A 36" X 36" (17"-19"
 HIGH)
 11-4.21.4 GRAB BARS. REQUIRED (SEE FIGURE 37)
 11-4.21.5 CONTROLS. REQUIRED (SEE FIGURE 37)
 11-4.21.7 CURBS. 36" X 36" MAXIMUM 1/2" CURB (NO CURB
 REQUIRED IN MINIMUM 30" X 60" STALLS)
  
 **THE FOLLOWING ARE NEW ITEMS THE ARE REQUIRED TO BE
 ADA COMPLIANT**
  
 ** 11-4.20 BATHTUBS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.20.2 FLOOR SPACE. (SEE FIGURE 33)
 11-4.20.3 SEAT. REQUIRED. (SEE FIGURE 33 & 34)
 11-4.20.4 GRAB BARS. REQUIRED. (SEE FIGURE 33 & 34)
 11-4.20.5 CONTROLS. (SEE FIGURE 34)
 11-4.20.6 SHOWER UNIT. SHOWER SPRAY UNIT WITH A HOSE
 MINIMUM 60" LONG USED BOTH AS A FIXED OR HAND HELD
 SHALL BE PROVIDED.
  
 **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR
 COUNTER.
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.(NO CABINET DOORS)
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 **11-4.23 BATHROOMS, BATHING FACILITIES AND SHOWER
 ROOMS.
 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR
 SPACE
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved