| | *** DENIED 2ND REVIEW *** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW MUST |
| | HAVE A PERMIT APPLICATION SUBMITTED BY A LICENSED |
| | CONTRACTOR. MAY NOT PERFORM WORK AS OWNER/BUILDER UNDER |
| | FS 489. |
| | |
| | 2) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW PLEASE |
| | BE SURE THE APPLIED VALUED FOR THE SCOPE OF WORK SHOWN |
| | IS BASED ON ALL LABOR, MATERIALS, EQUIPMENT ETC EVEN IF |
| | ANY ARE OWNER SUPPLIED. |
| | |
| | 3) NOTE: PLEASE SEE THE SMOKE DETECTOR SHOWN IN THE |
| | MIDDLE OF THE FAMILY ROOM IS ALSO NOTED AS BEING A |
| | SMOKE ALARMS. PLEASE SEE NFPA-72 DEFINITIONS AS PLANS |
| | SHOW A LOW VOLTAGE FIRE ALARM SYSTEM BEING INSTALLED. |
| | |
| | 4) NOTE: PLEASE SEE THE NEW PANELS SUBMITTED ARE |
| | UNCLEAR IN THE FACT THAT PANEL *A* WHICH IS SHOWN ON |
| | THE INSIDE OF THE HOUSE IS SHOWN FEEDING PANEL *B* |
| | WHICH IS OUTSIDE NEXT TO METER. IS THIS CORRECT? OR ARE |
| | PANELS THE OTHER WAY? |
| | PLEASE CLARIFY. |
| | |
| | 5) NOTE: PLEASE SHOW WHICH CIRCUITS ARE NEW ON PANEL |
| | SCHEDULE AND WHICH ARE EXISTING. PLEASE EXAMPLE PLEASE |
| | SEE ROOMS WHICH NOTE NEW ARC FAULT PROTECTION ON |
| | CIRCUITS HOWEVER CIRCUITS IN PANEL SCHEDULE ARE NOT |
| | NOTED. |
| | PLEASE SEE FOR EXAMPLE RANGE ON PLANS APPEARS TO BE |
| | NEW. PLEASE SEE THE HALLWAY IN THE MAIN AREA OF HOUSE |
| | SHOWS A NEW RECEPTACLE AND LT IN ATTIC HOWEVER HALLWAY |
| | ALSO SHOWS ANOTHER NEW RECEPTACLE IN WHAT APPEARS TO BE |
| | THE MIDDLE OF THE CEILING. |
| | |
| | 6) NOTE: PLEASE SEE KITCHEN COUNTER SPACE WITH NO GFI |
| | RECEPTACLE(S) MEETING 210.52C1 |
| | PLEASE SEE TWO REDLINED AREAS. |
| | IF THESE ARE NOT EXISTING MEETING MINIMUM CODE SPACING |
| | , NEW WILL BE REQUIRED. |
| | |
| | ** PLEASE SEE THAT SOME OF THESE ITEMS ARE ITEMS WHICH |
| | CAN BE REDLINED HOWEVER THE PERMIT APPLICATION HAS NOT |
| | YET BEEN APPLIED FOR BY LICENSED CONTRACTOR. |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS AND IF THERE ARE |
| | ANY QUESTIONS, PLEASE CONTACT THIS REVIEWER. |
| | |
| | |