| 2008-01-29 14:07:28 | BUILDING PLAN REVIEW |
| | PERMIT: 07060731 |
| | ADD: 226 E ALHAMBRA PLACE |
| | CONT: O/BOWNER- REGIONAL PROPERTIES |
| | TEL: (561)891-0705ALAN LIPTON |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT.IFYOUR PROJECT WILL REQUIRE A |
| | RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD |
| | BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE |
| | SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT |
| | ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM |
| | BEACH ADMINISTRATIVE CODE. NOTE ONLY ONE SET OF SIGNED |
| | AND SEALED SET OF PLANS WERE SUBMITTED. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE2007 SUPPLEMENTS PLEASE REVISE THE |
| | BUILDING CODE STATEMENT TO REFLECT THE 2007 |
| | SUPPLEMENTS. |
| | |
| | 1F) PLANS ALSO NEED TO REFLECT 2004 EXISTING BUILDING |
| | CODE W/ 2007 SUPPLEMENTS UNDER CHAPTER 8 CHANGE OF |
| | OCCUPANCY THIS SHALL ALSO BE NOTED ON PLANS. |
| | |
| | 1G)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 2)THE PERMIT APPLICATION INDICATES WORK TO BE |
| | COMPLETED UNDER THIS PERMIT BY A OWNER/ BUILDER. OWNER |
| | / BUILDERS CAN ONLY WORK ON A R-3 RESIDENCE, SINGLE |
| | FAMILY |
| | RESIDENCE. THE SECOND ISSUE WITH THE OWNER/ BUILDER |
| | PERMIT IS A COMPANY OWNS THE RESIDENCE NOT AN |
| | INDIVIDUAL PLEASE SEE FL S S 489.103 EXEMPTIONS(7). |
| | A CGC, CBC OR RESIDENTIAL CONTRACTOR MAY APPLY FOR |
| | PERMIT, A NOTIRIZED LETTER FROM THE OWNER TRANSFERRING |
| | THE PERMIT, FEES AND PLANS TO THE NEW CONTRACTOR WILL |
| | BE REQUIED. THERE IS A $100.00 FEE FOR THE TRANSFER OF |
| | OWNERSHIP OF THE PERMIT. THE NEW CONTRACTOR WILL NEED |
| | TO FILL OUT A NEW PERMIT APPLICATION, IF THE QUALIFIER |
| | FOR THE SUB-CONTRACTORS SIGNS ON MEP THESE WILL BE NO |
| | FEE PERMITS. |
| | |
| | 3)EXISTING BUILDING CODE, : |
| | A) TABLE 812.4.1 HAZARD CATEGORIES GOES TO A HIGHER |
| | HAZARD WHICH ENVOKES CHAPTER 10 FBC. |
| | B) 806.1ACCESSIBILITY IN ALL PORTIONS OFBUILDINGS |
| | UNDERGOING A CHANGE IN OCCUPANCY CLASSIFICATION SHALL |
| | COMPLY WITH CHAPTER 11 OF THE FBC, BUILDING |
| | ACCESSIBLE BATHROOMS 11-4.16, 11-4.19, 11-4.20, |
| | 11-4.21,& 11-4.23. |
| | ACCESSIBLE KITHCEN-SINK 11-4.24 |
| | ACCESSIBLE KITHEN - MICROWAVE SIDE APPROACH REACH |
| | RANGES11-4.27.3. |
| | 11-9.5(1) ALL PUBLIC AND COMMON USE AREAS SHALL |
| | COMPLY WITH SECTION 11-4 NEW CONSTRUCTION. AT LEAST ONE |
| | OF EACH TYPE AMENITY( SUCH AS WASHER, DRYERS AND |
| | SIMILAR EQUIPMENT INSTALLED FOR THE USE OF OCCUPANTS) |
| | IN EACH COMMON AREA SHALL BE ACCESSIBLE AND SHALL |
| | LOCATE ON AN ACCESSIBLE ROUTE TO ANY ACCESSIBLE UNIT OR |
| | SLEEPING ACCOMMODATION. |
| | |
| | 4) SHEET 1 DEMO NOTE 4 INDICATES THE REMOVAL OF DOORS, |
| | SEE EXISTING BUILDING CODE SECTION 812.3.2 -R-4THE |
| | FOLLOWING REQUIREMENTS ARE TO BE MET. |
| | A) CORRIDOR DOORS SHALL COMPLY WITH 605.5.1 AND |
| | 605.5.2 EXISTING BUILDING CODE |
| | B) FIRE ALARMS AND DETECTION SYSTEMS SHALL COMPLY |
| | WITH 604.4. |
| | |
| | 5)THE PRODUCT APPROVALS SUBMITTED ARE NOT TESTED FOR |
| | LARGE MISSLE IMPACT RESISTANCE. 1609.1.4 PROTECTION OF |
| | OPENINGS IN WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING |
| | THAT RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET |
| | (18.3 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS |
| | AND THE BALANCE OF GLAZED OPENINGS IN THE REST OF THE |
| | BUILDING SHALL BE ASSUMED TO BE ZERO UNLESS SUCH |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE IS IMPACT |
| | RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT |
| | COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E |
| | 1886 ANDASTM E 1996, OR MIAMI-DADE TAS 201, 202 AND |
| | 203 REFERENCED THEREIN AS FOLLOWS: 1. GLAZED OPENINGS |
| | LOCATED WITHIN 30 FEET (9.1 M) OF GRADE SHALL MEET THE |
| | REQUIREMENTS OF THE LARGE MISSILE TEST. 2.GLAZED |
| | OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) ABOVE GRADE |
| | SHALL MEET THE PROVISIONS OF THE SMALL MISSILE TEST. |
| | PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| | SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND |
| | MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING FBC |
| | 1609.1.4. |
| | STORM SHUTTES WILL BE REQUIRED, INDICATE AREA WHERE THE |
| | STORM SHUTTERS WILL BE STORED AND SECURED WHEN NOT IN |
| | USE.FL BLD CODE 2001 SECTION 103.6, 1609.1.4, 1714.5 |
| | & 3401.7.2.4. PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY |
| | HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT |
| | STORM BAR REINFORCING REQUIREMENTS, WALL PRESSURE |
| | ZONES, SLAT TYPES, ETC., SHALL BESUBMITTED AT TIME OF |
| | PERMIT APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | 6)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR |
| | OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) CASEMENTPGT WINDOWS*** |
| | B) SINGLE HUNG PGT WINDOWS *** |
| | C) NEW FRONT DOOR- NO REPORT SUBMITTED |
| | D) STORM SHUTTERS- NO REPORT |
| | |
| | **** NOTE THE NOA'S SUBMITTED DO NOT HAVE THE REQUIRED |
| | FLORIDA COVERSHEET, NOTE THESE OLDER NOA'S WERE BEFORE |
| | THE 2004 FBC AND MAY HAVE TOOK THE 1 1/3RD INCREASES IN |
| | THE FASTENERS(STEEL).SEE CALCULATIONS WERE BEFORE THE |
| | 2004 FBC ENACTMENT DATE OF 10-01-05. 1605.3.1.1. |
| | |
| | 7)PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 8)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE |
| | APPLICABLE. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |