| 2007-11-06 13:33:46 | *****DENIED***** |
| | |
| | |
| | 1.ONLY ONE PLAN SET WAS SUBMITTED FOR REVIEW.PLEASE |
| | BE ADVISED THAT AT LEAST TWO SETS OF PLANS ARE REQUIRED |
| | FOR REVIEW.WHEN THE PERMIT HAS BEEN ISSUED, ONE SET |
| | OF THE REVIEWED AND APPROVED CONSTRUCTION |
| | DOCUMENTS/PLANS SHALL BE RETAINED IN THE FILES OF THE |
| | CONSTRUCTION SERVICES DEPARTMENT. |
| | |
| | 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 3.BE ADVISED THAT NFPA 101 - 2003 EDITION DOES NOT |
| | RECOGNIZE GROUP HOMES;THEREFORE LIST THE OCCUPANCY |
| | TYPE FOR THIS PROJECT (RESIDENTIAL, NEW DAY-CARE, OR |
| | NEW RESIDENTIAL BOARD AND CARE - SMALL FACILITY) TO |
| | FURTHER BASE THE FIRE REVIEW.ON SHEET A-5, OCCUPANCY |
| | CLASSIFICATION OF BUSINESS IS INCORRECT. |
| | |
| | 4.IF THE OCCUPANCY IS OTHER THAN RESIDENTIAL, ADDRESS |
| | NUMBERS (AS PER WEST PALM BEACH CODE) SHALL BE NO LESS |
| | THAN 6" IN HEIGHT AND NO LESS THAN 1" IN STROKE. |
| | DISPLAY/SHOW THE ADDRESS NUMBER ON THE APPROPIATE |
| | EXTERIOR ELEVATION (SHEET A-3) WHICH FRONTS ALHAMBRA |
| | PLACE. |
| | |
| | 5.IN THE FIRE ALARM RISER SHOWN ON SHEET A-5, TEN |
| | (10) SMOKE ALARM (SA) DEVICES ARE LISTED HOWEVER, THE |
| | LIFE SAFETY/FIRE ALARM PLAN ONLY ILLUSTRATES NINE (9) |
| | SUCH DEVICES. |
| | |
| | 6.BATHROOM DOORS SHALL BE AT LEAST 24" WIDE AND SHALL |
| | BE DESIGNED TO ALLOW OPENING FROM THE OUTSIDE DURING AN |
| | EMERGENCY WHEN LOCKED. |
| | |
| | 7.EVERY CLOSET DOOR LATCH SHALL BE READILY OPENED |
| | FROM THE INSIDE. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS |
| | ADDRESSED |
| | |
| | |