Plan Review Notes For Permit 07060731
Permit Number 07060731
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-11-06 13:33:46*****DENIED*****
  
  
 1.ONLY ONE PLAN SET WAS SUBMITTED FOR REVIEW.PLEASE
 BE ADVISED THAT AT LEAST TWO SETS OF PLANS ARE REQUIRED
 FOR REVIEW.WHEN THE PERMIT HAS BEEN ISSUED, ONE SET
 OF THE REVIEWED AND APPROVED CONSTRUCTION
 DOCUMENTS/PLANS SHALL BE RETAINED IN THE FILES OF THE
 CONSTRUCTION SERVICES DEPARTMENT.
  
 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 3.BE ADVISED THAT NFPA 101 - 2003 EDITION DOES NOT
 RECOGNIZE GROUP HOMES;THEREFORE LIST THE OCCUPANCY
 TYPE FOR THIS PROJECT (RESIDENTIAL, NEW DAY-CARE, OR
 NEW RESIDENTIAL BOARD AND CARE - SMALL FACILITY) TO
 FURTHER BASE THE FIRE REVIEW.ON SHEET A-5, OCCUPANCY
 CLASSIFICATION OF BUSINESS IS INCORRECT.
  
 4.IF THE OCCUPANCY IS OTHER THAN RESIDENTIAL, ADDRESS
 NUMBERS (AS PER WEST PALM BEACH CODE) SHALL BE NO LESS
 THAN 6" IN HEIGHT AND NO LESS THAN 1" IN STROKE.
 DISPLAY/SHOW THE ADDRESS NUMBER ON THE APPROPIATE
 EXTERIOR ELEVATION (SHEET A-3) WHICH FRONTS ALHAMBRA
 PLACE.
  
 5.IN THE FIRE ALARM RISER SHOWN ON SHEET A-5, TEN
 (10) SMOKE ALARM (SA) DEVICES ARE LISTED HOWEVER, THE
 LIFE SAFETY/FIRE ALARM PLAN ONLY ILLUSTRATES NINE (9)
 SUCH DEVICES.
  
 6.BATHROOM DOORS SHALL BE AT LEAST 24" WIDE AND SHALL
 BE DESIGNED TO ALLOW OPENING FROM THE OUTSIDE DURING AN
 EMERGENCY WHEN LOCKED.
  
 7.EVERY CLOSET DOOR LATCH SHALL BE READILY OPENED
 FROM THE INSIDE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW