| Date |
Text |
| 2007-10-23 14:57:30 | |
| | |
| | ***DENIED *** |
| | |
| | 1) NOTE: PLEASE SEE NO PERMIT APPLICATION WAS SUBMITTED |
| | FOR SCOPE OF WORK WHICH IS REQUIRED TO BE DONE BY A |
| | LICENSED CONTRACTOR. THE PERMIT AS APPLIED MAY NOT BE |
| | DONE BY A CORPORATION, OWNER BUILDER, ETC AS STATED IN |
| | FS 489.113 |
| | |
| | 2) NOTE: PLEASE SEE A VALUATION FOR THE COMPLETE SCOPE |
| | OF WORK MUST BE STATED AND APPLIED. |
| | FBC 108.3 |
| | |
| | 3) NOTE: PLEASE SEE THAT ONLY ONE SET OF PLANS WAS |
| | SUBMITTED WHEN A MINIMUM OF TWO SETS OF ALL DOCUMENTS |
| | ARE REQUIRED. |
| | PLEASE SEE FBC 106.1 |
| | |
| | 4) NOTE: PLEASE SEE THE SINGLE SET OF PLANS SUBMITTED |
| | ARE IN FACT ARE PHOTO-COPIES OF PLANS WHICH APPEARED TO |
| | BE SIGNED, DATED AND SEALED BY AN ENGINEER. |
| | PLEASE SUBMIT ORIGINAL SIGNED, DATED AND SEALED PLANS |
| | BY THE DESIGNER OF RECORD AS REQUIRED PER FAC |
| | 61G15-23.002 AND FS 471.025 |
| | |
| | 5) NOTE: PLEASE SEE THE PLANS CALL FOR NEW CIRCUITS IN |
| | BATHROOMS WHICH ARE SHOWN AS #14 AWG. |
| | PLEASE SEE 210.52D, 210.11C3 AS #14 IS NOT SUFFICIENT |
| | SIZE. |
| | |
| | 6) NOTE: PLEASE SEE THE PLANS AND FIRE ALARM RISER |
| | CALLS FOR SA WHICH IS FOR SMOKE ALARMS. PLEASE SEE |
| | HOWEVER THE NOTE ON PLANS MENTIONS SMOKE DETECTORS. |
| | PLEASE KNOW AS THE PLAN CONTAINS HORN AND STROBE |
| | DEVICES FOR ALARM AND SOUNDING THESE DEVICES WOULD MOST |
| | LIKELY BE SD FOR SMOKE DETECTORS. SMOKE DETECTORS BY |
| | DEFINITION IN NFPA-72 ARE DEVICES WHICH ONLY DETECT |
| | SMOKE AND DO NOT SOUND AN ALARM. |
| | SMOKE ALARM DEVICES BY DEFINITION ACTUALLY DETECT AND |
| | SOUND AN ALARM. |
| | THESE DO NOT CORRELATE WITH PLANS. |
| | PLEASE REVISE AND ADJUST. |
| | |
| | 7) NOTE: PLEASE PROVIDE A PANEL SCHEDULE FOR NEW |
| | DEDICATED CIRCUITS AS REQUIRED. |
| | NEC 408.4, FBC 106.3.5.1.2 |
| | |
| | 8) NOTE: PLEASE KNOW THE PANEL SCHEDULE IS TO INCLUDED |
| | NEW DEDICATED CIRCUIT REQUIRED FOR FIRE ALARM PANEL |
| | WHICH IS REQUIRED TO BE MARKED/LABELED/LOCKED OFF FOR |
| | PROTECTION. |
| | PLEASE SEE NFPA-72 4.4.1.4.1 |
| | |
| | 9) NOTE: PLEASE PROVIDE AND CLARIFY INFORMATION AND |
| | SCOPE OF WORK AS APPLIED. |
| | PLANS CALL FOR BUSINESS OCCUPANCY BUT ALSO R-4? |
| | PLEASE PROVIDE INFORMATION FROM STATE REGARDING WHAT |
| | TYPE OF GROUP HOME ETC THIS WILL BE. |
| | PLEASE KNOW AT THIS TIME THERE MAY BE SOME COMMENTS |
| | WHICH CAN NOT BE MADE DUE TO INFORMATION AND/OR |
| | CLARIFICATION NEEDED. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |