| 2007-11-02 11:56:17 | CONSTRUCTION SERVICES DEPARTMENT |
| | 200 SECOND STREET, 3RD FLOOR, |
| | WEST PALM BEACH, FLORIDA33401 |
| | TEL:561-805-6713FAX:561-805-6731 |
| | |
| | JAMES JOHNSTON, |
| | BUILDING PLAN EXAMINER II |
| | E-MAIL:JJOHNSTON @WPB.ORG |
| | |
| | |
| | PERMIT NO07060731 |
| | PROJECT GROUP HOME |
| | ADDRESS226ALHAMBRA PLACE |
| | DATE NOVEMBER 1, 2007 |
| | |
| | |
| | BUILDINGPLANREVIEW |
| | |
| | FLORIDA BUILDING CODES 2004 W REVISIONS |
| | |
| | |
| | FLORIDA STATUE713.13NOTICE OF COMMENCEMENT FILE |
| | NOTICE WITH THE CLERK OF COURT RECORDING DIVISION. IF |
| | THE WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED |
| | WITHIN 90 DAYS OF FILING THE NOTICE WILL BECOME NULL |
| | AND VOID. SUBMIT THE NOTICE AT THE TIME OF PERMIT |
| | ISSUANCE AND POST A COPY AT THE JOB SITE BEFORE THE |
| | FIRST INSPECTION. |
| | COMMENT-FOR YOUR INFORMATION |
| | |
| | |
| | 1 |
| | CORRECTION SUBMITTAL |
| | WHEN RE-SUBMITTINGCORRECTED PLANS FOR PERMITTING, |
| | PLEASEREMOVE AND REPLACE ANY SHEETS AS NECESSARY. |
| | INCLUDE A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE REVISION |
| | MADE. |
| | |
| | IDENTIFY THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES |
| | CAN BE FOUND AND INCLUDE THE OLD SHEETS IN THE |
| | RE-SUBMITTAL |
| | PACKAGE FOR THE PLAN REVIEWER?S REFERENCE. |
| | |
| | COMMENT-FOR YOUR INFORMATION |
| | |
| | |
| | 2 |
| | FLORIDA STATUE471.025ENGINEER SEAL |
| | ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS, OR |
| | |
| | DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND BEING |
| | FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS |
| | PROVIDED |
| | TO THE OWNER OR THE OWNER'S REPRESENTATIVE SHALL BE |
| | SIGNED |
| | BY THE LICENSEE, DATED, AND SEALED WITH SAID SEAL. SUCH |
| | SIGNATURE, DATE, AND SEAL SHALL BE EVIDENCE OF THE |
| | AUTHENTICITY OF THAT TO WHICH THEY ARE AFFIXED. |
| | |
| | COMMENT-THE ENGINEER SHALL SEAL EACH SHEET OF THE |
| | DRAWINGS |
| | IN THE TITLE BLOCK AS REQUIRED BY THIS STATUE. |
| | |
| | |
| | 3 |
| | FLORIDA STATUE481.219CERTIFICATION OF PARTNERSHIPS, |
| | LIMITED LIABILITY COMPANIES, AND CORPORATIONS. |
| | |
| | ARCHITECTURAL SERVICES |
| | FOR THE PURPOSES OF THIS SECTION, A CERTIFICATE OF |
| | AUTHORIZATION SHALL BE REQUIRED FOR A CORPORATION, |
| | LIMITED LIABILITY COMPANY, PARTNERSHIP, OR PERSON |
| | PRACTICING UNDER A FICTITIOUS NAME, OFFERING |
| | ARCHITECTURAL |
| | SERVICES TO THE PUBLIC JOINTLY OR SEPARATELY. |
| | |
| | INTERIOR DESIGN SERVICES |
| | FOR THE PURPOSES OF THIS SECTION, A CERTIFICATE OF |
| | AUTHORIZATION SHALL BE REQUIRED FOR A CORPORATION, |
| | LIMITED LIABILITY COMPANY, PARTNERSHIP, OR PERSON |
| | OPERATING |
| | UNDER A FICTITIOUS NAME, OFFERING INTERIOR DESIGN |
| | SERVICES |
| | TO THE PUBLIC JOINTLY OR SEPARATELY. |
| | |
| | COMMENT- |
| | THE FIRM MCARCHITECTURE SHALL |
| | PROVIDE THEIR STATE OF FLORIDA CERTIFICATE OF |
| | AUTHORIZATION NUMBER IN THE TITLE BLOCK . |
| | |
| | |
| | |
| | 4 |
| | 481.221SEALS; DISPLAY OF CERTIFICATE NUMBER |
| | ALL FINAL CONSTRUCTION DOCUMENTS AND INSTRUMENTS OF |
| | SERVICE WHICH INCLUDE DRAWINGS, PLANS, SPECIFICATIONS, |
| | |
| | OR REPORTS PREPARED OR ISSUED BY THE REGISTERED |
| | ARCHITECT |
| | AND BEING FILED FOR PUBLIC RECORD SHALL BEAR THE |
| | SIGNATURE |
| | AND SEAL OF THE REGISTERED ARCHITECT WHO PREPARED OR |
| | APPROVED THE DOCUMENT AND THE DATE ON WHICH THEY WERE |
| | SEALED. |
| | THE SIGNATURE, DATE, AND SEAL SHALL BE EVIDENCE |
| | OF AUTHENTICITY. |
| | |
| | COMMENT- |
| | THE INDIVIDUAL MAYORICHAVERRA MUST PROVIDE |
| | THEIR SEAL DATE AND SIGNATURE IN COMPLIANCE WITH THIS |
| | FLORIDA STATUE |
| | |
| | |
| | 5 |
| | 481.221SEALS; DISPLAY OF CERTIFICATE NUMBER |
| | THE REGISTERED INTERIOR DESIGNER AND BEING FILED FOR |
| | PUBLIC |
| | RECORD SHALL BEAR THE SIGNATURE AND SEAL OF THE |
| | REGISTERED |
| | INTERIOR DESIGNER WHO PREPARED OR APPROVED THE |
| | DOCUMENT |
| | |
| | AND THE DATE ON WHICH THEY WERE SEALED. THE SIGNATURE, |
| | |
| | DATE, AND SEAL SHALL BE EVIDENCE OF AUTHENTICITY. |
| | |
| | COMMENT- |
| | THE INDIVIDUAL MAYORICHAVERRA MUST PROVIDE |
| | THEIR SEAL DATE AND SIGNATURE IN COMPLIANCE WITH THIS |
| | FLORIDA STATUE |
| | |
| | COMMENT- |
| | PLEASE NOTE THAT THE INDIVIDUAL MAYORI CHAVERRA |
| | ORMCARCHITECTURE IS NOT ON FILE WITH THE STATE OF |
| | FLORIDA |
| | DBPRFOR ARCHITECTURE OR INTERIOR DESIGN. |
| | IF THIS INDIVIDUAL IS NOT LICENSED BY THE STATE OF |
| | FLORIDA |
| | ALL REFERENCE TO THEIR NAME MUST BE REMOVED ON THE |
| | PLAN |
| | |
| | |
| | |
| | 6 |
| | FENCE REPAIR |
| | |
| | COMMENT |
| | FENCE WORK WILL REQUIRE A SEPARATE PERMIT |
| | |
| | |
| | 7 |
| | FBCTABLE 601BUILDING FIRE RESISTANT RATING THIS |
| | BUILDING HAS BEEN RATED III B BY THE DESIGN |
| | PROFESSIONAL AND THEREFORE SHALLREQUIRE A MORE |
| | STRINGENT CODE THAN THEV B RATINGWHICH IS |
| | APPLICABLE |
| | FOR THIS PROJECT |
| | |
| | COMMENT |
| | 1EXTERIOR BEARING WALLS SHALL BE RATED FOR 2 HOURS |
| | |
| | 2FIRE RETARDANT TREATED WOOD FRAMING SHALL BE |
| | ALLOWED |
| | IN EXTERIOR FRAMINGSECT2303.2 |
| | |
| | 3PLEASE COORDINATE THE BUILDING INFORMATION ON A-2 |
| | REFERENCING OCCUPANCY ETC. WITH THE BUILDING |
| | INFORMATION ON A-1. |
| | |
| | |
| | 8 |
| | 704.5 FIRE-RESISTANCE RATINGS. |
| | EXTERIOR WALLS SHALL BE FIRE-RESISTANCE RATED IN |
| | ACCORDANCE |
| | WITH TABLES 601 AND 602 . |
| | THE FIRE-RESISTANCE RATING OF EXTERIOR WALLS WITH A |
| | FIRE |
| | SEPARATION DISTANCE OF GREATER THAN 5 FEETSHALL BE |
| | RATED |
| | FOR EXPOSURE TO FIRE FROM THE INSIDE. |
| | |
| | COMMENT |
| | PLEASE NOTE EXTERIOR WALL RATING ON PLAN |
| | |
| | |
| | |
| | |
| | 9 |
| | |
| | 1715.4 FIRE-PROTECTION RATED GLAZING. |
| | ALL WINDOWS IN EXTERIOR WALLS SHALL HAVE A 1-1/2 HR |
| | RATING |
| | THE WINDOWS SHALL BE MANUFACTURED IN ACCORDANCE WITH |
| | NFPA- 257. |
| | DOORS SHALL HAVE A RATING OF 1-1/2 HR WITHOUT GLASS |
| | |
| | 2715.4.5 INSTALLATION. |
| | FIRE-PROTECTION-RATED GLAZING SHALL BE IN THE FIXED |
| | POSITION |
| | OR BE AUTOMATIC-CLOSING AND SHALL BE INSTALLED IN |
| | APPROVED |
| | FRAMES. |
| | |
| | 3 715.4.8 EXTERIOR FIRE WINDOW ASSEMBLIES. EXTERIOR |
| | OPENINGS, OTHER THAN DOORS, REQUIRED TO BE PROTECTED BY |
| | SECTION 704.12 , WHERE LOCATED IN A WALL REQUIRED BY |
| | TABLE 602 TO HAVE A FIRE-RESISTANCE RATING |
| | |
| | OF GREATER THAN 1 HOUR, SHALL BE PROTECTED WITH AN |
| | ASSEMBLY HAVING A FIRE PROTECTION RATING OF NOT LESS |
| | THAN 1? HOURS |
| | |
| | COMMENT |
| | PLEASE PROVIDE THE PRODUCT APPROVALS |
| | WITH THE 1-1/2 HR RATING FOR THE BUILDING COMPONENTS |
| | LISTED BELOW |
| | |
| | |
| | |
| | 10 |
| | 717.2 FIREBLOCKING. |
| | IN COMBUSTIBLE CONSTRUCTION, FIREBLOCKING SHALL BE |
| | INSTALLED TO CUT OFF CONCEALED DRAFT OPENINGS (BOTH |
| | VERTICAL AND HORIZONTAL) AND SHALL FORM AN EFFECTIVE |
| | BARRIER BETWEEN FLOORS, BETWEEN A TOP STORY AND A ROOF |
| | |
| | OR ATTIC SPACE |
| | |
| | COMMENT |
| | PLEASE NOTE ON PLAN FRAMING |
| | |
| | |
| | |
| | 11 |
| | 719.2 CONCEALED INSTALLATION. |
| | INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN |
| | BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A |
| | FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450. |
| | |
| | COMMENT |
| | PLEASE PROVIDE THE INSULATION APPLICATION FOR |
| | TYPE III-B CONSTRUCTION |
| | |
| | |
| | |
| | 12 |
| | SECTION 720 |
| | PRESCRIPTIVE FIRE RESISTANCE |
| | TABLE720.1(1) |
| | MINIMUM PROTECTION OF STRUCTURAL PARTS BASED |
| | ON TIME PERIODS FOR VARIOUS NONCOMBUSTIBLE INSULATING |
| | MATERIALS |
| | |
| | COMMENT |
| | PLEASE PROVIDE THE CORRECT INSULATING |
| | MATERIALS FOR THE TWO HOUR WALLS |
| | |
| | |
| | |
| | 13 |
| | 803.4 APPLICATION. |
| | WHERE THESE MATERIALS ARE APPLIED ON WALLS, CEILINGS OR |
| | STRUCTURAL ELEMENTS REQUIRED TO HAVE A FIRE-RESISTANCE |
| | RATING OR TO BE OF NONCOMBUSTIBLE CONSTRUCTION, THEY |
| | SHALL COMPLY WITH THE PROVISIONS OF THIS SECTION. |
| | |
| | |
| | COMMENT |
| | PLEASE SEE SECTION 803 FOR APPLICATION OF THE INTERIOR |
| | ELEMENTS |
| | |
| | |
| | |
| | 14 |
| | PRODUCT APPROVALS REQUIRED |
| | FBC 1609.1.4 AND WPB ADMINISTRATIVE CODE 106.3 |
| | REGULATED BY DCA RULE 9B-72FLORIDA PRODUCT APPROVALS |
| | SUBMIT TWO COPIES OF EACH APPROVAL WITH THE FLORIDA |
| | PRODUCT APPROVAL COVER SHEET THE ARCHITECT?S / |
| | ENGINEER?S SIGNATURE AS APPLICABLE, STATING ?TO THE |
| | BEST |
| | OF THEIR KNOWLEDGE THE PRODUCT APPROVAL COMPLIES WITH |
| | THE PLANS AND SPECIFICATIONS. |
| | |
| | COMMENT |
| | PLEASE SUBMIT THE 1-1/2 HR FIRE RATED WINDOW |
| | AND DOOR PRODUCT APPROVAL. |
| | |
| | |
| | |
| | 15 |
| | 11-4.22.3 CLEAR FLOOR SPACE. |
| | AN UNOBSTRUCTED TURNING SPACE COMPLYING WITH SECTION |
| | 11-4.2.3 SHALL BE PROVIDED WITHIN AN ACCESSIBLE TOILET |
| | ROOM. |
| | THE CLEAR FLOOR SPACE AT FIXTURES AND CONTROLS, THE |
| | ACCESSIBLE ROUTE, AND THE TURNING SPACE MAY OVERLAP. |
| | |
| | COMMENT |
| | THE BATHROOM DOOR CANNOT SWING INTO THE TURNING SPACE. |
| | |
| | |
| | |
| | 16 |
| | 11-4.19 LAVATORIES AND MIRRORS. |
| | 11-4.19.2 HEIGHT AND CLEARANCES. |
| | LAVATORIES SHALL BE MOUNTED WITH THE RIM OR COUNTER |
| | SURFACE NO HIGHER THAN 34 INCHES ABOVE THE FINISH |
| | FLOOR. |
| | |
| | COMMENT |
| | KNEE CLEARANCE THAT IS AT LEAST 27 INCHES HIGH, |
| | 30 INCHES WIDE, AND 19 INCHES DEEP SHALL BE PROVIDED |
| | UNDERNEATH SINKS. |
| | PROVIDE A CLEARANCE OF AT LEAST 29 INCHES ABOVE THE |
| | FINISH FLOOR TO THE BOTTOM OF THE APRON. |
| | KNEE AND TOE CLEARANCE SHALL COMPLY WITH FIGURE 31 . |
| | |
| | |
| | |
| | 17 |
| | 11-4.20.6 SHOWER UNIT. |
| | A SHOWER SPRAY UNIT WITH A HOSE AT LEAST 60 INCHES LONG |
| | THAT CAN BE USED BOTH AS A FIXED SHOWER HEAD AND AS A |
| | HAND-HELD SHOWER SHALL BE PROVIDED. |
| | |
| | COMMENT |
| | PLEASE COMPLY |
| | |
| | |
| | |
| | 18 |
| | 11-4.21.3 SEAT. |
| | A SEAT SHALL BE PROVIDED IN SHOWER STALLS 36 INCHES BY |
| | 36 |
| | INCHES THE SEAT SHALL BE MOUNTED 17 INCHES TO 19 |
| | INCHES |
| | |
| | FROM THE BATHROOM FLOOR AND SHALL EXTEND THE FULL DEPTH |
| | OF |
| | THE STALL. |
| | IN A 36-INCH BY 36-INCH SHOWER STALL, THE SEAT SHALL BE |
| | ON |
| | THE WALL OPPOSITE THE CONTROLS. |
| | |
| | COMMENT |
| | PLEASE LOCATE THE SEAT OPPOSITE THE CONTROLS |
| | |
| | |
| | |
| | 19 |
| | 11-4.21.7 CURBS. |
| | IF PROVIDED, CURBS IN SHOWER STALLS 36 INCHES BY 36 |
| | INCHES |
| | SHALL BE NO HIGHER THAN ? INCH |
| | SHOWER STALLS THAT ARE 30 INCHES BY 60 INCHES MINIMUM |
| | SHALL NOT HAVE CURBS. |
| | |
| | COMMENT |
| | PLEASE COMPLY |