2007-08-23 14:38:03*** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED.
  
 1) NOTE:PLEASE SEE A NEUTRAL CONDUCTOR IS BEING SHOWN
 TO THE TRANSFORMER WHICH IS NOT POSSIBLE WHEN THIS IS A
 TRANSFORMER CREATING A SEPARATELY DERIVED SYSTEM.
 PLEASE VERIFY AND REVISED AS NEEDED.
 250.20, 250.30
  
 2) NOT: PLEASE SEE NO MAXIMUM TIMES ARE STATED FOR THE
 OC TYPE DEVICES AS SHOWN ON LEGEND. THIS WAS REQUESTED
 ON THE PREVIOUS REVIEW.
 13-415.1.ABC.1.1
  
 3) NOTE: PLEASE SEE THE LIGHTING POWER DENSITIES SHOWN
 ON TABLE ARE INDICATING AT LEAST FOUR LOCATIONS WHERE
 THE MAXIMUM PERMITTED WATTS PER SQ FT IS EXCEEDED BASED
 ON THE TABLES IN 13-415.2.B.
 PLEASE CLARIFY WHICH TABLE IS BEING USED.
 PLEASE SEE NO TOTAL DESIGN/ALLOWANCE IS INDICATED ON
 PLANS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  