| Plan Review Notes For Permit 07060708 |
| Permit Number |
07060708 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-08-23 14:38:03 | *** DENIED 2ND REVIEW *** | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL | | | NEED TO BE ADDRESSED. | | | | | | 1) NOTE:PLEASE SEE A NEUTRAL CONDUCTOR IS BEING SHOWN | | | TO THE TRANSFORMER WHICH IS NOT POSSIBLE WHEN THIS IS A | | | TRANSFORMER CREATING A SEPARATELY DERIVED SYSTEM. | | | PLEASE VERIFY AND REVISED AS NEEDED. | | | 250.20, 250.30 | | | | | | 2) NOT: PLEASE SEE NO MAXIMUM TIMES ARE STATED FOR THE | | | OC TYPE DEVICES AS SHOWN ON LEGEND. THIS WAS REQUESTED | | | ON THE PREVIOUS REVIEW. | | | 13-415.1.ABC.1.1 | | | | | | 3) NOTE: PLEASE SEE THE LIGHTING POWER DENSITIES SHOWN | | | ON TABLE ARE INDICATING AT LEAST FOUR LOCATIONS WHERE | | | THE MAXIMUM PERMITTED WATTS PER SQ FT IS EXCEEDED BASED | | | ON THE TABLES IN 13-415.2.B. | | | PLEASE CLARIFY WHICH TABLE IS BEING USED. | | | PLEASE SEE NO TOTAL DESIGN/ALLOWANCE IS INDICATED ON | | | PLANS. | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|