| Date |
Text |
| 2007-06-24 15:44:31 | *** UNSAT *** |
| | |
| | |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES.SOME OF THESE ARE |
| | STATED ON PLANS HOWEVER NOT ALL OR NOT ALL CURRENT PER |
| | STATE ADOPTED CODES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETSAND |
| | ARCHITECTURAL COVER SHEET FOR THIS REVIEWER AT A |
| | MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE SEE SOME OF THE CODES REFLECTED ON PLANS ARE |
| | NOT CURRENT. |
| | ** PLEASE ALSO SEE COMMENTS FROM OTHER TRADES WHICH MAY |
| | REQUESTED OTHER CODES TO BE STATED. |
| | |
| | 2) NOTE: PLEASE PROVIDE LIGHTING CONTROLS IN SEPARATE |
| | SPACES AND AREAS PER 13-415.1.ABC.1.1, .1.2. |
| | PLEASE SEE ONLY ONE OS DEVICE WAS LOCATED IN MAIN |
| | AREA. |
| | PLEASE PROVIDE LIGHTING PERFORMANCE INFORMATION PER |
| | 13-415.2. |
| | AS NOT ENERGY CALCULATIONS WERE SUBMITTED (REQUIRED?), |
| | LIGHTING INFORMATION IS STILL NEEDED. |
| | PLEASE COORDINATE LPD'S WITH A FIXTURE LEGEND TO BE |
| | PROVIDED. |
| | PLEASE BE SURE ALL TIMES ARE INDICATED FOR DEVICES |
| | CHOSEN.(ALREADY NOTED FOR OS DEVICE SHOW). |
| | |
| | 3) NOTE: PLEASE INDICATE THE LOCATION OF ALL |
| | SERVICE/TRANSFORMER EQUIPMENT. PLANS MENTIONS THE |
| | TRANSFORMER IS BEING MOVED TO ABOVE CEILING. PLEASE |
| | PROVIDE DETAIL FOR STRUCTURAL MOUNTING OF WHAT IS BEING |
| | SHOWN AS EXISTING TRANSFORMER. |
| | 110.26, 450.13 |
| | PLEASE PROVIDE GROUNDING ATTACHMENT LOCATION FOR THE |
| | GROUNDING ELECTRODE CONDUCTOR OF TRANSFORMER. |
| | 250.50, 250.20, 250.30. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |