Plan Review Notes
Plan Review Notes For Permit 07060707
Permit Number 07060707
Review Stop E
Sequence Number 8
Notes
Date Text
2009-10-10 10:00:48 
  
 ** DENIED REVIEW **
 **ORIGINALLY SUBMITTED 8/13 AND PLACED ON HOLD FOR
 ELECTRICAL REVIEW AS NEW REVISED SHEETS NEEDED TO BE
 INSERTED INTO SETS BEFORE REVIEW.
 OTHER REVISED TRADE SHEETS WERE ALSO INCLUDED WHEN
 SHEETS WERE INSERTED WHICH ARE DATED AFTER ORIGINAL
 SUBMITTED DATE. THERE WERE ALSO NEW REVISED PLUMBING
 SHEETS INSERTED AFTER THE PLUMBING REVIEW WAS DONE. NEW
 SHEETS ALSO INSERTED THIS WEEK FOR ZONING.
 ORIGINALLY SUBMITTED AS 28 REVISED SHEETS THERE IS NOW
 A TOTAL OF 47 REVISED SHEETS IN EACH SET. INCLUDING
 FIVE REVISED PLUMBING REVISED SHEETS. ADDITIONAL FEE
 FOR REVISED SHEETS WILL BE DUE.
  
 1) NOTE: AS NOTED PREVIOUSLY. THE SAME ENERGY
 CALCULATIONS AS PREVIOUSLY SUBMITTED ARE NOT REVISED
 AND ARE THE SAME AS SUBMITTED.
  
 ** PREVIOUS NOTES**
 ENERGY CALCULATIONS NOT STAMPED FOR ELECTRIC. AS STATED
 ON PREVIOUS REVIEWS. ALL SYSTEMS AND COMPONENTS IN THE
 BUILDING AND ON SAID PLANS NEED TO COORDINATE WITH THE
 INPUT DATA REPORT. AN EXAMPLE IS TAKING A CREDIT FOR
 ALL ROOMS AND SPACES IN BUILDING TO CONTAIN * CARPET
 AND RUBBER PADDING*. THE FACT THERE IS NUMEROUS AREAS
 AND LOCATIONS WITHIN BUILDING WHICH DO NOT CONTAIN THIS
 TYPE OF FLOORING. THERE ARE ALSO ROOMS AND OTHER AREAS
 SUCH AS ELECTRICAL ROOMS, MECHANICAL ROOMS, SURGERY
 ROOMS, STORAGE ROOMS ETC WHICH WILL NOT HAVE ANY CARPET
 AND RUBBER PADDING.
 SEE COMMENTS FROM OTHER TRADES. SEE FBC CHAPTER 13 AS
 THE SUBMITTED CALCULATIONS DO NOT MEET THE MINIMUM OF
 THE FLORIDA BUILDING CODE IN CHAPTER 13.
  
 2) NOTE: REVISED PLANS SUBMITTED REMOVING PHASE TWO
 SCOPE OF WORK HOWEVER REVISED CIRCUITING, LOADS AND
 PANEL SCHEDULES WERE NOT SUBMITTED OR REVISED FOR AREAS
 WHICH ARE IN THE PHASE ONE SCOPE OF WORK. THERE ARE
 SEVERAL AREAS WHICH OVER LAP FOR THE ABOVE CIRCUITING
 ETC.
 PLEASE SUBMIT REVISED PANEL SCHEDULES PER 408.4 REVISED
 PANEL SCHEDULES WERE NOT SUBMITTED AS PART OF PHASE TWO
 SCOPE OF WORK.
 PLEASE REVISE CIRCUITING AND LOADS PER NEC 220,
 220.12,220.14, 220.42 ETC
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  