Plan Review Notes For Permit 07060707
Permit Number 07060707
Review Stop E
Sequence Number 7
Notes
Date Text
2009-06-29 14:30:01** DENIED REVIEW **
  
 1) NOTE: ENERGY CALCULATIONS NOT STAMPED FOR ELECTRIC.
 AS STATED ON PREVIOUS REVIEWS. ALL SYSTEMS AND
 COMPONENTS IN THE BUILDING AND ON SAID PLANS NEED TO
 COORDINATE WITH THE INPUT DATA REPORT. AN EXAMPLE IS
 TAKING A CREDIT FOR ALL ROOMS AND SPACES IN BUILDING TO
 CONTAIN * CARPET AND RUBBER PADDING*. THE FACT THERE IS
 NUMEROUS AREAS AND LOCATIONS WITHIN BUILDING WHICH DO
 NOT CONTAIN THIS TYPE OF FLOORING. THERE ARE ALSO ROOMS
 AND OTHER AREAS SUCH AS ELECTRICAL ROOMS, MECHANICAL
 ROOMS, SURGERY ROOMS, STORAGE ROOMS ETC WHICH WILL NOT
 HAVE ANY CARPET AND RUBBER PADDING.
 SEE COMMENTS FROM OTHER TRADES. SEE FBC CHAPTER 13 AS
 THE SUBMITTED CALCULATIONS DO NOT MEET THE MINIMUM OF
 THE FLORIDA BUILDING CODE IN CHAPTER 13.
  
 2) NOTE: NO OTHER ELECTRICAL REVISIONS SUBMITTED TO
 REVIEW SAID CALCULATIONS AND COORDINATE WITH PLANS. THE
 NEW REVISED CALCULATIONS DO NOT COORDINATE WITH PLANS
 ON FILE.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  