Plan Review Notes
Plan Review Notes For Permit 07060707
Permit Number 07060707
Review Stop E
Sequence Number 4
Notes
Date Text
2008-08-27 14:03:20 
 ** DENIED4TH REVIEW **
  
  
  
  
 1) NOTE:ENERGY CALCULATIONS DO NOT COORDINATE WITH
 THE PLANS. NOT ALL EXTERIOR LIGHTS ON THE IDR AND NOT
 ALL INTERIOR LIGHTS ON THE IDR COORDINATE WITH PLANS.
 LIGHTING ON MEZZANINE LEVEL IS MISSING MANY FIXTURES.
 LIGHTS FOR *H* FIXTURES ARE MISSING SOME.
 SPOKE TO ENGINEER OF RECORD AND MECHANICAL DESIGNER AND
 WILL CORRECT CALCULATIONS. 13-415.2.ABC.1.1,.1.2,.1.3.
  
 2) NOTE: PLEASE SEE THIRD SET IS MISSING THE SIGNATURE,
 DATE AND SEAL FROM SHEET E-002.
  
 3) NOTE: STILL NEED LETTERING OF UNDERSTANDING FROM
 OWNER THAT PROJECT CO WILL BE PLACED ON HOLD UNTIL FEE
 BALANCE OF 4X FEE IS PAID IN FULL AS REQUIRED BY FS
 553.80(2)(B).
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  