Plan Review Notes
Plan Review Notes For Permit 07060707
Permit Number 07060707
Review Stop P
Sequence Number 3
Notes
Date Text
2008-05-28 15:09:13DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW: (2ND REVIEW)
  
 ******FROM PREVIOUS REVIEWS: (3RD REVIEW)
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
  
 14. SHT A-709 DETAILS 79 & 81. SHOW COMPLIANCE WITH
 SECTION 11-4.24 & ALL SUBSECTIONS. NOTE: FORWARD
 APPROACH REQUIRED ON CLEAR FLOOR SPACE AND CABINET
 DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE.
 ****RESPONSE NOTED, BUT SHT A-709 DETAILS 79 & 81 SHOW
 THE FLOOD RIM LEVEL, (COUNTER TOP), AT 3'0". PER CODE
 34" IS MAXIMUM HEIGHT ALLOWED. SECTION 11-4.24.2. ALSO
 NOT SHOWN IS THE SINK DEPTH, SECTION 11-4.24.4, THE
 CLEAR FLOOR SPACE, SECTION 11-4.24.5, OR COMPLIANCE FOR
 THE FAUCET, SECTION 11-4.24.7.
 ******RESPONSE NOTED, BUT THE FOLLOWING IS STILL NOT
 SHOWN: THE SINK DEPTH, SECTION 11-4.24.4, THE CLEAR
 FLOOR SPACE, SECTION 11-4.24.5, OR COMPLIANCE FOR THE
 FAUCET, SECTION 11-4.24.7. ALSO INDICATE THE CLEARANCE
 REQUIRED BY SECTION 11-4.24.3.
  
 15. OK
 16. OK
 17. OK
 18. OK
  
 19. SHT P1-101 SUBMIT A DETAIL FOR THE CANINE
 PRE-OP/POST-OP KENNELS. SHOW A DETAIL FOR THE WATER
 BACKFLOW PROTECTION AND CONNECTION TO THE DOG BOWLS.
 SECTION 608. SHOW THE CONNECTION TO THE TRENCH DRAINS
 AND THE SN-1 FIXTURES. SECTION 106.1.2. (SN-1 FIXTURES
 NOT SHOWN ON THE ISOMETRIC RISER DIAGRAM. CLARIFY).
 ****RESPONSE NOTED, BUT IT WAS A SELECTIVE RESPONSE. NO
 DETAIL FOR THE CANINE PRE-OP/POST-OP KENNELS WERE
 SUBMITTED. ALSO NO DETAIL FOR THE BACKFLOW PROTEDTION
 TO THE CONNECTION TO THE DOG BOWLS IS INDICATED ON SHT
 P2-101. THE ONLY BACKFLOW PROTECTION SHOWN IS FOR THE
 P-16 FIXTURES. INDICTE MANUFACTURE AND MODEL OF
 BACKFLOW PER TABLE 608.1.
 ******RESPONSE NOTED, BUT BACKFLOW PREVENTERS SHALL BE
 INSTALLED MAXIMUM 4 FEET ABOVE THE FLOOR FOR SERVICING
 AND TESTING. THE BACKFLOW PREVENTER IN THE RECESSED
 SHALL BE ACCESSIBLE FOR SERVICING & TESTING ALSO.
  
 20. SHT P1-103 SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING REQUIREMENTS SHALL BE SUBMITTED FOR GAS
 REVIEW:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
 G. N/A
 H. N/A
  
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
  
 27. SHT P3-101 SHOW ALL PIPE SIZES AND INDICATED ON THE
 SANITARY ISOMETRIC RISER DIAGRAM THE DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM. TABLES 709.1, 710.1(1) &
 710.1(2).
 ****RESPONSE NOTED, BUT THE DFU'S ARE NOT INDICATED AS
 THEY ACCUMULATE IN THE SYSTEM.
 ******RESPONSE NOTED, BUT MANY PIPE SIZES ARE NOT
 SHOWN. (EXAMPLE: ALL PIPING TO THE CAGES FOR PRE-OP &
 POST-OP).
  
 28. OK
 29. OK
 30. OK
 31. OK
 32. OK
 33. OK
 34. OK
  
 35. SUBMIT STORM RISER DIAGRAMS . SHOW ALL PIPE SIZES &
 INDICATE SQUARE FOOTAGE AS IT ACCUMULATES IN THE
 SYSTEM. ALSO SHOW ALL CLEANOUTS REQUIRED BY SECTION
 1101.8. (ALSO SHOW CLEANOUTS ON SHT P1-105).
 106.3.5.1.3(7)(13).
 ****RESPONSE NOTED, BUT THE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM IS NOT INDICATED.
 ******RESPONSE NOTED, BUT THE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM IS STILL NOT INDICATED ON THE
 RISER DIAGRAM. ALSO PER TABLE 1106.3, MINIMUM 6" PIPE
 IS REQUIRED FOR 1625SF @ 1/8"/FT.
  
 36. OK
 37. OK
  
 38. SHT P4-101 PACKAGED WATER HEATER-STORAGE
 RECIRCULATION SYSTEM GWH-1. THE COLD WATER SUPPLY TURNS
 INTO HOT WATER SUPPLY AFTER THE DROP. PLEASE CLARIFY.
 --THE COLD WATER SUPPLY IS SHOWN TO THE STORAGE TANK.
 PLEASE EXPLAIN.--HOT & COLD INLETS TO THE STORAGE
 TANK? CLARIFY. SECTION 106.1.1.--A VACUUM RELIEF
 VALVE IS REQUIRED FOR ALL BOTTOM FED WATER HEATERS.
 SECTION 504.2.--THE FLOOR DRAIN IS NOT AN APPROVED
 INDIRECT WASTE RECEPTOR. A FLOOR SINK OR A HUB DRAIN IS
 REQUIRED. SECTIONS 802.3 & 802.3.2.
 ****RESPONSE NOTED, BUT NO CLARIFICATION OF HOW THE
 COLD WATER SUPPLY TURNS INTO THE HOT WATER SUPPLY.
 ******RESPONSE NOTED, BUT THE COLD WATER IS STILL SHOWN
 AS COLD WATER TO THE WATER HEATER, BUT HOT WATER TO THE
 STORAGE TANK. ALSO THE PUMP IS INDICATED AS PUMPING THE
 HOT WATER FROM THE STORAGE TANK AND INTO THE HOT WATER
 HEATER. PLEASE SHOW THE PUMP AS PUMPING FROM THE WATER
 HEATER AND INTO THE STORAGE TANK AND INDICATE DIRECTION
 OF FLOW.--THE MANUF. PIPING DIAGRAM STATES "THIS
 ILLUSTRATION IS FOR CONCEPT ONLY AND SHOULD NOT BE USED
 FOR ACTUAL INSTALLATION WITHOUT ENGINEERING OR
 TECHNICAL ADVICE FROM A LICENSED ENGINEER."
  
 39. OK
  
  
 **********NEW COMMENT**********
  
 1B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE FOR THE REQUEST TO SUBMIT ONE SET OF
 OLD/VOID SHEETS TO HELP EXPEDITE THE REVIEW PROCESS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]