2008-05-29 14:14:35REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1-5: OK
  
 6A ? 6C: OK
  
 6D: A SYSTEM SIZING SUMMARY HAS BEEN PROVIDED IN LIEU
 OF COOLING LOAD CALCULATIONS AS ALLOWED UNDER EXCEPTION
 #1 OF FBCB 13-407.1.ABC.1. HOWEVER, THIS EXCEPTION
 REQUIRES THAT THE SYSTEM SIZING SUMMARY BE SIGNED AND
 SEALED BY THE DESIGN PROFESSIONAL. THE SYSTEM SIZING
 SUMMARY WHICH WAS SUBMITTED IN RESPONSE TO THIS COMMENT
 WAS NOT SIGNED AND SEALED. PLEASE CORRECT AND
 RESUBMIT.
  
 7. OK. LOUVERS INCLUDED IN PRODUCT APPROVAL PACKAGE AND
 WILL BE REVIEWED BY BUILDING PLAN REVIEWER.
  
 8-15: OK
  
 16. FAN SCHEDULE ON PAGE M3-103 STILL CALLS FOR EF81
 AND EF 83 TO BE CONTROLLED BY LIGHT SWITCH RATHER THAN
 INTERLOCKED WITH AH4 AS INDICATED IN WRITTEN RESPONSE
 (DATED 3/14/08) TO PREVIOUS REVIEW COMMENT (DATED
 2/7/08) . PLEASE CORRECT AND RESUBMIT. FBCM 403.2.1.
  
 17. OK
  
 18. FAN SCHEDULE ON M3-103 STILL CALLS FOR EF84 TO BE
 CONTROLLED BY WALL SWITCH RATHER THAN RUN CONTINUOUS AS
 STATED IN WRITTEN RESPONSE (DATED 3/14/08) TO PREVIOUS
 REVIEW COMMENT (DATED 2/7/08). FBCM 404.
  
 19. OK
  
 20. ATTACHMENT DETAILS WITH SUPPORTING CALCULATIONS
 HAVE BEEN PROVIDED AND WILL BE REVIEWED BY THE BUILDING
 PLAN REVIEWER. HOWEVER, NO INFORMATION WAS PROVIDED, AS
 PREVIOUSLY REQUESTED, DEMONSTRATING THAT THE OUTDOOR
 APPLIANCES ARE DESIGNED TO WITHSTAND ANTICIPATED WIND
 PRESSURES IN ACCORDANCE WITH FBCM 301.13.
  
 21 AND 22: OK
  
 23. THE THROUGH-PENETRATION FIRESTOP DETAILS PROVIDED
 ON PAGE M4-104 DO NOT INCLUDE ANY PENETRATING PIPES
 WHICH ARE INSULATED. WHAT SYSTEM IS TO BE USED FOR
 INSULATED PIPE?
  
 24. OK
  
 25. GENERATOR INFORMATION: PAGE E-203 INDICATES AN 840
 GALLON IN-BASE FUEL TANK IS TO BE USED. THE FOLLOWING
 ISSUES NEED TO BE ADDRESSED:
 A) AS STATED IN FIRST AND SECOND REVIEWS, PROPOSED
 ABOVE GROUND FUEL STORAGE TANKS WITH A FUEL STORAGE
 CAPACITY IN EXCESS OF 550 GALLONS SHALL BE SUBMITTED TO
 PALM BEACH COUNTY DERM FOR APPROVAL PRIOR TO PERMIT
 ISSUANCE. NO INFORMATION WAS PROVIDED WITH THIS
 SUBMITTAL INDICATING THAT THE PROPOSED FUEL TANK AND
 LOCATION HAVE BEEN APPROVED BY DERM. PBC DERM APPROVED
 PLANS SHALL BE INCLUDED WITH EACH SET OF PLANS
 SUBMITTED TO THIS JURISDICTION FOR PERMIT. SEE ORIGINAL
 COMMENT #25 (DATED 7/23/07) FOR PBC DERM CONTACT
 INFORMATION.
  
 B) THE SUBMITTAL PROVIDED FOR THE GENERATOR FUEL TANK
 INDICATES THAT THE MAXIMUM CAPACITY FOR AN IN-BASE FUEL
 TANK (WHICH IS SHOWN ON E-203) 77 GALLONS. THERE IS NO
 840 GALLON IN-BASE TANK OPTION, AS INDICATED ON PLANS,
 IN THE SUBMITTAL FROM THE MANUFACTURER. PLEASE VERIFY
 THE TYPE OF TANK TO BE USED AS WELL AS A CAPACITY FOR
 THE TANK WHICH CORRESPONDS WITH THE MANUFACTURER?S
 SUBMITTAL DATA.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]