| 2008-06-12 12:32:13 | ** DENIED 3RD REVIEW ** |
| | |
| | ** PLEASE SEE THERE ARE STILL ITEMS ON PREVIOUS REVIEWS |
| | WHICH ARE STILL IN NEED OF ADDRESSING THEREFORE SOME |
| | COMMENTS ARE REPEATED FROM INITIAL REVIEW AS WELL AS |
| | THE SECOND REVIEW. |
| | |
| | ** PLEASE ALSO SEE THERE ARE NEW COMMENTS DUE TO SOME |
| | ITEMS ONLY NOW SUBMITTED FOR FIRST REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEWS |
| | COMPLIANCE WITH FLORIDA BUILDING CODE AND CHAPTER 13 |
| | FOR ENERGY CODE COMPLIANCE. |
| | PLEASE SEE ONCE AGAIN THE SUBMITTED ENERGY CALCULATIONS |
| | ARE REQUIRED TO COORDINATE WITH PLANS. ALL SYSTEMS ON |
| | PLANS SHALL BE PLACED INTO THE INPUT DATA REPORT. THIS |
| | IS REQUIRED OF ALL LIGHTING ON PLANS AS WELL AS OTHER |
| | SYSTEMS SUCH AS BUILDING COMPONENTS. THE FOLLOWING |
| | ITEMS WILL ONCE AGAIN BE NOTED. THE INPUT DATA REPORT |
| | WILL BE NOTED AS IDR. |
| | PLEASE SEE 13-400.3.A, 13-415.1.A, 13-415.1.AB, |
| | 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3. ALL LIGHTING |
| | ON PLANS SHALL COORDINATE WITH THE IDR FOR WATTAGE OF |
| | FIXTURES, THE TYPES OF FIXTURES, THE METHOD OF CONTROLS |
| | AND THE NUMBER OF FIXTURES. ON THE PREVIOUS REVIEW |
| | EXAMPLES WERE GIVEN AS A BENEFIT TO HELP LOCATE ALL |
| | FIXTURES WHICH ARE CLEARLY SHOWN ON PLANS HOWEVER ARE |
| | NOT BEING SHOWN IN THE CALCULATIONS. |
| | ONCE AGAIN THIS REVIEWER WILL GIVE SOME EXAMPLES AND |
| | CAN NOT EXPRESS ENOUGH THE FOLLOWING IS NOT AN |
| | EXHAUSTED LIST NOR IS IT ALL ITEMS WHICH DO NOT |
| | COORDINATE. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE EXTERIOR LIGHTING ON THE IDR WHICH DOES NOT |
| | INCLUDE ANY 400W OR 35W FIXTURES.THESE ARE ONLY TWO |
| | FIXTURES ON EXTERIOR WHICH ARE BEING NOTED. HOW IS THIS |
| | POSSIBLE WHEN THE PLANS CLEARLY SHOW TYPE *S-1* AND *L* |
| | ??HOW IS THIS POSSIBLE WHEN THE PLANS CLEARLY SHOW |
| | DOZENS OF MORE FIXTURES THAN WHAT IS SHOWN IN THE INPUT |
| | DATA REPORT? |
| | THESE TWO FIXTURES ALONE WERE SPECIFICALLY GIVEN AS A |
| | BENEFIT ON PREVIOUS REVIEW ALONG WITH OTHER YET THESE |
| | ARE STILL NOT IN THE ENERGY CALCULATIONS. THERE ARE |
| | OTHER FIXTURES ON PLANS WHICH ALSO DO NOT COORDINATE |
| | WITH THE NUMBER OF FIXTURES AND THE WATTAGE. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE INTERIOR LIGHTING ON PLANS WHICH ARE ALL |
| | REQUIRED TO COORDINATE WITH THE IDR OF THE SUBMITTED |
| | ENERGY CALCULATIONS. PLEASE SEE ONE ZONE SUCH AS THE |
| | *SURRENDER LOBBY* DOES NOT COORDINATE WITH ALL LIGHTING |
| | ON PLANS. PLEASE SEE THE NUMBER OF FIXTURES AND WATTAGE |
| | OF THESE FIXTURES IN THIS AREA IS GREATER THAN THE |
| | NUMBER OF FIXTURES SHOWN ON THE IDR. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE ALL METHOD OF CONTROLS IS REQUIRED TO BE |
| | AUTOMATIC PER CODE. HOW CAN MANUAL ON/OFF CONTROLS |
| | STILL BE NOTED IN THE IDR? |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE IDR SHOWS *HOSPITAL* AS THE ALLOWANCE |
| | FOR LIGHTING HOWEVER BASED ON THE BUILDING CODE AND |
| | DEFINITIONS IN NFPA-70 AS WELL AS NFPA-101 THIS CAN NOT |
| | BE CLASSIFIED AS A HOSPITAL. PLEASE SEE THE COVER SHEET |
| | FOR THE ENERGY CALCULATIONS DOES NOT SHOW HOSPITAL, IT |
| | SHOW OFFICE. PLEASE ADJUST THE IDR FOR INTERIOR |
| | LIGHTING ALLOWANCES IN THESE AREAS. |
| | |
| | ** AS NOTED ON PREVIOUS REVIEWS, PLEASE BE SURE ALL |
| | ITEMS ON PLANS ARE PLACED INTO THE IDR/ENERGY |
| | CALCULATIONS. |
| | ** SAME AS PREVIOUS REVIEWS. |
| | |
| | 2) NOTE: PLEASE SEE SOME LIGHTING CONTROLS DO NOT YET |
| | COMPLY WITH CHAPTER 13. PLEASE SEE MECHANICAL ROOM ON |
| | FIRST FLOOR WHERE *SHIPS* LADDER IS LOCATED. THIS ROOM |
| | SHOWS A TWIST TIME YET THIS ROOM ON SHEET E-104 ALSO |
| | SHOWS A 3-WAY SWITCH AND OCCUPANCY SENSOR. PLEASE |
| | EXPLAIN HOW THIS WILL OPERATE. PLEASE SEE THE FOLLOWING |
| | COMMENT WITH RESPECT TO THE PROPOSED TIMERS. PREVIOUS |
| | REVIEW ALSO REQUESTED THE MAXIMUM TIMES TO BE NOTED ON |
| | PLANS. THE RESPONSE MENTIONS TO SEE NOTE ADDED TO |
| | PLANS. PLEASE SEE THE NOTE WAS ADDED HOWEVER THE CODE |
| | SECTION NOTED NEEDS TO BE ADJUSTED. IT SHOULD BE |
| | 13-415.1.ABC.1.1.( PLEASE ADJUST FOR POSSIBLE |
| | MISPRINT) |
| | 13-415.1.ABC.1.1, .1.2. |
| | **PREVIOUS COMMENT AND NEW BASED ON DESIGN CHANGES. |
| | |
| | 3) NOTE: PLEASE SEE FBC 11-4.27.4 AS TWIST TIMERS AS |
| | NOTED ON SYMBOL LEGEND MAY NOT BE USED AS THEY DO NOT |
| | MEET ADA MINIMUM REQUIREMENTS. |
| | **NEW COMMENT. |
| | |
| | 4) NOTE: THE MANUFACTURES SPECS/CUT SHEETS ARE ONLY NOW |
| | BEING SUBMITTED FOR THE FIRST TIME FOR REVIEW. RESPONSE |
| | AND PLANS NOW SHOW THE OVER CURRENT PROTECTION FROM THE |
| | GENERATOR BEING REMOVED. THIS IS OK HOWEVER WHEN DOING |
| | SO THIS NOW REQUIRES THE CONDUCTORS FROM THE GENERATOR |
| | TO THE FIRST MEANS OF OVER CURRENT PROTECTION TO MEET |
| | 445.13. THIS SECTION OF THE CODE REQUIRES THE |
| | CONDUCTORS TO BE SIZE AT A MINIMUM OF 115%. PLEASE BE |
| | AWARE OF THE TEMPERATURE RISE ON SPECS AS THE OUTPUT |
| | AMPERAGE IS GREATLY AFFECTED. EVEN IF THE OUTPUT IS THE |
| | LOWER OF THE FOUR SHOWN THE CONDUCTORS AS LISTED ARE |
| | STILL NOT LARGE ENOUGH. PLEASE KNOW AS THE TEMP RISE IS |
| | TYPICALLY THE 150C, OR 130C AS SHOWN THE OUTPUT |
| | AMPERAGE IS 1504 AMPS. THE CONDUCTORS PER 310.16, |
| | 110.14 ARE RATED FOR 1550AMPS. THE 115% RATING FOR |
| | MINIMUM SHALL BE 1729.6, OR RATHER 1730AMPS MINIMUM. |
| | PLEASE SEE 240.4C, 310.16 AND 110.14. THE CONDUCTORS ON |
| | DEVICES RATED OVER 800AMPS SHALL MEET OR EXCEED THIS |
| | RATING. PLEASE ADJUST CONDUCTORS OR PLACE OVER CURRENT |
| | PROTECTION BACK ON GENERATOR. |
| | ** NEW COMMENT BASED ON CHANGES MADE TO DESIGN. |
| | |
| | 5) NOTE: THE PREVIOUS REVIEWS REQUESTED THE SPECS FOR |
| | THE ATS. THESE WERE SUBMITTED AND THE GENERAL SHEET |
| | INDICATES SWITCHES RATED UP TO 4000AMPS.HOWEVER THE |
| | MANUFACTURES SPECS INSIDE THE PACKAGE DOES NOT INDICATE |
| | ANY 1600AMP ATS UNITS AS SHOWN ON PLANS. THEY LIST |
| | 1200AMP BUT NOT THE OTHER. PLEASE PROVIDE COORDINATING |
| | MANUFACTURE SPECS. THIS MAY AFFECT AIC WITHSTAND |
| | RATINGS ETC. |
| | 90.7, 110.3. |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | **PREVIOUS COMMENTS AND NEW COMMENT. |
| | |
| | 6) NOTE: PLEASE KNOW THE RESPONSE FOR SLAB ELEVATION |
| | DOES NOT CLEARLY GIVE ANY INFORMATION ON FLOOD ZONE. |
| | PLEASE KNOW THIS CAN BE A PROVISO AS THIS IS STRICTLY |
| | AN OPTIONAL STAND-BY SYSTEM HOWEVER THE EQUIPMENT IS |
| | STILL REQUIRED TO BE MOUNTED A MINIMUM OF 6INCHES ABOVE |
| | THE FLOOD LEVEL. A CERTIFICATION BY A LICENSED |
| | SURVEYOR, ENGINEER OR ARCHITECT WILL BE REQUIRED FOR |
| | ELEVATION VERIFICATION AND CERTIFICATION OF THE SLAB |
| | ONCE INSTALLED. |
| | ** THIS WAS ON PREVIOUS REVIEW AND AS NOTED CAN BE DONE |
| | AS A *PROVISO*. |
| | |
| | 7) NOTE: PLEASE SEE THE LIGHTING SHOWN THE UPPER AREA |
| | OF THE FIRST FLOOR MECHANICAL ROOM ON SHEET E-104 IS |
| | NOT THE SAME AS THE LIGHTING IN THE SAME ROOM AS SHOWN |
| | ON E-103. |
| | PLEASE COORDINATE. |
| | FBC 106.1.2 |
| | ** NEW COMMENT AS ROOMS ARE NOW LABELED. |
| | |
| | 8) NOTE: PLEASE KNOW AS THE EGRESS FROM THE SECOND |
| | LEVEL MECHANICAL ROOM IS NOW CLEAR AS DISCUSSED WITH |
| | OTHER REVIEWERS IT APPEARS THE EGRESS FROM MECHANICAL |
| | ROOM #2 IS OUTSIDE AND ACROSS THE ROOF BACK INTO |
| | MECHANICAL ROOM #1 AND THEN DOWN LADDER. PLEASE KNOW |
| | EGRESS LIGHTING FOR NORMAL AND EMERGENCY CONDITIONS |
| | SHALL BE PROVIDED AT THIS ROOF AREA BETWEEN THE DOORS |
| | ON THE SECOND ROOM BACK INTO THE FIRST ROOM. NFPA-101 |
| | 7.8, 7.9. |
| | ** NEW COMMENT |
| | |
| | 9) NOTE: PLEASE PLACE NOTE ON PLANS FOR BONDING OF |
| | METAL FRAMING PER 2704.1. THIS WAS CONFIRMED RECENTLY |
| | ON A STATE LEVEL THIS NOTE SHOULD BE ON PLANS. |
| | ** NEW COMMENT |
| | |
| | 10) NOTE: THE PREVIOUS REVIEW REQUESTED TO SHOW |
| | COMPLIANCE FOR SOUND LEVELS OF FIRE ALARM HORN DEVICES |
| | PER FBC 11-4.28.2. RESPONSE MENTIONS TO SEE NOTE ADDED |
| | TO FA RISER. THE NOTE QUOTES THE SAME CODE SECTION AS |
| | GIVEN IN REVIEW. THE CODE MAY NOT BE QUOTED IN GENERAL |
| | IN LIEU OF GIVING SPECIFIC DETAILS. THE LEVEL(S) NEED |
| | TO BE SHOWN OR NOTED AS REQUIRED IN THE SECTION OF THE |
| | CODE. THE NOTE ALSO STATES LEVELS ARE REQUIRED DURING |
| | TESTING. THE LEVELS OF HORN DEVICES DURING INITIAL |
| | TESTING WOULD ACTUALLY BE LOUDER THAN LEVELS ACTUALLY |
| | HEARD DURING BUILDING OCCUPANCY. THE CODE REQUIRES THE |
| | LEVELS TO BE ABOVE THE OTHER MAXIMUM SOUND LEVELS IN |
| | ANY ONE AREA ETC. PLEASE SEE THE FOLLOWING TEXT IS |
| | EXTRACTED FROM THE CODE FOR CLARITY OF COMMENTS SO THE |
| | NOTES, DEVICES AND SOUND LEVELS OF DEVICES CAN BE |
| | ADJUSTED, SHOWN OR NOTED. |
| | **IF PROVIDED, AUDIBLE EMERGENCY ALARMS SHALL PRODUCE A |
| | SOUND THAT EXCEEDS THE PREVAILING EQUIVALENT SOUND |
| | LEVEL IN THE ROOM OR SPACE BY AT LEAST 15 DBA OR |
| | EXCEEDS ANY MAXIMUM SOUND LEVEL WITH A DURATION OF 60 |
| | SECONDS BY 5 DBA, WHICHEVER IS LOUDER. SOUND LEVELS FOR |
| | ALARM SIGNALS SHALL NOT EXCEED 120 DBA.** |
| | |
| | 11) NOTE: THE PREVIOUS REVIEW GAVE SEVERAL NOTES WITH |
| | RESPECT TO CIRCUITING AND EVEN GAVE SOME EXAMPLES. |
| | PLEASE SEE 210.52B1 AS THE MINIMUM OF TWO SMALL |
| | APPLIANCE CIRCUITS ARE REQUIRED ON PLANS. THESE SHALL |
| | NOT CONTAIN ANY OTHER ITEMS ON THESE CIRCUITS WITH THE |
| | EXCEPTION OF THE ITEMS LISTED IN THE 210.52B1. LIGHTING |
| | IS NOT PERMITTED TO BE ON THE SMALL APPLIANCE |
| | CIRCUITS. |
| | PLEASE SEE SHEET E-102 AS THE LIGHTING CIRCUITS SHOWN |
| | ARE CIRCUITS P4-1, P4-3 AND P4-5. PLEASE SEE THE PANEL |
| | SCHEDULE ON SHEET WHICH SHOWS ONLY TWO OF THESE |
| | LIGHTING CIRCUITS. CIRCUIT SHOWN AS P4-5 IS ACTUALLY |
| | *BLANK* ON SCHEDULE AS THIS IS NOTED AS *SPARE*. PLEASE |
| | ALSO SEE SHEET E-202 AS THIS CLEARLY SHOWS THE LIGHTING |
| | STILL BEING CIRCUITED TO THE SMALL APPLIANCE CIRCUITS |
| | AS THE SMALL APPLIANCE CIRCUITS ON THIS SHEET E-202 IS |
| | SHOWING P4-1 AND P4-3 AS THE SMALL APPLIANCE CIRCUITS. |
| | PLEASE SEE THE FOLLOWING TEXT WHICH IS EXTRACTED FROM |
| | THE CODE WHICH INDICATES WHICH ITEMS MAY ON THE SAME |
| | CIRCUITS AS THE SMALL APPLIANCE CIRCUITS. |
| | **(B) SMALL APPLIANCES |
| | (1) RECEPTACLE OUTLETS SERVED IN THE KITCHEN, PANTRY, |
| | BREAKFAST ROOM, DINING ROOM, OR SIMILAR AREA OF A |
| | DWELLING UNIT, THE TWO OR MORE 20-AMPERE |
| | SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY |
| | 210.11(C)(1) SHALL SERVE ALL WALL AND FLOOR RECEPTACLE |
| | OUTLETS COVERED BY 210.52(A), ALL COUNTERTOP OUTLETS |
| | COVERED BY 210.52(C), AND RECEPTACLE OUTLETS FOR |
| | REFRIGERATION EQUIPMENT.** |
| | THIS CAN BE FOR RECEPTACLE OUTLETS ONLY IN THESE AREAS, |
| | NO OTHER OUTLETS ARE PERMITTED. PLEASE ADJUST. |
| | ** PREVIOUS REVIEWS. |
| | |
| | 12) NOTE: THE PREVIOUS REVIEW GAVE SEVERAL NOTES WITH |
| | RESPECT TO CIRCUITING AND EVEN GAVE SOME EXAMPLES. |
| | PLEASE SEE THE PREVIOUS REVIEWS WITH RESPECT TO |
| | REQUIRED ARC FAULT PROTECTION REQUIRED ON ALL OUTLETS |
| | IN BEDROOMS PER 210.12. THE PREVIOUS PANEL SCHEDULE |
| | ALONG WITH THE CURRENT REVISED PANEL SCHEDULE SUBMITTED |
| | CONTAINS TWO ASTERISK ( **) AT THE TOP OF THE PANEL |
| | SCHEDULE WHICH STATES THE CIRCUITS NOTED WITH THE TWO |
| | ASTERISK (**) ARE TO CONTAIN AFCI BREAKERS/ARC FAULT |
| | PROTECTION. PLEASE SEE THE PREVIOUS REVIEW GAVE |
| | SPECIFIC NOTE THAT NOT ALL CIRCUITS WHICH REQUIRED AFCI |
| | PROTECTION SHOWED THE ASTERISK (**). THE RESPONSE |
| | MENTIONS THE TWO CIRCUITS WHICH REQUIRE ARC FAULT |
| | PROTECTION PER THE 2005 NEC DOES SHOW THE PROTECTION. |
| | ** PLEASE SEE THE 2002 AS WELL AS THE 2005 NEC REQUIRES |
| | ARC FAULT PROTECTION FOR *ALL OUTLETS* INSIDE THE |
| | SLEEPING ROOMS. THIS PROTECTION IS NOT FOR RECEPTACLES |
| | ONLY. THIS IS FOR RECEPTACLES, LIGHTS, SMOKE ALARMS |
| | (WHEN 120V) , FANS ETC. |
| | PLEASE SEE THE PLANS STILL DO NOT SHOW ANY PROTECTION |
| | FOR THE OTHER OUTLETS IN THESE ROOMS. THE CIRCUITS |
| | WHICH INDICATE PROTECTION STILL ONLY SHOW THIS FOR |
| | *RECEPTACLES*. PLEASE SEE CIRCUITS NOTED AS P4-1 AND |
| | P4-5 DO NOT INDICATE PROTECTION. |
| | PLEASE SEE E-102 AND E-303. AS NOTED ABOVE IN NOTE #11 |
| | CIRCUITS ALSO DO NOT CORRELATE. |
| | PLEASE COORDINATE PLANS, PLEASE ADJUST FOR CODE |
| | COMPLIANCE AND PLEASE LIST ALL REQUIRED BRANCH CIRCUITS |
| | WITH AFCI PROTECTION AS REQUIRED PER 2005 NEC. |
| | ** PREVIOUS REVIEWS |
| | |
| | 13) NOTE: DINING ROOM WALL APPEARS TO REQUIRE A SECOND |
| | RECEPTACLE TO MEET WALL SPACING REQUIREMENTS PER |
| | 210.52. WALL SPACE IS UNCLEAR AND IS BEING NOTED AS THE |
| | INDENTION IN WALL MAY OR MAY NOT BE CABINETS. AS THIS |
| | IS DOES NOT SHOW CABINETS AND APPEARS TO BE WALL, |
| | PLEASE ADD RECEPTACLE AS TOTAL LENGTH OF WALL FROM |
| | DOORWAY OF LAUNDRY ROOM TO DOORWAY AT FRONT DOOR |
| | APPEARS TO BE 12FT OR MORE. |
| | ** NEW COMMENT. |
| | |
| | 14) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEET |
| | SHOWING THE 42CIRCUIT PANELS AS 100AMP RATED. AS NOTED |
| | PREVIOUSLY PANELS AT 100AMP RATED AND 60AMP RATED ARE |
| | NOT KNOWN TO BE 42CIRCUIT. PLEASE SUBMIT SPEC/CUT |
| | SHEET. A SEARCH OF A FEW OF THE STANDARD MANUFACTURE |
| | DID NOT PRODUCE ANY LISTED 42CIRCUIT PANEL BOARDS WHICH |
| | WERE ONLY 100AMP RATED. |
| | NEC 110.3, 90.7 |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 15) NOTE: PLEASE PLACE NOTE ON PLANS FOR COLOR CODING |
| | OF CONDUCTORS. THE SPECIFICATION DIVISION SPECS ARE NOT |
| | PART OF THE RECORD PLANS AND ARE NOT TYPICALLY USED |
| | DURING INSPECTIONS. THESE ARE NOT PART OF REVIEW FOR |
| | MINIMUM CODE COMPLIANCE. PLEASE PLACE NOTE ON |
| | RISER/ALONG WITH CONDUCTORS FOR BROWN, PURPLED AND |
| | YELLOW. 277/480V. |
| | 90.4, 310.11,310.12 ETC |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | ** PREVIOUS COMMENTS. |
| | |
| | 16) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WHICH |
| | MENTIONED THE RECEPTACLE WHICH APPEARED TO BE SHOWN |
| | ABOVE THE CEILING FOR WATER COOLERS. THE SECTION OF |
| | CODE GIVEN WAS THAT NO CORDS ARE PERMITTED ABOVE THE |
| | CEILING. THE RESPONSE COMMENT MENTIONED THESE |
| | RECEPTACLES ARE FOR REMOTE CHILLER UNIT ABOVE CEILINGS. |
| | THESE ARE NOT PERMITTED TO BE CORD AND PLUG CONNECTED. |
| | PLEASE SEE 400.8 AND PLEASE REVISE DESIGN. |
| | FBC 106.1.2. |
| | |
| | 17) NOTE: PLEASE SEE PREVIOUS REVIEW GAVE NOTICE TO |
| | FLORIDA STATUTES 553.80(2)(B) WITH RESPECT TO REPEAT |
| | COMMENTS FOR CODE COMPLIANCE. THERE ARE SEVERAL CODE |
| | SECTIONS WHICH HAVE BEEN REPEATED FOR THE THREE |
| | REVIEWS. THE FEE IS A STATUTORY REQUIRED FEE AND IS NOT |
| | A LOCAL ORDINANCE, FINE OR REQUIRED BY THE LOCAL LEVEL. |
| | THE FEE IS ASSESSED TO THE DESIGN TEAM AS REQUIRED BY |
| | THE STATUTE. THE FEE IS THE PORTION OF THE BASE FEE |
| | ATTRIBUTED TO PLAN REVIEW TIMES FOUR. THE BASE PERMIT |
| | FEE OF THIS PROJECT IS $52,000. THE PORTION OF THAT FEE |
| | WHICH IS ATTRIBUTED TO PLAN REVIEW IS 30% OF THE BASE |
| | PERMIT FEE WHICH IS $15,600. THIS IS THE AMOUNT TIMES |
| | FOUR WHICH IS ASSESSED. THIS AMOUNT IS $62,400. THIS IS |
| | A STATUTE REQUIRED FEE WHICH IS REQUIRED TO BE PAID |
| | BEFORE PLANS ARE RESUBMITTED FOR THE FOLLOWING REVIEW. |
| | PLEASE KNOW THAT ONE SET OF ELECTRICAL PLANS ALONG WITH |
| | ENERGY CALCULATIONS AND OTHER POSSIBLE DOCUMENTS ARE |
| | BEING RETAINED BY THIS OFFICE. |
| | IT IS RECOMMENDED IF THERE ARE QUESTIONS TO PLEASE |
| | CONTACT THIS OFFICE/REVIEWER. |
| | |
| | *** PLEASE KNOW THERE MAY VERY WELL BE NEW COMMENTS ON |
| | THE NEXT REVIEW WHICH CAN NOT BE MADE AT THIS TIME DUE |
| | TO INFORMATION ETC NOT YET IN DESIGN OR ON PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |