| Date |
Text |
| 2008-02-15 10:37:01 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY WPB MUNICIPAL CODE |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | |
| | 3. CIVIL DRAWINGS. THE ADDRESS FOR THE ENGINEERING |
| | CONPANY IN THE TITLE BLOCK DOES NOT REFLECT THE ADDRESS |
| | INDICATED ON THE FLORIDA STATE DBPR WEBSITE. PLEASE |
| | UPDATE THE WEBSITE OR THE TITLE BLOCKS PRIOR TO |
| | RESUBMITTING. ALSO THE ENGINEER SHALL LEGIBLY INDICATE |
| | HER ADDRESS IN THE TITLE BLOCK.FAC 61G15-23.002(2) & |
| | FS 471.025. PLEASE INDICATE ENGINEER'S ADDRESS. |
| | ****RESPONSE NOTED, BUT THE ADDRESS INDICATED IN THE |
| | DBPR WEBSITE IS 6380 SANDY HILL WAY LAKE WORTH FLA |
| | 33463, NOT 120 S. OLIVE AVE. ETC. AS INDICATED IN THE |
| | TITLE BLOCK. BUSINESS LICENSE NUMBER IS 9664 AS SHOWN |
| | ON THE TITLE BLOCK THE CORPORATION NUMBER IS OF NO |
| | RELEVANCE TO THIS COMMENT. |
| | |
| | 4. OK |
| | |
| | 5. ALL ARCHITECTURAL SHEETS. THE SIGNATURE IS REQUIRED |
| | FOR THE ARCHITECT. IT APPEARS THAT INITIALS HAVE BEEN |
| | USED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE |
| | ARCHITECT, THEN A SIGNED, SEALED, DATED, NOTORIZED |
| | LETTER INDICATING THE LEGAL SIGNATURE OF THE ARCHITECT |
| | SHALL BE SUBMITTED FOR OUR FILES. FAC 61G1-16.003, |
| | 61G1-16.004(5) & FS 481.2055. |
| | ****RESPONSE NOTED, BUT THE SEAL IS STILL SIGNED WITH |
| | WHAT APPEARS TO BE INITIALS AND NO LETTER HAS BEEN |
| | SUBMITTED. |
| | |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | 11. OK |
| | |
| | 12. SHT A-300 UPPER ROOF AT N.E. CORNER INDICATES R5 AS |
| | AN O.S. PLEASE CLARIFY.--LOWER ROOF DRAINS ARE |
| | INDICATED AS O.S., NOT PRIMARY SCUPPER DRAINS. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT DETAIL R7/A302 DOES NOT REFLECT |
| | THE PARAPET FOR THE UPPER ROOF. SECONDARY ROOF DRAIN |
| | REQUIRED. (SEE DETAIL R4/A-301). |
| | |
| | 13. SHT A-300 INDICATES R15 FOR THE SCUPPER WITH |
| | DOWNSPOUT & O.S. R15 SHOWS NO COLLECTOR HEAD OR |
| | DOWNSPOUT. ALSO SHEET A-400 SHOWS NO DOWNSPOUTS. PLEASE |
| | CLARIFY AND INDICATE THE SIZE OF THE DOWNSPOUTS AND |
| | SHOW COLLECTOR HEAD WITH DIMENSIONS. TABLES 1106.3 & |
| | 1106.7.--ALSO INDICATE HOW THE PRIMARY DRAIN & O.S. |
| | CAN BE AT THE ROOF LEVEL. SECTIONS 1503.4.2 & |
| | 1503.4.3. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. DETAIL |
| | R15 STILL DOES NOT SHOW A COLLECTOR HEAD OR |
| | DOWNSPOUTS. |
| | |
| | 14. SHT A-709 DETAILS 79 & 81. SHOW COMPLIANCE WITH |
| | SECTION 11-4.24 & ALL SUBSECTIONS. NOTE: FORWARD |
| | APPROACH REQUIRED ON CLEAR FLOOR SPACE AND CABINET |
| | DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE. |
| | ****RESPONSE NOTED, BUT SHT A-709 DETAILS 79 & 81 SHOW |
| | THE FLOOD RIM LEVEL, (COUNTER TOP), AT 3'0". PER CODE |
| | 34" IS MAXIMUM HEIGHT ALLOWED. SECTION 11-4.24.2. ALSO |
| | NOT SHOWN IS THE SINK DEPTH, SECTION 11-4.24.4, THE |
| | CLEAR FLOOR SPACE, SECTION 11-4.24.5, OR COMPLIANCE FOR |
| | THE FAUCET, SECTION 11-4.24.7. |
| | |
| | 15. OK |
| | 16. OK |
| | 17. OK |
| | |
| | 18. SHT P1-101. SUBMIT THE MANUF. SPECIFICATION SHEETS |
| | FOR THE SN-1 FIXTURE INCLUDING INSTALLATION |
| | INSTRUCTIONS. SECTION 106.1.2. |
| | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. TABLE 604.3 |
| | & 604.5, SECTION 608.2. |
| | |
| | 19. SHT P1-101 SUBMIT A DETAIL FOR THE CANINE |
| | PRE-OP/POST-OP KENNELS. SHOW A DETAIL FOR THE WATER |
| | BACKFLOW PROTECTION AND CONNECTION TO THE DOG BOWLS. |
| | SECTION 608. SHOW THE CONNECTION TO THE TRENCH DRAINS |
| | AND THE SN-1 FIXTURES. SECTION 106.1.2. (SN-1 FIXTURES |
| | NOT SHOWN ON THE ISOMETRIC RISER DIAGRAM. CLARIFY). |
| | ****RESPONSE NOTED, BUT IT WAS A SELECTIVE RESPONSE. NO |
| | DETAIL FOR THE CANINE PRE-OP/POST-OP KENNELS WERE |
| | SUBMITTED. ALSO NO DETAIL FOR THE BACKFLOW PROTEDTION |
| | TO THE CONNECTION TO THE DOG BOWLS IS INDICATED ON SHT |
| | P2-101. THE ONLY BACKFLOW PROTECTION SHOWN IS FOR THE |
| | P-16 FIXTURES. INDICTE MANUFACTURE AND MODEL OF |
| | BACKFLOW PER TABLE 608.1. |
| | |
| | 20. SHT P1-103 SEPARATE GAS PERMIT IS REQUIRED. THE |
| | FOLLOWING REQUIREMENTS SHALL BE SUBMITTED FOR GAS |
| | REVIEW: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ****RESPONSE NOTED, BUT NOT ALL SECTIONS OF PIPE SHOW |
| | THE CORRESPONDING LENGHTS AS REQUIRED. ALSO THE PIPING |
| | IS NOT CLEAR AT THE GB1 APPLIANCES. (DELETE BACKGROUND |
| | FLOOR PLAN & GAS APPLIANCES). |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE |
| | NOTED, BUT SPECIFICATION 15483 IS REFERENCED AS BEING |
| | DESIGNED BY FBC-2001. THE ADOPTED CODE IS FBC-2004. |
| | PLEASE CHECK THE INFORMATION IS THE SPECIFICATION BOOKS |
| | AS THEY WILL BE REVIEWED COMPLETLY UPON RESUBMISSION |
| | AND THEY SHALL BE REQUIRED TO REFLECT THE PLANS TO BE |
| | APPROVED. |
| | |
| | C. OK |
| | D. OK |
| | E. OK |
| | |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, BUT THE GAS PLANS WILL NOT BE |
| | APPROVED UNTIL THE COMMENT IS COMPLIED WITH. COMMENT |
| | NOT ADDRESSED. |
| | |
| | G. N/A |
| | H. N/A |
| | |
| | 21. OK |
| | |
| | 22. SHT P1-105 A RELIEF VENT, (GOOSE-NECK) FITTING |
| | SHALL BE INSTALLED IN THE CONDENSATE DRAIN LINE AS IT |
| | EXITS THE BUILDING. |
| | ****RESPONSE NOTED, BUT P1-105 DOES NOT REFLECT THE |
| | RISER DIAGRAM ON SHT P1-101. PLEASE CORRELATE. SECTION |
| | 106.1.1. |
| | |
| | 23. OK |
| | 24. OK |
| | 25. OK |
| | 26. OK |
| | |
| | 27. SHT P3-101 SHOW ALL PIPE SIZES AND INDICATED ON THE |
| | SANITARY ISOMETRIC RISER DIAGRAM THE DFU'S AS THEY |
| | ACCUMULATE IN THE SYSTEM. TABLES 709.1, 710.1(1) & |
| | 710.1(2). |
| | ****RESPONSE NOTED, BUT THE DFU'S ARE NOT INDICATED AS |
| | THEY ACCUMULATE IN THE SYSTEM. |
| | |
| | 28. OK |
| | 29. OK |
| | 30. OK |
| | 31. OK |
| | 32. OK |
| | 33. OK |
| | 34. OK |
| | |
| | 35. SUBMIT STORM RISER DIAGRAMS . SHOW ALL PIPE SIZES & |
| | INDICATE SQUARE FOOTAGE AS IT ACCUMULATES IN THE |
| | SYSTEM. ALSO SHOW ALL CLEANOUTS REQUIRED BY SECTION |
| | 1101.8. (ALSO SHOW CLEANOUTS ON SHT P1-105). |
| | 106.3.5.1.3(7)(13). |
| | ****RESPONSE NOTED, BUT THE SQUARE FOOTAGE AS IT |
| | ACCUMULATES IN THE SYSTEM IS NOT INDICATED. |
| | |
| | 36. OK |
| | 37. OK |
| | |
| | 38. SHT P4-101 PACKAGED WATER HEATER-STORAGE |
| | RECIRCULATION SYSTEM GWH-1. THE COLD WATER SUPPLY TURNS |
| | INTO HOT WATER SUPPLY AFTER THE DROP. PLEASE CLARIFY. |
| | --THE COLD WATER SUPPLY IS SHOWN TO THE STORAGE TANK. |
| | PLEASE EXPLAIN.--HOT & COLD INLETS TO THE STORAGE |
| | TANK? CLARIFY. SECTION 106.1.1.--A VACUUM RELIEF |
| | VALVE IS REQUIRED FOR ALL BOTTOM FED WATER HEATERS. |
| | SECTION 504.2.--THE FLOOR DRAIN IS NOT AN APPROVED |
| | INDIRECT WASTE RECEPTOR. A FLOOR SINK OR A HUB DRAIN IS |
| | REQUIRED. SECTIONS 802.3 & 802.3.2. |
| | ****RESPONSE NOTED, BUT NO CLARIFICATION OF HOW THE |
| | COLD WATER SUPPLY TURNS INTO THE HOT WATER SUPPLY. |
| | |
| | 39. OK |
| | |
| | |
| | **********NEW COMMENT********** |
| | |
| | 1B. INFORMATIONAL: THE CERTIFICATIONS AND WELDING |
| | PROCEDURE WILL BE REQUIRED AT THE TIME OF GAS PERMIT |
| | APPLICATION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | ****NO RESPONSE FOR THE REQUEST TO SUBMIT ONE SET OF |
| | OLD/VOID SHEETS TO HELP EXPEDITE THE REVIEW PROCESS. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |