Plan Review Notes
Plan Review Notes For Permit 07060707
Permit Number 07060707
Review Stop M
Sequence Number 2
Notes
Date Text
2008-02-13 07:43:31REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1 THROUGH 5: OK
  
 6. THIS IS THE FIRST REVIEW OF THE ENERGY CALCULATIONS
 AS THEY WERE NOT INCLUDED WITH THE ORIGINAL SUBMITTAL.
 THE FOLLOWING DISCREPANCIES WERE FOUND IN THE ENERGY
 CALCULATIONS:
 A) THE DESIGN IPLV ON THE PLANT PORTION OF THE INPUT
 DATA REPORT (IDR) DOES NOT CORRESPOND WITH THE IPLV ON
 THE EQUIPMENT SCHEDULE. ADDITIONALLY, THE DATA IN THE
 EQUIPMENT SCHEDULE DOES NOT CORRESPOND WITH THE
 MANUFACTURER?S DATA FROM THEIR WEBSITE (WWW.TRANE.COM).
  
 B) THE IDR CALLS FOR 1.5 INCH THICK INSULATION ON
 DOMESTIC HOT WATER PIPING, BUT THE SPECIFICATIONS
 (SEC.15250) CALL FOR 1 INCH THICK INSULATION.
 C) THE IDR CALLS FOR 2 INCH THICK INSULATION ON 2 INCH
 CHILLED WATER HVAC PIPING AND THE SPECIFICATIONS
 (SEC.15250) CALL FOR 1.5 INCH THICK INSULATION.
 THE VALUES IN THE IDR SHALL MATCH THE VALUES ON THE
 PLANS AND SPECIFICATIONS IN ACCORDANCE WITH FBC
 13-103.2
 D) COOLING LOAD CALCULATIONS FOR THE PURPOSE OF SYSTEM
 SIZING SHALL BE APPENDED TO THE ENERGY CALCULATIONS IN
 ACCORDANCE WITH FBC 13-407.1.ABC.1.
  
 7. NO CUT SHEETS WERE FOUND IN THE PACKAGE SUBMITTED.
 ALSO, NO LOUVERS WERE PROVIDED IN THE PRODUCT APPROVAL
 BOOKLET. WALL LOUVERS ARE DEFINED AS PANEL WALLS PER
 FAC RULE 9B-72 AND ARE SUBJECT TO THE FLORIDA PRODUCT
 APPROVAL SYSTEM. PRODUCT APPROVALS SHALL BE APPROVED IN
 WRITING BY THE DESIGNER OF RECORD AND SUBMITTED PRIOR
 TO PERMIT IN ACCORDANCE WITH FBC 106.3.3
  
 8 ? 13: OK
  
 14. A 100% OUTSIDE AIR DUCT HAS BEEN ADDED TO AREA
 SERVED BY BC-1. HOWEVER, THERE IS AN 8 INCH FLEX DUCT
 SHOWN ON FLOOR PLAN, PAGE M1-102, WHICH IS PENETRATING
 A TWO-HOUR FIRE RESISTANCE RATED WALL. SEE PAGE
 LS-001SHOW HOW THIS PENETRATION IS TO BE PROTECTED IN
 ACCORDANCE WITH FBC, M 607.5.2.
  
 15. OK
  
 16. THERE IS NO INDICATION ON PLANS AS TO HOW THIS
 COMMENT WAS ADDRESSED. FAN SCHEDULE ONLY CALLS FOR
 INTERLOCK WITH THE LIGHT SWITCH. WHAT PROVISIONS ARE
 MADE TO ENSURE THE EFS ARE RUNNING WHENEVER BC-1 IS
 RUNNING? SHOW COMPLIANCE WITH FBC, M 403.2.1(3).
  
 17. THERE IS STILL A DETAIL FOR A DRYWELL ON PAGE
 M4-101. WILL THERE STILL BE A DRYWELL AS PART OF THE
 CONDENSATE DISPOSAL SYSTEM?
  
 18. FAN SCHEDULE CALLS FOR EF84 TO BE CONTROLLED BY
 WALL SWITCH. MECHANICAL VENTILATION SYSTEMS FOR
 ENCLOSED PARKING GARAGES ARE NOT REQUIRED TO OPERATE
 CONTINUOUSLY WHERE THE SYSTEM IS ARRANGED TO OPERATE
 AUTOMATICALLY UPON DETECTION OF A CONCENTRATION OF
 CARBON MONOXIDE OF 25 PARTS PER MILLION (PPM) BY
 APPROVED AUTOMATIC DETECTION DEVICES IN ACCORDANCE WITH
 FBC, M 404.1. IN LIEU OF BEING CONTROLLED BY APPROVED
 CARBON MONOXIDE SENSOR(S) THE VENTILATION FAN FOR THE
 SALLY PORT SHALL OPERATE CONTINUOUSLY AT A MINUM RATE
 OF 1.5 CFM PER SQUARE FOOT IN ACCORDANCE WITH THIS
 SECTION. AUTOMATIC OPERATION OF THE SYSTEM SHALL NOT
 REDUCE THE CONTINUOUS VENTILATION RATE BELOW0.05 CFM
 PER SQUARE FOOT OF THE FLOOR AREA AND THE SYSTEM SHALL
 BE CAPABLE OF PRODUCING A VENTILATION RATE OF 1.5 CFM
 PER SQUARE FOOT OF FLOOR AREA IN ACCORDANCE WITH FBC, M
 404.2 SHOW HOW THE CONTINUOUS OR VARIABLE RATES ARE TO
 BE PROVIDED. IF A CARBON MONOXIDE DETECTION SYSTEM IS
 EMPLOYED, SHOW LOCATION(S) OF DETECTOR(S) AND PROVIDE
 MANUFACTURER?S SUBMITTAL AND INSTALLATION INSTRUCTIONS
 FOR REVIEW. FBC 106.1.2.
  
 19. OK
  
 20. NO INFORMATION COULD BE FOUND IN STRUCTURAL PLANS
 RELATED TO WIND LOADS OR ATTACHMENTS FOR MECHANICAL
 EQUIPMENT AND APPLIANCES. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 ON THE EQUIPMENT AND THE SUPPORTS AS DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING PER
 FBC, M 301.13. PLEASE NOTE THAT THIS CODE REQUIREMENT
 NOT ONLY APPLIES TO ATTACHMENTS BUT TO THE EQUIPMENT
 AND APPLIANCES THEMSELVES. IT INCLUDES BUT IS NOT
 LIMITED TO ERUS, EXHAUST FANS, OUTSIDE AIR INTAKES AND
 CHILLERS. PROVIDE DATA SHOWING EQUIPMENT, APPLIANCES
 AND INSTALLATION METHODS SUFFICIENT TO WITHSTAND
 ANTICIPATED WIND PRESSURES WITH SUPPORTING CALCULATIONS
 TO DEMONSTRATE COMPLIANCE WITH THIS SECTION.
  
 21 AND 22: OK
  
 23. NO DETAIL OF ANY THROUGH-PENETRATION FIRESTOP
 SYSTEM FOR PIPE PENETRATIONS OF FIRE-RESISTANCE RATED
 ASSEMBLIES COULD BE FOUND ON PG P4-101 AS SPECIFIED IN
 DESIGNER?S WRITTEN RESPONSE. THIS COMMENT HAS NOT BEEN
 ADDRESSED. SHOW COMPLIANCE WITH FBC 712.3 AND 712.4.
  
 24. OK
  
 25. THIS COMMENT REMAINS ESSENTIALLY UNADDRESSED. AS
 LONG AS THE GENERATOR IS SHOWN AS PART OF THIS PERMIT
 APPLICATION, ALL RELEVANT INFORMATION (SEE PREVIOUS
 REVIEW COMMENT #25) SHALL BE PROVIDED PRIOR TO PERMIT
 ISSUANCE.
 NOTE: ADDITIONAL COMMENTS ARE POSSIBLE DUE TO THE LACK
 OF INFORMATION.
  