| 2008-02-13 07:43:31 | REVIEW #: 2ND |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1 THROUGH 5: OK |
| | |
| | 6. THIS IS THE FIRST REVIEW OF THE ENERGY CALCULATIONS |
| | AS THEY WERE NOT INCLUDED WITH THE ORIGINAL SUBMITTAL. |
| | THE FOLLOWING DISCREPANCIES WERE FOUND IN THE ENERGY |
| | CALCULATIONS: |
| | A) THE DESIGN IPLV ON THE PLANT PORTION OF THE INPUT |
| | DATA REPORT (IDR) DOES NOT CORRESPOND WITH THE IPLV ON |
| | THE EQUIPMENT SCHEDULE. ADDITIONALLY, THE DATA IN THE |
| | EQUIPMENT SCHEDULE DOES NOT CORRESPOND WITH THE |
| | MANUFACTURER?S DATA FROM THEIR WEBSITE (WWW.TRANE.COM). |
| | |
| | B) THE IDR CALLS FOR 1.5 INCH THICK INSULATION ON |
| | DOMESTIC HOT WATER PIPING, BUT THE SPECIFICATIONS |
| | (SEC.15250) CALL FOR 1 INCH THICK INSULATION. |
| | C) THE IDR CALLS FOR 2 INCH THICK INSULATION ON 2 INCH |
| | CHILLED WATER HVAC PIPING AND THE SPECIFICATIONS |
| | (SEC.15250) CALL FOR 1.5 INCH THICK INSULATION. |
| | THE VALUES IN THE IDR SHALL MATCH THE VALUES ON THE |
| | PLANS AND SPECIFICATIONS IN ACCORDANCE WITH FBC |
| | 13-103.2 |
| | D) COOLING LOAD CALCULATIONS FOR THE PURPOSE OF SYSTEM |
| | SIZING SHALL BE APPENDED TO THE ENERGY CALCULATIONS IN |
| | ACCORDANCE WITH FBC 13-407.1.ABC.1. |
| | |
| | 7. NO CUT SHEETS WERE FOUND IN THE PACKAGE SUBMITTED. |
| | ALSO, NO LOUVERS WERE PROVIDED IN THE PRODUCT APPROVAL |
| | BOOKLET. WALL LOUVERS ARE DEFINED AS PANEL WALLS PER |
| | FAC RULE 9B-72 AND ARE SUBJECT TO THE FLORIDA PRODUCT |
| | APPROVAL SYSTEM. PRODUCT APPROVALS SHALL BE APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD AND SUBMITTED PRIOR |
| | TO PERMIT IN ACCORDANCE WITH FBC 106.3.3 |
| | |
| | 8 ? 13: OK |
| | |
| | 14. A 100% OUTSIDE AIR DUCT HAS BEEN ADDED TO AREA |
| | SERVED BY BC-1. HOWEVER, THERE IS AN 8 INCH FLEX DUCT |
| | SHOWN ON FLOOR PLAN, PAGE M1-102, WHICH IS PENETRATING |
| | A TWO-HOUR FIRE RESISTANCE RATED WALL. SEE PAGE |
| | LS-001SHOW HOW THIS PENETRATION IS TO BE PROTECTED IN |
| | ACCORDANCE WITH FBC, M 607.5.2. |
| | |
| | 15. OK |
| | |
| | 16. THERE IS NO INDICATION ON PLANS AS TO HOW THIS |
| | COMMENT WAS ADDRESSED. FAN SCHEDULE ONLY CALLS FOR |
| | INTERLOCK WITH THE LIGHT SWITCH. WHAT PROVISIONS ARE |
| | MADE TO ENSURE THE EFS ARE RUNNING WHENEVER BC-1 IS |
| | RUNNING? SHOW COMPLIANCE WITH FBC, M 403.2.1(3). |
| | |
| | 17. THERE IS STILL A DETAIL FOR A DRYWELL ON PAGE |
| | M4-101. WILL THERE STILL BE A DRYWELL AS PART OF THE |
| | CONDENSATE DISPOSAL SYSTEM? |
| | |
| | 18. FAN SCHEDULE CALLS FOR EF84 TO BE CONTROLLED BY |
| | WALL SWITCH. MECHANICAL VENTILATION SYSTEMS FOR |
| | ENCLOSED PARKING GARAGES ARE NOT REQUIRED TO OPERATE |
| | CONTINUOUSLY WHERE THE SYSTEM IS ARRANGED TO OPERATE |
| | AUTOMATICALLY UPON DETECTION OF A CONCENTRATION OF |
| | CARBON MONOXIDE OF 25 PARTS PER MILLION (PPM) BY |
| | APPROVED AUTOMATIC DETECTION DEVICES IN ACCORDANCE WITH |
| | FBC, M 404.1. IN LIEU OF BEING CONTROLLED BY APPROVED |
| | CARBON MONOXIDE SENSOR(S) THE VENTILATION FAN FOR THE |
| | SALLY PORT SHALL OPERATE CONTINUOUSLY AT A MINUM RATE |
| | OF 1.5 CFM PER SQUARE FOOT IN ACCORDANCE WITH THIS |
| | SECTION. AUTOMATIC OPERATION OF THE SYSTEM SHALL NOT |
| | REDUCE THE CONTINUOUS VENTILATION RATE BELOW0.05 CFM |
| | PER SQUARE FOOT OF THE FLOOR AREA AND THE SYSTEM SHALL |
| | BE CAPABLE OF PRODUCING A VENTILATION RATE OF 1.5 CFM |
| | PER SQUARE FOOT OF FLOOR AREA IN ACCORDANCE WITH FBC, M |
| | 404.2 SHOW HOW THE CONTINUOUS OR VARIABLE RATES ARE TO |
| | BE PROVIDED. IF A CARBON MONOXIDE DETECTION SYSTEM IS |
| | EMPLOYED, SHOW LOCATION(S) OF DETECTOR(S) AND PROVIDE |
| | MANUFACTURER?S SUBMITTAL AND INSTALLATION INSTRUCTIONS |
| | FOR REVIEW. FBC 106.1.2. |
| | |
| | 19. OK |
| | |
| | 20. NO INFORMATION COULD BE FOUND IN STRUCTURAL PLANS |
| | RELATED TO WIND LOADS OR ATTACHMENTS FOR MECHANICAL |
| | EQUIPMENT AND APPLIANCES. MECHANICAL EQUIPMENT, |
| | APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL |
| | BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES |
| | ON THE EQUIPMENT AND THE SUPPORTS AS DETERMINED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING PER |
| | FBC, M 301.13. PLEASE NOTE THAT THIS CODE REQUIREMENT |
| | NOT ONLY APPLIES TO ATTACHMENTS BUT TO THE EQUIPMENT |
| | AND APPLIANCES THEMSELVES. IT INCLUDES BUT IS NOT |
| | LIMITED TO ERUS, EXHAUST FANS, OUTSIDE AIR INTAKES AND |
| | CHILLERS. PROVIDE DATA SHOWING EQUIPMENT, APPLIANCES |
| | AND INSTALLATION METHODS SUFFICIENT TO WITHSTAND |
| | ANTICIPATED WIND PRESSURES WITH SUPPORTING CALCULATIONS |
| | TO DEMONSTRATE COMPLIANCE WITH THIS SECTION. |
| | |
| | 21 AND 22: OK |
| | |
| | 23. NO DETAIL OF ANY THROUGH-PENETRATION FIRESTOP |
| | SYSTEM FOR PIPE PENETRATIONS OF FIRE-RESISTANCE RATED |
| | ASSEMBLIES COULD BE FOUND ON PG P4-101 AS SPECIFIED IN |
| | DESIGNER?S WRITTEN RESPONSE. THIS COMMENT HAS NOT BEEN |
| | ADDRESSED. SHOW COMPLIANCE WITH FBC 712.3 AND 712.4. |
| | |
| | 24. OK |
| | |
| | 25. THIS COMMENT REMAINS ESSENTIALLY UNADDRESSED. AS |
| | LONG AS THE GENERATOR IS SHOWN AS PART OF THIS PERMIT |
| | APPLICATION, ALL RELEVANT INFORMATION (SEE PREVIOUS |
| | REVIEW COMMENT #25) SHALL BE PROVIDED PRIOR TO PERMIT |
| | ISSUANCE. |
| | NOTE: ADDITIONAL COMMENTS ARE POSSIBLE DUE TO THE LACK |
| | OF INFORMATION. |
| | |