Plan Review Notes
Plan Review Notes For Permit 07060707
Permit Number 07060707
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2008-02-27 17:56:44*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 06.FIRE ALARM SYSTEM SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.ADD COMMENT TO THE FIRE ALARM
 NOTES
  
 07.A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING. SHOW
 THE LOCATION OF THE KNOX BOX IN AN ACCESSIBLE LOCATION
 ON THE APPROPIATE EXTERIOR ELEVATION..FOR
 APPLICATIONS, CONTACT WPB FIRE PREVENTION BUREAU AT
 561-804-4724.ANY INQUIRIES AND/OR REQUIREMENTS TO
 THIS MATTER SHALL BE WITH THE AHJ = CITY OF WEST PALM
 BEACH, NOT PALM BEACH COUNTY
  
 15.IN ADDITION TO THE ELECTRONIC SWITCHES FOR THE
 DOUBLE CHECK DETECTOR ASSEMBLY (DCDA), CHAIN AND LOCK
 WILL BE REQUIRED.ADD COMMENT TO AN APPROPIATEFP
 SHEET
  
 16.FLOW TEST DATA (03/28/07) WAS GATHERED BY PALM
 BEACH COUNTY FIRE DEPARTMENT.IF THIS PROJECT IS TRULY
 IN THE JURISDICTION OF THE CITY OF WEST PALM BEACH, WHY
 WASN'T THE DATA SUPPLIED BY WEST PALM BEACH FIRE
 RESCUE'S PREVENTION DIVISION.ANY INQUIRIES AND/OR
 REQUIREMENTS TO THIS MATTER SHALL BE WITH THE AHJ =
 CITY OF WEST PALM BEACH, NOT PALM BEACH COUNTY
  
 17.KNOX LOCKING CAPS WILL BE REQUIRED ON THE FIRE
 DEPARTMENT CONNECTIONS (FDC).CONTACT 561-804-4724 FOR
 APPLICATIONS.ANY INQUIRIES AND/OR REQUIREMENTS TO
 THIS MATTER SHALL BE WITH THE AHJ = CITY OF WEST PALM
 BEACH, NOT PALM BEACH COUNTY
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722