| Date |
Text |
| 2008-02-27 17:56:44 | *****DENIED***** |
| | |
| | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE |
| | PLAN REVIEW STILL NEED TO BE ADDRESSED: |
| | |
| | 06.FIRE ALARM SYSTEM SHALL BE UL CERTIFIED FOR |
| | CENTRAL STATION SERVICE.ADD COMMENT TO THE FIRE ALARM |
| | NOTES |
| | |
| | 07.A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING. SHOW |
| | THE LOCATION OF THE KNOX BOX IN AN ACCESSIBLE LOCATION |
| | ON THE APPROPIATE EXTERIOR ELEVATION..FOR |
| | APPLICATIONS, CONTACT WPB FIRE PREVENTION BUREAU AT |
| | 561-804-4724.ANY INQUIRIES AND/OR REQUIREMENTS TO |
| | THIS MATTER SHALL BE WITH THE AHJ = CITY OF WEST PALM |
| | BEACH, NOT PALM BEACH COUNTY |
| | |
| | 15.IN ADDITION TO THE ELECTRONIC SWITCHES FOR THE |
| | DOUBLE CHECK DETECTOR ASSEMBLY (DCDA), CHAIN AND LOCK |
| | WILL BE REQUIRED.ADD COMMENT TO AN APPROPIATEFP |
| | SHEET |
| | |
| | 16.FLOW TEST DATA (03/28/07) WAS GATHERED BY PALM |
| | BEACH COUNTY FIRE DEPARTMENT.IF THIS PROJECT IS TRULY |
| | IN THE JURISDICTION OF THE CITY OF WEST PALM BEACH, WHY |
| | WASN'T THE DATA SUPPLIED BY WEST PALM BEACH FIRE |
| | RESCUE'S PREVENTION DIVISION.ANY INQUIRIES AND/OR |
| | REQUIREMENTS TO THIS MATTER SHALL BE WITH THE AHJ = |
| | CITY OF WEST PALM BEACH, NOT PALM BEACH COUNTY |
| | |
| | 17.KNOX LOCKING CAPS WILL BE REQUIRED ON THE FIRE |
| | DEPARTMENT CONNECTIONS (FDC).CONTACT 561-804-4724 FOR |
| | APPLICATIONS.ANY INQUIRIES AND/OR REQUIREMENTS TO |
| | THIS MATTER SHALL BE WITH THE AHJ = CITY OF WEST PALM |
| | BEACH, NOT PALM BEACH COUNTY |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS |
| | ADDRESSED. |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |