| 2008-02-07 20:07:48 | 2008-02-07 20:07:48 |
| | |
| | *** DENIED 2ND REVIEW*** |
| | |
| | |
| | NEW GRACE PAVILION |
| | PEGGY ADAMS ANIMAL RESCUE LEAGUE. |
| | |
| | *** PLEASE SEE THERE ARE ITEMS FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE ALSO SEE |
| | THERE ARE ALSO NEW NOTES DUE TO CHANGES, NEW ITEMS OR |
| | NOTES BASED ON NEW DOCUMENTS NOT PREVIOUSLY SUBMITTED, |
| | ** AS MENTIONED ON PREVIOUS REVIEW ALL ITEMS COULD NOT |
| | BE REVIEWED AND THERE MAY BE NEW COMMENTS WHICH COULD |
| | NOT HAVE BEEN MADE. |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WHICH |
| | MENTIONED TO SEE CODE REFLECTED ON PLANS NEED TO BE |
| | CHANGED TO THE CURRENT CODE IN WHICH THE PROJECT WAS |
| | UNDER FOR DESIGN. A COUPLE OF EXAMPLES WERE GIVEN AND |
| | STILL NEED TO ADDRESS THESE. |
| | PLEASE SEE WITH THE EXCEPTION OF THE CORRECTION FOR |
| | CODES REFLECTED ON THE BOTTOM OF PANEL P1-S2, ALL OTHER |
| | PANELS STILL SHOW CODE FROM THE 1999 NFPA-70. PLEASE |
| | SEE THIS SAME CODE 220.13 IS STILL ALSO BEING REFLECTED |
| | ON THE PANEL P4 EVEN AS THIS DOES NOT APPLY TO THIS |
| | RESIDENTIAL UNIT. PLEASE ADJUST. |
| | PLEASE SHEET E-301 OCTAGONAL NOTE #6 WHICH REFLECTS |
| | 250.81C WHICH IS FROM THE 1996 NFPA-70. PLEASE BE SURE |
| | TO GO OVER PLANS AND ADJUST ANY CODE REFERENCED. FBC |
| | 106.1.2 FOR COORDINATION. |
| | |
| | 2) NOTE: PLEASE CLARIFY WHY THE RESPONSE NOTES CONTAIN |
| | A BOOKLET FOR CAPRI ENGINEERING IN THE MIDDLE OF NOTES |
| | SHOWING PROJECTS ETC. IF THIS PROJECT IS BEING |
| | SUBMITTED AS PRIVATE PROVIDER PLEASE FOLLOW |
| | REQUIREMENTS OF FS 553.791. AS THIS PROJECT HAS NOT |
| | BEEN SUBMITTED PREVIOUSLY UNDER FS 553.791 WITH ALL |
| | DOCUMENTS REQUIRED IT IS UNCLEAR WHY OTHER DOCUMENTS |
| | WERE SUBMITTED. |
| | PLEASE ALSO VERIFY CURRENT DOCUMENTS FROM CAPRI |
| | ENGINEERING AS THESE MAY BE UPDATED. |
| | |
| | 3) NOTE: PLEASE BE SURE TO MAKE SURE ADDRESSING ON ALL |
| | DOCUMENTS SUBMITTED IS REFLECTED TO THE NEW ADDRESS |
| | ASSIGNED BY THE ADDRESSING REVIEWER. |
| | PLEASE SEE FOR EXAMPLE: PLANS SHOW 3100, PERMIT |
| | APPLICATION SHOWS 3200 AND ENERGY CALCULATIONS SHOW |
| | 3200. |
| | FBC ADMIN SECTION 106.1.2, 106.5 |
| | FAC 61G1-16.004, 61G15-23.002 |
| | |
| | 4) NOTE: PLEASE SEE NOTES FROM OTHER TRADES FOR ANY |
| | REFERENCES TO THE GENERATOR, LOCATION, SCREENING ETC. |
| | PLEASE SUBMIT CALCULATIONS FOR BUILDING REVIEW OF SLAB |
| | DETAIL. PLEASE KNOW IF IN A FLOOD ZONE, THE UNIT SHALL |
| | BE REQUIRED TO BE A MINIMUM OF 6INCHES ABOVE GRADE. |
| | PLEASE SEE THE PLANS SHOW A SLAB THICKNESS OF ONLY |
| | 4INCHES FOR THIS 1000KW GENERATOR. PLEASE KNOW THE |
| | INSTALLATION SHALL MEET NFPA-110CHAPTER 7 AND MINIMUM |
| | INSTALLATION REQUIREMENTS AS SET-FORTH BY THE GENERATOR |
| | MANUFACTURE. |
| | PLEASE BE SURE TO SEE ANY POSSIBLE COMMENTS FROM OTHER |
| | REVIEWERS WITH RESPECT TO THE GENERATOR ON THE OTHER |
| | TRADE PLANS SUCH AS ARCHITECTURAL SITE PLANS, LANDSCAPE |
| | ETC. THIS IS GIVEN FOR INFORMATION ONLY BY THIS |
| | REVIEWER AS THIS INFORMATION WAS FORWARDED TO OTHER |
| | TRADES TO PLACE IN COMMENTS AS APPLICABLE. |
| | PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS ON THIS |
| | UNIT AND FUEL TANK. THE FUEL TANK WILL BE REVIEWED BY |
| | MECHANICAL AND FIRE REVIEW AND PLEASE SEE NOTES FROM |
| | THOSE TRADES WITH RESPECT TO DERM STAMPS REQUIRED BASED |
| | ON THE SIZE OF FUEL CAPACITY. |
| | FBC 106.1.2 |
| | NEC 110.3, 90.7 |
| | |
| | 5) NOTE: PLEASE SEE THE RISER SHOWS GFP (GROUND FAULT |
| | PROTECTION) ON THE GENERATOR UNIT ITSELF. IS THIS NOT |
| | TO READ GFS, (GROUND FAULT SENSING) OR GFA (GROUND |
| | FAULT ALARM) ? THE CODE REQUIRES THE GFP PROTECTION ON |
| | THE NORMAL SIDE OF THE SERVICE EQUIPMENT, BUT NOT ON |
| | THE EMERGENCY SIDE. THE CODE DOES REFERENCE GROUND |
| | FAULT SENSING. |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR |
| | THIS UNIT AS NOTED ABOVE AND FOR THE ATS DEVICE. 110.3, |
| | 90.7 |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | THE RISER STATES TO SEE SPECS FOR THE ATS YET COULD NOT |
| | LOCATE ANY SUBMITTED IN PACKAGE. |
| | |
| | 6) NOTE: PLEASE SEE THE RISER HAS THIS GENERATOR AS A |
| | SEPARATELY DERIVED UNIT WHICH IS CODE COMPLIANT AND |
| | CORRECT HOWEVER PLEASE SEE THE RISER DOES NOT SHOW ANY |
| | GROUNDING ELECTRODE SYSTEM FOR THIS UNIT. PLEASE SEE |
| | 250.20, 250.30, 250.50. |
| | PLEASE SEE NFPA-110 6.2.1.5 |
| | |
| | 7) NOTE: PLEASE SEE THE RAISED SEAL FROM THE ENGINEER |
| | ON THE SEVERAL SHEETS AND SUPPORTING DOCUMENTS ARE ONCE |
| | AGAIN FAINT ON MANY SHEETS WHERE THE LICENSE |
| | INFORMATION CAN NOT BE SEEN. THIS WAS A COMMENT ON |
| | PREVIOUS REVIEW AND RESPONSE WAS THIS WILL BE |
| | ADDRESSED. MOST SHEETS ARE OK, HOWEVER SOME ARE STILL |
| | NOT READABLE. PLEASE SEE ENERGY CALCULATIONS FOR |
| | EXAMPLE AS ONE OF THE SETS COULD NOT BE READ. PLEASE |
| | SEE FAC 61G15-23.001 WHICH REQUIRES ALL INFORMATION TO |
| | BE CLEAR AND VISIBLE. |
| | |
| | 8) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS FOR |
| | REVIEW AND BE SURE TO COORDINATE ALL INFORMATION ON THE |
| | INPUT DATA REPORT WITH THE LIGHTING ON PLANS AND THE |
| | FIXTURE LEGEND. 13-415.1.A, 13-415.1.AB, 13-415.2 THE |
| | INPUT DATA REPORT IN THE REST OF THIS COMMENT WILL BE |
| | REFLECTED AS IDR. |
| | |
| | A) ** PLEASE BE SURE TO GO THROUGH ALL ITEMS ON THE |
| | INTERIOR LIGHTING SHOWN ON THE IDR AND COORDINATE WITH |
| | PLANS. PLEASE SEE THERE ARE DIFFERENCES IN THE AMOUNT |
| | OF FIXTURES, THE WATTAGES/TOTALS AND THE METHOD OF |
| | CONTROLS. |
| | PLEASE SEE FOR EXAMPLE: LOBBY AREA LIGHTING ON PLANS |
| | DOES NOT MATCH WITH THE AMOUNT AND TYPE OF FIXTURES ON |
| | THE IDR. |
| | PLEASE SEE FOR EXAMPLE: THE METHODS OF CONTROL FOR SOME |
| | ARE BEING SHOWN AS *MANUAL ON/OFF* YET THE METHOD OF |
| | CONTROL IS AN AUTOMATED MEANS. PLEASE GO OVER ALL |
| | FIXTURES ON PLANS AND COORDINATE WITH THE IDR. THIS |
| | OFFICE CAN NOT EMPHASIZE ENOUGH THE IMPORTANCE. THE |
| | ENERGY CALCULATIONS SUBMITTED DATED JUNE 07 AND DEC 07 |
| | ARE NOT CHANGED. |
| | |
| | B) ** PLEASE BE SURE TO GO OVER PLANS AND THE SQUARE |
| | FOOTAGE INFORMATION ON THE CALCULATIONS SUBMITTED. |
| | PLEASE SEE THE PERMIT APPLICATION STATES A SQ FT LESS |
| | THAN CALCULATIONS AND THE CALCULATIONS COVER SHEET IS |
| | LESS THAN THATOF THE SQ FT SHOWN ON THE ARCHITECTURAL |
| | PLANS. |
| | 13-415.1.A, 13-400.3.A |
| | |
| | C) ** PLEASE BE SURE ALL INFORMATION ON PLANS FOR |
| | EXTERIOR LIGHTING COORDINATES WITH THE IDR AND THE |
| | FIXTURE LEGEND. PLEASE SEE FOR AN EXAMPLE: THE IDR FOR |
| | EXTERIOR LIGHTING SHOWS A TOTAL OF 24 -40WATT FIXTURES. |
| | HOW IS THIS POSSIBLE WHEN NOT ONLY THE PLANS SHOWS |
| | DOZENS MORE FIXTURES FOR EXTERIOR LIGHTING FIXTURES BUT |
| | THE FIXTURE WATTAGES ON PLANS ARE SUBSTANTIALLY HIGHER |
| | THAN THE STATED 40WATTS ON THE IDR. |
| | PLEASE SEE SOME OF THESE FOR EXAMPLE ARE 400W FIXTURES, |
| | 70W, 50W ETC ETC. PLEASE SEE THE FIXTURE LEGEND FOR |
| | TYPES, P, D1, S-1, L, H ETC . THIS IS NOTED ONLY FOR A |
| | FEW. |
| | |
| | D) ** PLEASE SEE THE CLASSIFICATION OF THE EXTERIOR |
| | LIGHTING FIXTURES ON THE IDR MENTIONS * LIGHTING THAT |
| | IS SPECIFICALLY DESIGNATED AS REQUIRED BY A HEALTH OR |
| | LIFE SAFETY, STATUE, ORDINANCE, OR REGULATION*. PLEASE |
| | PROVIDE INFORMATION ON ANY OF THESE AS THERE ARE KNOWN |
| | STATUTES, ORDINANCES, LIFE SAFETY CODES ETC WHICH |
| | REQUIRES ANY OF THESE EXTERIOR LIGHT FIXTURES. PLEASE |
| | ADJUST DESIGNATIONS. |
| | |
| | E) ** PLEASE BE SURE THE ENERGY CALCULATIONS ARE |
| | SIGNED, DATED AND SEALED WITH RAISED SEAL AS NOTED |
| | ABOVE AND REQUIRED PER FAC 61G15-23.002, FS 471.025 AND |
| | FBC 13-103.1.1.1. |
| | PLEASE BE SURE THE OWNER AGENT IS ALSO SIGNED ON NEW |
| | CALCULATIONS. |
| | |
| | 9) NOTE: PLEASE SUBMIT AND SHOW ALL MAXIMUM TIMES FOR |
| | ALL LIGHTING CONTROL DEVICES PER 13-415.1.ABC.1.1, .1.2 |
| | AND .1.3 |
| | |
| | 10) NOTE: PLEASE BE SURE TO SHOW AND LABEL ALL ROOM AND |
| | AREA DESIGNATIONS ON PLANS. PLEASE SEE FOR EXAMPLE |
| | ROOMS OFF OF LOADING DOCKS/BAY AREAS WHICH DOE NOT |
| | CONTAIN ANY DESIGNATIONS. |
| | PLEASE SEE FOR EXAMPLE: THE ROOM NORTH OF STORAGE AND |
| | WEST OF MECHANICAL ROOM. PLEASE KNOW AS THESE ROOMS ARE |
| | NOT DESIGNATE * STORAGE 101* ETC THE CIRCUITING CAN NOT |
| | BE VERIFIED. |
| | FBC 106.3.5.1.2, 106.1.2 FOR COORDINATION AND |
| | ADDITIONAL INFORMATION. |
| | NEC 408.4 ETC |
| | |
| | 11) NOTE: PLEASE CORRELATE ALL CIRCUITING ON PLANS WITH |
| | THAT OF THE PANEL SCHEDULES SUBMITTED OR TO BE |
| | SUBMITTED. |
| | PLEASE SEE SOME EXAMPLES BELOW: |
| | |
| | A) ** THE WP GFI CIRCUITED FOR THE ROOF-TOP UNITS |
| | INDICATE A P-78, YET NO *P* PANEL IS ON RISER OR |
| | SUBMITTED WITH SCHEDULES. THIS IS ASSUMED AS MISPRINT. |
| | |
| | B) **PLEASE SEE PANEL P4 WHICH CONTAINS MANY CIRCUITS |
| | WHICH DO NOT CORRELATE. PLANS SHOW LAUNDRY ROOM |
| | RECEPTACLE ON CIRCUIT 4, YET THE PANEL SCHEDULE SHOWS |
| | 6. |
| | |
| | C) ** PLEASE SEE PLANS SHOWS WASHER ON CIRCUIT P-14, |
| | YET THE PANEL SCHEDULE SHOWS P-12. THIS AFFECTS THE |
| | DRYER AND OTHER CIRCUITS. |
| | |
| | D) ** PLEASE SEE P4-16 AS THIS IS BEDROOM ON PLANS AND |
| | BATH ROOM ON SCHEDULE. |
| | |
| | ** THESE ARE SOME EXAMPLES OF THE PLANS FOR ALL. PLEASE |
| | SEE THERE ARE OTHERS ALSO AND SOME ARE NOTED BELOW WITH |
| | RESPECT TO OTHER CODES AFFECTED BY MANY NOT CIRCUITED |
| | CORRECTLY. |
| | 408.4, 240.4, 310.16, ETC |
| | FBC 106.3.5.4, 106.3.5.1.2, 106.1.2 FOR COORDINATION. |
| | |
| | 12) NOTE: PLEASE SEE NFPA-70 210.11C3 WHICH REQUIRES |
| | DEDICATE BATH CIRCUIT(S) IN ONLY TWO SCENARIOS. PLEASE |
| | KNOW WHEN THE GFI IS FED IN ONE BATH ROOM AND FEEDS |
| | OTHER ITEMS IN THAT *SAME* BATH, IT MAY NOT FEED ANY |
| | OTHER ROOMS, BATHROOMS OR APPLIANCES. |
| | PLEASE SEE FOR EXAMPLE: THE CIRCUIT SHOWN ON PLANS FOR |
| | P4-18 SHOWS THE GFI BEING FED AND THEN THE PANEL |
| | SCHEDULE ALSO NOTES THIS AS FEEDING NOT ONLY THE |
| | EXHAUST FAN IN THE SAME BATHROOM WHICH IS OK, BUT THE |
| | PANEL SCHEDULE ALSO SHOWS THIS FEEDING EF-82 AND83 |
| | WHICH IS NOT PERMITTED PER CODE SECTION NOTED ABOVE. |
| | PLEASE ALSO SEE FOR EXAMPLE: THE PANEL SCHEDULE SHOWS |
| | THE P4-6 AS FEEDING BATH AND LAUNDRY ROOM COMMON |
| | RECEPTACLE WHICH IS NOT PERMITTED. THE PLANS ACTUALLY |
| | SHOW THE LAUNDRY ROOM RECEPTACLE ON WITH THE BEDROOM. |
| | |
| | 13) NOTE: PLEASE SEE THE PANEL SCHEDULE SHOWS PANEL P4 |
| | WITH THREE SMALL APPLIANCE CIRCUITS YET THE LOAD |
| | CALCULATIONS ONLY INDICATE TWO. |
| | PLEASE ALSO SEE THE PLANS ARE MISSING THE THIRD CIRCUIT |
| | ALSO: (15). |
| | PLEASE SEE 210.52B1, 210.11C1, 220.52 |
| | |
| | 14) NOTE: PLEASE SEE COUNTER SPACE IN BETWEEN RANGE AND |
| | WALL TOWARDS ELECTRICAL PANEL APPEARS TO BE MISSING A |
| | GFI RECEPTACLE PER 210.52C1 FOR 12 INCHES OR MORE OF |
| | COUNTER SPACE BASED ON SCALE ON PLANS. |
| | |
| | 15) NOTE: PLEASE SEE ARC FAULT PROTECTION IS NOT SHOWN |
| | FOR ALL OUTLETS IN THE BEDROOMS AS REQUIRED PER 210.12 |
| | OF THE 2005 NEC> |
| | PLEASE KNOW THIS REQUIRES ALL RECEPTACLES, FANS, LIGHTS |
| | ETC |
| | PLEASE SEE FOR EXAMPLE: CIRCUIT # 16 DOES NOT INDICATE |
| | ANY DOUBLE ** ASTERISK AS NOTED ON PANEL FOR AFCI |
| | BREAKER. |
| | PLEASE ADJUST. |
| | |
| | 16) NOTE: PLEASE VERIFY SOUNDING LEVELS FOR ADA |
| | COMPLIANCE ON PLANS PER FBC 11-4.28.2. |
| | |
| | 17) NOTE: PLEASE CLARIFY THE NOTE AND LOCATIONS OF |
| | LIGHTING ON SHEET E-104. THE TITLE ON THIS SHEET |
| | MENTIONS MECHANICAL SPACE STILL YET THE RESPONSE TO ONE |
| | OF THE PREVIOUS COMMENTS IS THAT MECHANICAL EQUIPMENT |
| | IS ON ROOF. |
| | PLEASE SEE THE RESPONSE TO NOTE #15 STILL MENTIONS A |
| | MEZZANINE LEVEL HOWEVER LIGHTING CONTROLS PER FBC |
| | 13-415.1.ABC.1.1 AND .1.2 ARE NOT LOCATED ON THIS |
| | SHEET. |
| | THERE IS A NOTE ON LIGHTING PLANS E-103 WHICH MENTIONS |
| | TO INDIRECT LIGHTING ABOVE. ARE THE FIXTURES ON E-104 |
| | OPEN AND ABOVE FIRST FLOOR AREA? |
| | ARE THESE SEPARATE AREAS? SEE NOTES FORM OTHER TRADES. |
| | NO FINAL DETERMINATION CAN BE DONE AT THIS TIME. |
| | |
| | 18) NOTE: PLEASE SEE THE COLOR CODING FOR THE 277/480V |
| | SYSTEM CONDUCTORS WILL BE REQUIRED TO BE BROWN, PURPLE, |
| | AND YELLOW. |
| | PLEASE KNOW FOR SEVERAL DECADES ALL OF PALM BEACH |
| | COUNTY ALONG WITH THE CITY OF WEST PALM BEACH CONTAINED |
| | TECHNICAL AMENDMENTS TO THE CODE FOR COLOR CODING OF |
| | CONDUCTORS AS NFPA-70 DOES NOT PROVIDE COLOR CODING OF |
| | SYSTEM VOLTAGES. AS THE TECHNICAL AMENDMENTS ARE NO |
| | LONGER IN EFFECT AND KEEPING WITH THE CONSISTENCY OF |
| | SAFE INSTALLATION PRACTICES WITHIN THE CITY THIS IS |
| | REQUIRED ON A LOCAL LEVEL. THE COLOR ORANGE AS STATED |
| | IN DIVISION SPECS IS CLEARLY REQUIRED FOR *HIGH-LEG* |
| | DELTA SYSTEMS IN THE NEC AND WOULD NOT APPLY FOR |
| | 277/480V SYSTEMS. |
| | PLEASE ADJUST COLOR CODING AS NOTED ABOVE. PLEASE ALSO |
| | SEE PAGE #4 IN 16120 3.01. |
| | 90.4 |
| | |
| | 19) NOTE: PLEASE CLARIFY EMERGENCY BACK UP LIGHTING. |
| | THE RESPONSE MENTIONS THAT HALF SHADED FIXTURES WILL BE |
| | BATTERY BACK UP AND DETAILS ON LIGHTING PLANS SHOW THAT |
| | BATTERIES ARE PART OF THE FIXTURE WIRING HOWEVER THE |
| | FIXTURE SCHEDULE DOES NOT CONTAIN ANY NOTES FOR BACK UP |
| | BALLAST/BATTERIES. PLEASE ALSO SEE THE SHADED FIXTURES |
| | ON THE ELECTRICAL SYMBOL LEGEND ONLY SHOWS FIXTURES |
| | *B*. |
| | PLEASE ADJUST AND COMPLETE FIXTURE LEGENDS FOR ALL NEW |
| | FIXTURES AS NOTED. |
| | LS -101 7.8, 7.9 |
| | |
| | 20) NOTE: **ONLY NOTED** ANY PROPOSED INSTALLED |
| | LIGHTNING PROTECTION SYSTEM WILL BE UNDER SEPARATE |
| | PLANS, PERMIT AND MOST IMPORTANTLY SHALL MEET |
| | NFPA-780. |
| | |
| | 21) NOTE: PLEASE CLARIFY J-BOX BEING SHOWN ABOVE |
| | CEILINGS FOR WATER COOLERS. |
| | PLEASE KNOW NO CORDS ARE PERMITTED ABOVE CEILINGS FOR |
| | CORD AND PLUG CONNECTED UNITS. |
| | PLEASE KNOW THIS CAN BE REDLINED BUT WILL STILL NEED TO |
| | SHOW FINAL CONNECTIONS PER NEC. |
| | THIS CAN BE DONE AT THIS TIME OR WILL BE NEED TO BE |
| | REVISED AT A LATER DATE. |
| | 400.8 |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 22) NOTE: PLEASE KNOW THE REQUIRED CALCULATIONS FOR |
| | SITE LIGHTING POLES MAY BE PART OF A *PROVISO* WHICH |
| | WILL REQUIRE THESE TO BE SUBMITTED BEFORE INSTALLATION. |
| | THIS IS GIVEN FOR INFORMATION AT THIS TIME. IF WIND |
| | LOAD CALCULATIONS ARE PROVIDED AT THIS TIME, THERE WILL |
| | BE NO NEED FOR PROVISO. |
| | |
| | 23) NOTE: PLEASE SEE THERE IS A LOSS IN TRANSLATION FOR |
| | THE CLARIFICATION OF THE PANEL RATINGS. THE PREVIOUS |
| | REVIEW NOTES MENTIONED THERE WERE SEVERAL PANELS SHOWN |
| | AS 60AMP RATED MAIN LUG ONLY PANELS AND 30 CIRCUITS. |
| | THE COMMENT MENTIONED THAT THIS OFFICE WAS NOT AWARE OF |
| | 30CIRCUIT 60AMP RATED MLO PANELS AND TO VERIFY. THE |
| | PLANS HAVE NOW COME BACK WITH 42CIRCUIT 60AMP RATED MLO |
| | PANELS. |
| | IF THE PANEL IS FED FROM A 60AMP BREAKER THIS WOULD NOT |
| | BE A 60AMP RATED MLO PANEL. IT WOULD STILL BE RATED AT |
| | THE AMPERAGE RATING OF THE PANEL. IE; 150A RATED, 200 |
| | AMP RATED, 225AMP RATED MLO. |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR ANY |
| | 60AMP RATED 42 CIRCUIT PANELS. |
| | 110.3, 90.7. |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION |
| | |
| | 24) NOTE: PLEASE CLARIFY THE AIC RATINGS OF ALL THE |
| | PANELS AND EQUIPMENT. PLEASE SEE FOR EXAMPLE THE SAME |
| | PANELS AS NOTED ABOVE IN NOTE #23 ARE BEING SHOWN WITH |
| | A 22,000 RATING. IS THIS FOR THE PANEL? THE BRANCH |
| | BREAKERS? OR BOTH? |
| | PLEASE SEE THE MSB IS SHOWN AS 42,000 AIC RATED ON |
| | SCHEDULE YET THE NOTES ON RISER ON SHEET E-301 MORE |
| | SPECIFICALLY MSB NOTES 2A INDICATES 100,000 AIC RATED |
| | MAIN. WHICH ONE IS THIS? |
| | PLEASE INDICATE THE RATINGS OF PANELS AND BRANCH |
| | BREAKERS AND ANY MAIN BREAKERS. |
| | IF THE AIC RATING IS SHOWN AS 22K, THEN THIS IS WHAT |
| | WILL BE REQUIRED TO BE INSTALLED. |
| | 110.9, 110.3, 90.7 |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 25) NOTE: PLEASE SEE THE CEILING FANS IN THE |
| | RESIDENTIAL UNIT WILL REQUIRE LIGHT KITS OR OTHER MEANS |
| | OF TURNING ON LIGHTING IN ROOMS PER 210.70 SHALL BE |
| | SUPPLIED. THIS CAN BE DONE WITH SWITCHED RECEPTACLE OR |
| | OTHER LIGHTING MEANS. THE FIXTURE LEGEND FOR FANS |
| | INDICATES NO LIGHTING TO BE A PART OF THE FANS. IN FACT |
| | IT IS BLANK. |
| | LS 101 7.8 |
| | |
| | 26) NOTE: PLEASE KNOW AS MENTIONED ON PREVIOUS REVIEW |
| | AND IN MEETING HELD AFTER THE FIRST REVIEW, IF THE |
| | DISCONNECTING MEANS ON THE GENERATOR DOES NOT MEET THE |
| | *EXCEPTIONS* IN THE CODE MORE SPECIFICALLY 702.11. A |
| | DISCONNECT RATED FOR THE LOAD SERVED SHALL BE REQUIRED |
| | AT THE BUILDING PER 225.31-225.39. THIS DISCONNECT AS |
| | PREVIOUSLY MENTIONED DOES NOT REQUIRE OVER CURRENT |
| | PROTECTION. THIS ONLY REQUIRES DISCONNECT TO BE RATED |
| | FOR THE LOAD SERVED. THE SHUNT/BUTTON SHOWN ON RISER |
| | DOES NOT MEET CODE FOR THIS REQUIREMENT. |
| | |
| | 27)NOTE: PLEASE SEE NOTICE TO FLORIDA STATUTES |
| | 553.80(2)(B) IS BEING GIVEN WITH RESPECT TO REPEAT |
| | COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY GIVEN AS A |
| | NOTICE AT THIS TIME. |
| | PLEASE KNOW THAT ONE SET OF ELECTRICAL PLANS MAY BE |
| | RETAINED BY THIS OFFICE ALONG WITH ONE SET OF THE |
| | ENERGY CALCULATIONS. |
| | |
| | 28) NOTE: PLEASE CONFIRM THE LOCATION OF THE FACP WHICH |
| | IS NOW IN THE TELECOM ROOM. |
| | PLEASE BE SURE TO CONTACT THE FIRE MARSHAL AS THIS WILL |
| | HAVE AN AFFECT ON THE ELECTRICAL PLANS AND ANY |
| | RELOCATION NEEDED. |
| | |
| | ** AS THERE ARE ITEMS NOT YET SUBMITTED, OR ITEMS FROM |
| | OTHER TRADES WHICH MAY AFFECT PROJECT DESIGN, PLEASE |
| | KNOW THAT ANY CHANGES ETC WHICH ARE NOT PART OF THIS |
| | SUBMITTED PACKAGE COULD NOT BE REVIEWED AT THIS TIME. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2008-02-06 19:31:37 | 2008-02-06 19:31:37 |
| | |
| | ONE SET OF PLANS AND SPECS IN ELEC FOR REVIEW. |