Plan Review Notes
Plan Review Notes For Permit 07060707
Permit Number 07060707
Review Stop P
Sequence Number 1
Notes
Date Text
2007-08-23 11:59:28DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 1. SHT G-001 OCCUPANCY DATA. PLEASE CLARIFY SQUARE
 FOOTAGE FOR THE BUSINESS AND STORAGE OCCUPANCY. PER
 DATA INDICATED IT SEEM THAT THE AREA FOR THE STORAGE IS
 APPROXIMATLY TWICE THAT OF THE BUSINESS AREA. LOOKING
 AT THE FLOOR PLAN THIS DOES NOT SEEM TO BE THE CASE.
 PLEASE INDICATE EACH AREA TO BE INDICATED AS STORAGE
 WITH THE SQUARE FOOTAGE FOR EACH AREA. ALSO INDICATE
 EACH AREA TO BE BUSINESS OCCUPANCY AND SHOW SQUARE
 FOOTAGE OF EACH AREA. SECTION 106.3.5.1.1(2). THIS WILL
 HELP VERIFY OCCUPANCY DATA.
  
 2. SHT G-001 BUILDING DATA INDICATES 37,772SF, BUT THE
 APPLICATION INDICATES 27,308SF. PLEASE CORRELATE
 INFORMATION ON PLANS WITH THE APPLICATION. SECTION
 106.1.1.
  
 3. CIVIL DRAWINGS. THE ADDRESS FOR THE ENGINEERING
 CONPANY IN THE TITLE BLOCK DOES NOT REFLECT THE ADDRESS
 INDICATED ON THE FLORIDA STATE DBPR WEBSITE. PLEASE
 UPDATE THE WEBSITE OR THE TITLE BLOCKS PRIOR TO
 RESUBMITTING. ALSO THE ENGINEER SHALL LEGIBLY INDICATE
 HER ADDRESS IN THE TITLE BLOCK.FAC 61G15-23.002(2) &
 FS 471.025. PLEASE INDICATE ENGINEER'S ADDRESS.
  
 4. SHTS L-1 THRU L-6 THEFIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE
 TITLE BLOCK PER FAC 61G1-16.004(2) & FS 481.219,
 481.2055. PLEASE SHOW FIRM LICENSE NUMBER IN TITLE
 BLOCK.
  
 5. ALL ARCHITECTURAL SHEETS. THE SIGNATURE IS REQUIRED
 FOR THE ARCHITECT. IT APPEARS THAT INITIALS HAVE BEEN
 USED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 ARCHITECT, THEN A SIGNED, SEALED, DATED, NOTORIZED
 LETTER INDICATING THE LEGAL SIGNATURE OF THE ARCHITECT
 SHALL BE SUBMITTED FOR OUR FILES. FAC 61G1-16.003,
 61G1-16.004(5) & FS 481.2055.
  
 6. SHT A-104 DETAILS 1 THRU 4. SHOW THE 5' TURNING AREA
 REQUIRED IN THE TOILET ROOMS PER SECTION 11-4.22.3.
  
 7. SHT A-104 DETAIL 4 SHOW THE CLEAR FLOOR SPACE FOR
 ALL REQUIRED ACCESSIBLE FIXTURES PER SECTIONS
 11-4.16.2, 11-4.19.3 & 11-4.21.2.--A TURNING AREA
 IS REQUIRED FOR THE SHOWER ROOMS PER SECTION 11-4.2.3.
 PLEASE SHOW ON DETAIL.--DOORS SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE. SECTION
 11-4.23.2. THIS WILL INCLUDE THE SHOWERS AND THE LAVS
 OUTSIDE THE SHOWERS.
  
 8. SHT A-104 DETAIL 4. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.5 FLUSH CONTROLS
 ___FOR LAVS:
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 ___FOR SHOWERS:
 A. 11-4.21.2 SIZE & CLEARANCES
 B. 11-4.21.3 SEAT
 C. 11-4.21.4 GRAB BARS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.6 SHOWER UNIT
 F. 11-4.21.7 CURBS
  
 9. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING
 FOUNTAINS. SHOW COMPLIANCE WITH THE SECTION 11-4.15 AND
 ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 10. SHT A-300 SUBMIT CALCULATIONS FOR PRIMARY &
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS & TABLES. SHOW THE SQUARE FOOT AREA OF EACH
 ROOF DRAIN WITH 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS AS WELL AS THE SQUARE FOOTAGE OF ALL
 ROOFS THAT DRAIN ONTO EACH AREA FROM ABOVE ADDED IN THE
 CALCULATIONS.
  
 11. SHT A-300 LOWER ROOF ON THE WEST SIDE OF THE
 BUILDING INDICATES R5 TYP FOR O.S. DETAIL R5 INDICATES
 A PARAPET WALL. SECONDARY ROOF DRAIS REQUIRED PER
 SECTION 1107.2. IS THE DRAIN SHOWN A SCUPPER DRAIN OR
 AN OVERFLOW SCUPPER DRAIN? PLEASE CLARIFY AND INDICATE
 SECONDARY DRAIN. SECTION 106.1.1.
  
 12. SHT A-300 UPPER ROOF AT N.E. CORNER INDICATES R5 AS
 AN O.S. PLEASE CLARIFY.--LOWER ROOF DRAINS ARE
 INDICATED AS O.S., NOT PRIMARY SCUPPER DRAINS. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 13. SHT A-300 INDICATES R15 FOR THE SCUPPER WITH
 DOWNSPOUT & O.S. R15 SHOWS NO COLLECTOR HEAD OR
 DOWNSPOUT. ALSO SHEET A-400 SHOWS NO DOWNSPOUTS. PLEASE
 CLARIFY AND INDICATE THE SIZE OF THE DOWNSPOUTS AND
 SHOW COLLECTOR HEAD WITH DIMENSIONS. TABLES 1106.3 &
 1106.7.--ALSO INDICATE HOW THE PRIMARY DRAIN & O.S.
 CAN BE AT THE ROOF LEVEL. SECTIONS 1503.4.2 &
 1503.4.3.
  
 14. SHT A-709 DETAILS 79 & 81. SHOW COMPLIANCE WITH
 SECTION 11-4.24 & ALL SUBSECTIONS. NOTE: FORWARD
 APPROACH REQUIRED ON CLEAR FLOOR SPACE AND CABINET
 DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE.
  
 15. ALL PLUMBING, MECHANICAL, ELECTRICAL & FIRE
 PROTECTION SHEETS. THE ENGINEER SHALL LEGIBLY INDICATE
 THEIR ADDRESS. FAC 61G15-23.002(2) & FS 471.025.
  
 16. SHT P0-1-1 IS INDICATED AS HVAC LEGEND, SCHEDULE &
 GENERAL NOTES IN THE SHEET TITLE. PLEASE CHANGE
 REFERENCE TO IDENTIFY INFORMATION ON SHEET. SECTION
 106.1.1.
  
 17. SHT P0-101 THE MAXIMUM DISTANCE OF THE FIXTURE TRAP
 FROM THE VENT SHALL COMPLY WITH TABLE 906.1. SOME FLOOR
 DRAINS APPEAR TO EXCEED THE LIMIT, BUT NO PIPE/TRAP
 SIZE IS INDICATED. PLEASE CHECK THE DISTANCE FROM THE
 VENT AND INDICATE PIPE/TRAP SIZE. TABLE 709.1.
  
 18. SHT P1-101. SUBMIT THE MANUF. SPECIFICATION SHEETS
 FOR THE SN-1 FIXTURE INCLUDING INSTALLATION
 INSTRUCTIONS. SECTION 106.1.2.
  
 19. SHT P1-101 SUBMIT A DETAIL FOR THE CANINE
 PRE-OP/POST-OP KENNELS. SHOW A DETAIL FOR THE WATER
 BACKFLOW PROTECTION AND CONNECTION TO THE DOG BOWLS.
 SECTION 608. SHOW THE CONNECTION TO THE TRENCH DRAINS
 AND THE SN-1 FIXTURES. SECTION 106.1.2. (SN-1 FIXTURES
 NOT SHOWN ON THE ISOMETRIC RISER DIAGRAM. CLARIFY).
  
 20. SHT P1-103 SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING REQUIREMENTS SHALL BE SUBMITTED FOR GAS
 REVIEW:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505. (NOT SHOWN FOR GB1
 UNITS).
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 21. SHT P1-103 DETAIL (2) GB1(1300MBTH) NOT INDICATED
 ON THE PLUMBING EQUIPMENT SCHEDULE ON SHT P5-101.
 PLEASE IDENTIFY THESE FIXTURES. SECTION 106.1.2.
  
 22. SHT P1-105 A RELIEF VENT, (GOOSE-NECK) FITTING
 SHALL BE INSTALLED IN THE CONDENSATE DRAIN LINE AS IT
 EXITS THE BUILDING.
  
 23. SHT P2-101 WATER HAMMER ARRESTORS ARE REQUIRED ON
 ALL QUICK CLOSING VALVES PER SECTION 604.9. (ICE
 MAKERS, DISH WASHERS, WASH MACHINES ETC.). PLEASE SHOW
 ON THE WATER ISOMETRIC RISER DIAGRAM. WHA'S TO BE
 LOCATED NEAR THE FIXTURE, NOT IN THE CEILING. PDI-WH
 201.
  
 24. SHT P2-101 2" WATER SUPPLY LINE DOES NOT CONNECT TO
 THE WATER SUPPLY LINE IN THE CEILING ABOVE THE
 VESTIBLUE FOR THE MEN'S LOCKER ROOM. (ALSO SEE SHT
 P1-103). SECTION 106.1.1. PLEASE INDICATE WHERE THE 2"
 CW CONNECTS.
  
 25. SHT P2-101 PLEASE IDENTIFY THE FIXTURE THAT
 CONNECTS TO THE COLD WATER SUPPLY LINE THEN INDICATES
 HOT WATER LINE CONNECTING TO THE 3/8TH" STAINLESS STEEL
 TUBING INDICATED AS A COLD WATER LINE. THIS IS ABOVE
 ROOM #174. PLEASE CLARIFY SECTION 106.1.2.
  
 26. SHT P2-101 SHOW ALL PIPE SIZES. SECTIONS 106.2.1 &
 604.
  
 27. SHT P3-101 SHOW ALL PIPE SIZES AND INDICATED ON THE
 SANITARY ISOMETRIC RISER DIAGRAM THE DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM. TABLES 709.1, 710.1(1) &
 710.1(2).
  
 28. SHT P3-101 INDICATE HOW THE VENT CONNECTS TO THE
 BRANCH LINE BEHIND THE W/C IN TOILET ROOM 183. SECTIONS
 905.3 & 905.4. (ALSO SEE SHT P1-101).
  
 29. SHT P3-101 A TRAP AND A VENT ARE REQUIRED FOR THE
 SINK IN ROOM 172. SECTIONS 901.2.1 & 1002.1. (ALSO SEE
 SHT P1-101).
  
 30. SHT P3-101 NOT ALL KENNELS SHOW A TD1. PLEASE
 CLARIFY. (ALSO SEE SHT P1-101). SECTION 106.2.1.
  
 31. SHT P3-101 TRAPS FOR TD1'S ON SANITARY RISER
 ISOMETRIC DIAGRAM ARE NOT LEGIBLE. PLEASE CLARIFY HOW
 THE TRAPS ARE TO BE CONNECTED TO THE BRANCH LINE.
 SECTION 106.1.1.
  
 32. SHT P3-101 NOTE "PROVIDE FUNNEL" FOR RESIDENTIAL
 AREA CONDENSATE NOT APPROVED. CONDENSATE SHALL NOT
 DRAIN INTO THE SANITARY SYSTEM. CONDENSATE SHALL DRAIN
 SEPARATELY OUT OF THE BUILDING AND TERMINATE INTO THE
 STORM, A CATCH BASIN, DRWELLL, OR PLANTED AREA A
 MINIMUM 1 FOOT FROM THE STRUCTURAL WALL.MUNICIPAL
 CODE ARTICLE III SECTION 90-125(5). PLEASE INDICATE HOW
 CONDENSATE TO BE DRAINED FROM RESIDENTIAL AREA. SECTION
 106.1.2.
  
 33. SHT P3-101 THE WASH MACHINES REQUIRE A STANDPIPE,
 MINIMUM 18" AND A CLEANOUT, MINIMUM 4FT ABOVE THE
 FLOOR. SECTIONS 708.9 & 802.4. PLEASE SHOW ON THE SANT.
 RISER DIAGRAM.
  
 34. SHT P3-101 CLEANOUTS REQUIRED PER SECTIONS 708.3.1
 & 708.3.5. PLEASE INDICATE ON THE SANT. RISER DIAGRAM &
 ON THE FLOOR PLANS SHTS P1-101, P1-102 & P1-103.
  
 35. SUBMIT STORM RISER DIAGRAMS . SHOW ALL PIPE SIZES &
 INDICATE SQUARE FOOTAGE AS IT ACCUMULATES IN THE
 SYSTEM. ALSO SHOW ALL CLEANOUTS REQUIRED BY SECTION
 1101.8. (ALSO SHOW CLEANOUTS ON SHT P1-105).
 106.3.5.1.3(7)(13).
  
 36. SUBMIT A CONDENSATE RISER DIAGRAM. INDICATE ALL
 PIPE SIZES AND SHOW PIPES FROM A/C UNIT THRU
 TERMINATION. INDICATE MATERIAL FOR CONDENSATE PIPING.
 SECTION 106.3.5.1.3(13).
  
 37. SHT P4-1-1 WATER HAMMER ARRESTOR DETAIL. THE
 LOCATION OF THE WATER HAMMER ARRESTORS SHALL BE NEAR
 THE FIXTURE, IN AN "EFFECTIVE RANGE" NOT IN THE CEILING
 AS SHOWN. PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
  
 38. SHT P4-101 PACKAGED WATER HEATER-STORAGE
 RECIRCULATION SYSTEM GWH-1. THE COLD WATER SUPPLY TURNS
 INTO HOT WATER SUPPLY AFTER THE DROP. PLEASE CLARIFY.
 --THE COLD WATER SUPPLY IS SHOWN TO THE STORAGE TANK.
 PLEASE EXPLAIN.--HOT & COLD INLETS TO THE STORAGE
 TANK? CLARIFY. SECTION 106.1.1.--A VACUUM RELIEF
 VALVE IS REQUIRED FOR ALL BOTTOM FED WATER HEATERS.
 SECTION 504.2.--THE FLOOR DRAIN IS NOT AN APPROVED
 INDIRECT WASTE RECEPTOR. A FLOOR SINK OR A HUB DRAIN IS
 REQUIRED. SECTIONS 802.3 & 802.3.2.
  
 39. SHT P4-101 GAS WATER HEATER FLUE DETAIL SHOWS 2
 VENTS. IS THE CAT 1, CLASS B VENT TO THE WALL A DIRECT
 VENT? PLEASE CLARIFY. (IF DIRECT VENT, CLASS B NOT
 REQUIRED). SECTION 106.1.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. RESUBMIT
 MARKED UP PLUMBING SHEETS TO ALLSO HELP EXPEDITE PLAN
 REVIEW. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS