| Date |
Text |
| 2007-08-23 11:59:28 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY WPB MUNICIPAL CODE |
| | |
| | 1. SHT G-001 OCCUPANCY DATA. PLEASE CLARIFY SQUARE |
| | FOOTAGE FOR THE BUSINESS AND STORAGE OCCUPANCY. PER |
| | DATA INDICATED IT SEEM THAT THE AREA FOR THE STORAGE IS |
| | APPROXIMATLY TWICE THAT OF THE BUSINESS AREA. LOOKING |
| | AT THE FLOOR PLAN THIS DOES NOT SEEM TO BE THE CASE. |
| | PLEASE INDICATE EACH AREA TO BE INDICATED AS STORAGE |
| | WITH THE SQUARE FOOTAGE FOR EACH AREA. ALSO INDICATE |
| | EACH AREA TO BE BUSINESS OCCUPANCY AND SHOW SQUARE |
| | FOOTAGE OF EACH AREA. SECTION 106.3.5.1.1(2). THIS WILL |
| | HELP VERIFY OCCUPANCY DATA. |
| | |
| | 2. SHT G-001 BUILDING DATA INDICATES 37,772SF, BUT THE |
| | APPLICATION INDICATES 27,308SF. PLEASE CORRELATE |
| | INFORMATION ON PLANS WITH THE APPLICATION. SECTION |
| | 106.1.1. |
| | |
| | 3. CIVIL DRAWINGS. THE ADDRESS FOR THE ENGINEERING |
| | CONPANY IN THE TITLE BLOCK DOES NOT REFLECT THE ADDRESS |
| | INDICATED ON THE FLORIDA STATE DBPR WEBSITE. PLEASE |
| | UPDATE THE WEBSITE OR THE TITLE BLOCKS PRIOR TO |
| | RESUBMITTING. ALSO THE ENGINEER SHALL LEGIBLY INDICATE |
| | HER ADDRESS IN THE TITLE BLOCK.FAC 61G15-23.002(2) & |
| | FS 471.025. PLEASE INDICATE ENGINEER'S ADDRESS. |
| | |
| | 4. SHTS L-1 THRU L-6 THEFIRM LICENSE NUMBER, |
| | (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE |
| | TITLE BLOCK PER FAC 61G1-16.004(2) & FS 481.219, |
| | 481.2055. PLEASE SHOW FIRM LICENSE NUMBER IN TITLE |
| | BLOCK. |
| | |
| | 5. ALL ARCHITECTURAL SHEETS. THE SIGNATURE IS REQUIRED |
| | FOR THE ARCHITECT. IT APPEARS THAT INITIALS HAVE BEEN |
| | USED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE |
| | ARCHITECT, THEN A SIGNED, SEALED, DATED, NOTORIZED |
| | LETTER INDICATING THE LEGAL SIGNATURE OF THE ARCHITECT |
| | SHALL BE SUBMITTED FOR OUR FILES. FAC 61G1-16.003, |
| | 61G1-16.004(5) & FS 481.2055. |
| | |
| | 6. SHT A-104 DETAILS 1 THRU 4. SHOW THE 5' TURNING AREA |
| | REQUIRED IN THE TOILET ROOMS PER SECTION 11-4.22.3. |
| | |
| | 7. SHT A-104 DETAIL 4 SHOW THE CLEAR FLOOR SPACE FOR |
| | ALL REQUIRED ACCESSIBLE FIXTURES PER SECTIONS |
| | 11-4.16.2, 11-4.19.3 & 11-4.21.2.--A TURNING AREA |
| | IS REQUIRED FOR THE SHOWER ROOMS PER SECTION 11-4.2.3. |
| | PLEASE SHOW ON DETAIL.--DOORS SHALL NOT SWING INTO |
| | THE CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE. SECTION |
| | 11-4.23.2. THIS WILL INCLUDE THE SHOWERS AND THE LAVS |
| | OUTSIDE THE SHOWERS. |
| | |
| | 8. SHT A-104 DETAIL 4. SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | ___FOR W/C'S: |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | ___FOR LAVS: |
| | A. 11-4.19.2 CLEARANCES |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | ___FOR SHOWERS: |
| | A. 11-4.21.2 SIZE & CLEARANCES |
| | B. 11-4.21.3 SEAT |
| | C. 11-4.21.4 GRAB BARS |
| | D. 11-4.21.5 CONTROLS |
| | E. 11-4.21.6 SHOWER UNIT |
| | F. 11-4.21.7 CURBS |
| | |
| | 9. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING |
| | FOUNTAINS. SHOW COMPLIANCE WITH THE SECTION 11-4.15 AND |
| | ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A) |
| | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | |
| | 10. SHT A-300 SUBMIT CALCULATIONS FOR PRIMARY & |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS & TABLES. SHOW THE SQUARE FOOT AREA OF EACH |
| | ROOF DRAIN WITH 1/2 AREA OF ALL VERTICAL WALLS |
| | INCLUDING PARAPETS AS WELL AS THE SQUARE FOOTAGE OF ALL |
| | ROOFS THAT DRAIN ONTO EACH AREA FROM ABOVE ADDED IN THE |
| | CALCULATIONS. |
| | |
| | 11. SHT A-300 LOWER ROOF ON THE WEST SIDE OF THE |
| | BUILDING INDICATES R5 TYP FOR O.S. DETAIL R5 INDICATES |
| | A PARAPET WALL. SECONDARY ROOF DRAIS REQUIRED PER |
| | SECTION 1107.2. IS THE DRAIN SHOWN A SCUPPER DRAIN OR |
| | AN OVERFLOW SCUPPER DRAIN? PLEASE CLARIFY AND INDICATE |
| | SECONDARY DRAIN. SECTION 106.1.1. |
| | |
| | 12. SHT A-300 UPPER ROOF AT N.E. CORNER INDICATES R5 AS |
| | AN O.S. PLEASE CLARIFY.--LOWER ROOF DRAINS ARE |
| | INDICATED AS O.S., NOT PRIMARY SCUPPER DRAINS. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 13. SHT A-300 INDICATES R15 FOR THE SCUPPER WITH |
| | DOWNSPOUT & O.S. R15 SHOWS NO COLLECTOR HEAD OR |
| | DOWNSPOUT. ALSO SHEET A-400 SHOWS NO DOWNSPOUTS. PLEASE |
| | CLARIFY AND INDICATE THE SIZE OF THE DOWNSPOUTS AND |
| | SHOW COLLECTOR HEAD WITH DIMENSIONS. TABLES 1106.3 & |
| | 1106.7.--ALSO INDICATE HOW THE PRIMARY DRAIN & O.S. |
| | CAN BE AT THE ROOF LEVEL. SECTIONS 1503.4.2 & |
| | 1503.4.3. |
| | |
| | 14. SHT A-709 DETAILS 79 & 81. SHOW COMPLIANCE WITH |
| | SECTION 11-4.24 & ALL SUBSECTIONS. NOTE: FORWARD |
| | APPROACH REQUIRED ON CLEAR FLOOR SPACE AND CABINET |
| | DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE. |
| | |
| | 15. ALL PLUMBING, MECHANICAL, ELECTRICAL & FIRE |
| | PROTECTION SHEETS. THE ENGINEER SHALL LEGIBLY INDICATE |
| | THEIR ADDRESS. FAC 61G15-23.002(2) & FS 471.025. |
| | |
| | 16. SHT P0-1-1 IS INDICATED AS HVAC LEGEND, SCHEDULE & |
| | GENERAL NOTES IN THE SHEET TITLE. PLEASE CHANGE |
| | REFERENCE TO IDENTIFY INFORMATION ON SHEET. SECTION |
| | 106.1.1. |
| | |
| | 17. SHT P0-101 THE MAXIMUM DISTANCE OF THE FIXTURE TRAP |
| | FROM THE VENT SHALL COMPLY WITH TABLE 906.1. SOME FLOOR |
| | DRAINS APPEAR TO EXCEED THE LIMIT, BUT NO PIPE/TRAP |
| | SIZE IS INDICATED. PLEASE CHECK THE DISTANCE FROM THE |
| | VENT AND INDICATE PIPE/TRAP SIZE. TABLE 709.1. |
| | |
| | 18. SHT P1-101. SUBMIT THE MANUF. SPECIFICATION SHEETS |
| | FOR THE SN-1 FIXTURE INCLUDING INSTALLATION |
| | INSTRUCTIONS. SECTION 106.1.2. |
| | |
| | 19. SHT P1-101 SUBMIT A DETAIL FOR THE CANINE |
| | PRE-OP/POST-OP KENNELS. SHOW A DETAIL FOR THE WATER |
| | BACKFLOW PROTECTION AND CONNECTION TO THE DOG BOWLS. |
| | SECTION 608. SHOW THE CONNECTION TO THE TRENCH DRAINS |
| | AND THE SN-1 FIXTURES. SECTION 106.1.2. (SN-1 FIXTURES |
| | NOT SHOWN ON THE ISOMETRIC RISER DIAGRAM. CLARIFY). |
| | |
| | 20. SHT P1-103 SEPARATE GAS PERMIT IS REQUIRED. THE |
| | FOLLOWING REQUIREMENTS SHALL BE SUBMITTED FOR GAS |
| | REVIEW: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | E. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. (NOT SHOWN FOR GB1 |
| | UNITS). |
| | |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | G. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | H. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | 21. SHT P1-103 DETAIL (2) GB1(1300MBTH) NOT INDICATED |
| | ON THE PLUMBING EQUIPMENT SCHEDULE ON SHT P5-101. |
| | PLEASE IDENTIFY THESE FIXTURES. SECTION 106.1.2. |
| | |
| | 22. SHT P1-105 A RELIEF VENT, (GOOSE-NECK) FITTING |
| | SHALL BE INSTALLED IN THE CONDENSATE DRAIN LINE AS IT |
| | EXITS THE BUILDING. |
| | |
| | 23. SHT P2-101 WATER HAMMER ARRESTORS ARE REQUIRED ON |
| | ALL QUICK CLOSING VALVES PER SECTION 604.9. (ICE |
| | MAKERS, DISH WASHERS, WASH MACHINES ETC.). PLEASE SHOW |
| | ON THE WATER ISOMETRIC RISER DIAGRAM. WHA'S TO BE |
| | LOCATED NEAR THE FIXTURE, NOT IN THE CEILING. PDI-WH |
| | 201. |
| | |
| | 24. SHT P2-101 2" WATER SUPPLY LINE DOES NOT CONNECT TO |
| | THE WATER SUPPLY LINE IN THE CEILING ABOVE THE |
| | VESTIBLUE FOR THE MEN'S LOCKER ROOM. (ALSO SEE SHT |
| | P1-103). SECTION 106.1.1. PLEASE INDICATE WHERE THE 2" |
| | CW CONNECTS. |
| | |
| | 25. SHT P2-101 PLEASE IDENTIFY THE FIXTURE THAT |
| | CONNECTS TO THE COLD WATER SUPPLY LINE THEN INDICATES |
| | HOT WATER LINE CONNECTING TO THE 3/8TH" STAINLESS STEEL |
| | TUBING INDICATED AS A COLD WATER LINE. THIS IS ABOVE |
| | ROOM #174. PLEASE CLARIFY SECTION 106.1.2. |
| | |
| | 26. SHT P2-101 SHOW ALL PIPE SIZES. SECTIONS 106.2.1 & |
| | 604. |
| | |
| | 27. SHT P3-101 SHOW ALL PIPE SIZES AND INDICATED ON THE |
| | SANITARY ISOMETRIC RISER DIAGRAM THE DFU'S AS THEY |
| | ACCUMULATE IN THE SYSTEM. TABLES 709.1, 710.1(1) & |
| | 710.1(2). |
| | |
| | 28. SHT P3-101 INDICATE HOW THE VENT CONNECTS TO THE |
| | BRANCH LINE BEHIND THE W/C IN TOILET ROOM 183. SECTIONS |
| | 905.3 & 905.4. (ALSO SEE SHT P1-101). |
| | |
| | 29. SHT P3-101 A TRAP AND A VENT ARE REQUIRED FOR THE |
| | SINK IN ROOM 172. SECTIONS 901.2.1 & 1002.1. (ALSO SEE |
| | SHT P1-101). |
| | |
| | 30. SHT P3-101 NOT ALL KENNELS SHOW A TD1. PLEASE |
| | CLARIFY. (ALSO SEE SHT P1-101). SECTION 106.2.1. |
| | |
| | 31. SHT P3-101 TRAPS FOR TD1'S ON SANITARY RISER |
| | ISOMETRIC DIAGRAM ARE NOT LEGIBLE. PLEASE CLARIFY HOW |
| | THE TRAPS ARE TO BE CONNECTED TO THE BRANCH LINE. |
| | SECTION 106.1.1. |
| | |
| | 32. SHT P3-101 NOTE "PROVIDE FUNNEL" FOR RESIDENTIAL |
| | AREA CONDENSATE NOT APPROVED. CONDENSATE SHALL NOT |
| | DRAIN INTO THE SANITARY SYSTEM. CONDENSATE SHALL DRAIN |
| | SEPARATELY OUT OF THE BUILDING AND TERMINATE INTO THE |
| | STORM, A CATCH BASIN, DRWELLL, OR PLANTED AREA A |
| | MINIMUM 1 FOOT FROM THE STRUCTURAL WALL.MUNICIPAL |
| | CODE ARTICLE III SECTION 90-125(5). PLEASE INDICATE HOW |
| | CONDENSATE TO BE DRAINED FROM RESIDENTIAL AREA. SECTION |
| | 106.1.2. |
| | |
| | 33. SHT P3-101 THE WASH MACHINES REQUIRE A STANDPIPE, |
| | MINIMUM 18" AND A CLEANOUT, MINIMUM 4FT ABOVE THE |
| | FLOOR. SECTIONS 708.9 & 802.4. PLEASE SHOW ON THE SANT. |
| | RISER DIAGRAM. |
| | |
| | 34. SHT P3-101 CLEANOUTS REQUIRED PER SECTIONS 708.3.1 |
| | & 708.3.5. PLEASE INDICATE ON THE SANT. RISER DIAGRAM & |
| | ON THE FLOOR PLANS SHTS P1-101, P1-102 & P1-103. |
| | |
| | 35. SUBMIT STORM RISER DIAGRAMS . SHOW ALL PIPE SIZES & |
| | INDICATE SQUARE FOOTAGE AS IT ACCUMULATES IN THE |
| | SYSTEM. ALSO SHOW ALL CLEANOUTS REQUIRED BY SECTION |
| | 1101.8. (ALSO SHOW CLEANOUTS ON SHT P1-105). |
| | 106.3.5.1.3(7)(13). |
| | |
| | 36. SUBMIT A CONDENSATE RISER DIAGRAM. INDICATE ALL |
| | PIPE SIZES AND SHOW PIPES FROM A/C UNIT THRU |
| | TERMINATION. INDICATE MATERIAL FOR CONDENSATE PIPING. |
| | SECTION 106.3.5.1.3(13). |
| | |
| | 37. SHT P4-1-1 WATER HAMMER ARRESTOR DETAIL. THE |
| | LOCATION OF THE WATER HAMMER ARRESTORS SHALL BE NEAR |
| | THE FIXTURE, IN AN "EFFECTIVE RANGE" NOT IN THE CEILING |
| | AS SHOWN. PDI-WH 201 AND MANUF. INSTALLATION |
| | INSTRUCTIONS. |
| | |
| | 38. SHT P4-101 PACKAGED WATER HEATER-STORAGE |
| | RECIRCULATION SYSTEM GWH-1. THE COLD WATER SUPPLY TURNS |
| | INTO HOT WATER SUPPLY AFTER THE DROP. PLEASE CLARIFY. |
| | --THE COLD WATER SUPPLY IS SHOWN TO THE STORAGE TANK. |
| | PLEASE EXPLAIN.--HOT & COLD INLETS TO THE STORAGE |
| | TANK? CLARIFY. SECTION 106.1.1.--A VACUUM RELIEF |
| | VALVE IS REQUIRED FOR ALL BOTTOM FED WATER HEATERS. |
| | SECTION 504.2.--THE FLOOR DRAIN IS NOT AN APPROVED |
| | INDIRECT WASTE RECEPTOR. A FLOOR SINK OR A HUB DRAIN IS |
| | REQUIRED. SECTIONS 802.3 & 802.3.2. |
| | |
| | 39. SHT P4-101 GAS WATER HEATER FLUE DETAIL SHOWS 2 |
| | VENTS. IS THE CAT 1, CLASS B VENT TO THE WALL A DIRECT |
| | VENT? PLEASE CLARIFY. (IF DIRECT VENT, CLASS B NOT |
| | REQUIRED). SECTION 106.1.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. RESUBMIT |
| | MARKED UP PLUMBING SHEETS TO ALLSO HELP EXPEDITE PLAN |
| | REVIEW. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |