2007-07-25 17:59:10--------------DENIED---------------
  
 FBC 2004 CODE FAMILY WITH 2005 AND 2006 REVISIONS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: LOCATIONS ON PLANS RELATED TO THE FOLLOWING
 COMMENTS WERE MARKED ON ONE SET OF PLANS, WHEN
 PRACTICAL, TO HELP CLARIFY THE NATURE AND LOCATION OF
 THE COMMENTS.
  
 1. M0-101: GENERAL NOTE 1(M) REFERENCES ASHRAE 62-01.
 AS OF DECEMBER 8,2006 THE CORRECT STANDARD IS ASHRAE
 62.1-2004. FBC,M CH.15. PLEASE CORRECT.
  
 2. M0-101: GENERAL NOTE 7 IS IN CONFLICT WITH
 CONDENSATE DRAIN TRAP DETAIL ON M4-101. IS TRAP TO BE
 AT STATIC +1" OR STATIC +2"? CONDENSATE DRAINS SHALL BE
 TRAPPED AS REQUIRED BY THE EQUIPMENT OR APPLIANCE
 MANUFACTURER. FBC,M 307.2.4
  
 3. M0-101: HVAC LEGEND SHOWS AN "OPTION" FOR FIRE
 DAMPERS. FIRE DAMPER EXCEPTIONS HAVE CHANGED AND THE "5
 FOOT RULE" NO LONGER APPLIES. SEE FBC,M 607.5 FOR
 REQUIREMENTS. THE UPDATED EXCEPTIONS DO NOT APPLY TO
 2-HOUR ASSEMBLIES AS ARE INDICATED ON LIFE SAFETY PLAN.
 ALSO, PLANS SHALL CLEARLY INDICATE WHERE FIRE DAMPERS
 ARE TO BE INSTALLED PER FBC,M 607.8. PLEASE REMOVE
 "OPTIONAL" NOTES FROM PLANS AND INSTEAD SHOW ON PLANS
 WHERE FIRE DAMPERS ARE REQUIRED AND TO BE INSTALLED.
 ALSO SEE FBC 106.1.1.
  
 4. M0-102: ASHRAE 62-2001 IS NOT CORRECT. SEE COMMENT
 #1.
  
 5. M0-102: AH1-AH4 AND AH7, PLEASE PROVIDE MISSING
 INFORMATION ON SCHEDULES REGARDING ACTUAL REQUIRED
 QUANTITIES (CFM/PERSON OR CFM/SQ FT WITH TOTAL FOR EACH
 SPACE) OF OUTDOOR AIR, EVEN IF THE SYSTEM IS DESIGNED
 TO SUPPLY FAR IN EXCESS OF THE MINIMUM REQUIREMENT. THE
 SCHEDULES, AS SHOWN, DO OT CONTAIN ACCURATE
 INFORMATION. EXAMPLE: AH7 IN LOBBY 301, SCHEDULE
 INDICATES 8070 CFM OUTDOOR AIR IS REQUIRED.
 NOTE: 13-409.1.ABC.1.1 VENTILATION SYSTEMS SHALL BE
 DESIGNED TO BE CAPABLE OF REDUCING THE SUPPLY OF
 OUTDOOR AIR TO THE MINIMUM VENTILATION RATES REQUIRED
 BY SECTION 6.1.3 OF ASHRAE 62. SYSTEMS MAY BE DESIGNED
 TO SUPPLY OUTSIDE AIR QUANTITIES EXCEEDING MINIMUM
 LEVELS, BUT THEY SHALL BE CAPABLE OF OPERATING AT NO
 MORE THAN MINIMUM LEVELS THROUGH THE USE OF RETURN
 DUCTS, MANUALLY OR AUTOMATICALLY OPERATED CONTROL
 DAMPERS, FAN VOLUME CONTROLS, OR OTHER DEVICES.
  
 6. PROVIDE ENERGY CALCULATIONS AND ALL REQUIRED
 ACCOMPANYING DOCUMENTATION. FBC 106.3.5, FBC
 13-400.0.ABC, FBC 13-400.3.ABC.2
  
 7. PROVIDE ALL REQUIRED SUBMITTALS FOR LISTED AND
 LABELED EQUIPMENT AND MATERIALS SUCH AS AHUS, CHILLERS,
 VAVS, FANS, PUMPS, ERVS, VALVES, FITTINGS, HEAT COILS.
 PRODUCT APPROVAL IS REQUIRED FOR LOUVERS PER FAC RULE
 9B-72.
  
 8. M1-101: DUCT SIZES ARE MISSING ON TWO EXHAUST DROPS
 ON ERU 81. PLEASE CORRECT.
  
 9. M1-101: ARE ERU81 AND ERU82 BOTH FEEDING AH7 THROUGH
 THE SAME DUCT? IT APPEARS THAT THE OA RISER DUCT FOR
 ERU82 IS INCORRECTLY MARKED AS THE RETURN/EXHAUST GRILL
 IN THE CEILING ABOVE THE RECEPTION DESK.
  
 10. M1-101: ERU81 AND 82 ARE BOTH FEEDING AH7.
 ACCORDING TO CONTROL SEQUENCE DIAGRAM ON M5-101, AH AND
 ERU DESIGNATION NUMBERS SHOULD CORRELATE. IT IS UNCLEAR
 WHETHER AH7 AND AH* OR ERU81 AND ERU 82 ARE MISLABELED.
 CONTROL DIAGRAM IDENTIFIES AH8 AS A 100% OA UNIT IN ONE
 PLACE BUT INDICATES AH7 AS THE SAME IN ANOTHER. PLEASE
 COORDINATE ALL THESE ISSUES SO PLANS, SCHEDULES AND
 CONTROL DIAGRAMS CORRELATE.
  
 11. M1-102: ON FLOOR PLANS, AH6 IS IN A MECHANICAL ROOM
 ON FIRST FLOOR AND AH8 IS IN A STORAGE ROOM. HOWEVER,
 ON EQUIPMENT SCHEDULE, BOTH ARE SHOWN TO BE ON THE
 MEZANNINE LEVEL. PLEASE COORDINATE FLOOR PLANS AND
 SCHEDULES.
  
 12. M1-102: AH6 SUPPLY DUCT, LOCATION OF TRANSITION
 BETWEEN 34X18 AND 34X16 DUCT IS NOT SHOWN. PLEASE
 CLARIFY.
  
 13. SMOKE DETECTORS ARE REQUIRED ON ALL SUPPLY, OUTSIDE
 AIR AND EXHAUST DUCTS RELATED TO AH1, AH2, AH3, AH4 AND
 AH7 PER FBC,M 607.2.2. ALSO ON SUPPPLY SIDE OF AH5, AH6
 AND BC-1 PER FBC,M 606.2.1. SOME ARE SHOWN ON PLANS AND
 OTHERS ARE NOT. PLEASE SHOW LOCATION OF ALL DUCT SMOKE
 DETECTORS. FBC 106.1.1
  
 14. PROVIDE VENTILATION INFORMATION FOR AREA BEING
 SERVED BY BC-1 (DWELLING UNIT?) FBC 401.2.
  
 15. SSHOW MEANS AND LOCATION OF DRYER EXHAUST PER FBC,M
 504.4. ALSO, VERIFY IF MAKE-UP AIR IS REQUIRED PER
 FBC,M 504.5.
  
 16. M1-102: EF 71 AND EF 73 SHALL BE INTERLOCKED WITH
 BC-1 PER FBC,M 403.2.1(3) AND WITH BATHROOM LIGHTS PER
 FBC,M 401.3.
  
 17. PLEASE SHOW MEANS AND LOCATION OF ALL CONDENSATE
 DISPOSAL, INCLUDING THE LOCATION OF DRYWELLS. FBC
 307.2.1
  
 18. "SALLY PORT" AREA SHALL BE VENTILATED PER FBC,M
 TABLE 403.3 AND SEC 404.
  
 19. NO INFORMATION COULD BE FOUND ON PLANS FOR VENTING
 OR COMBUSTION AIR FOR GAS APPLIANCES IN THE MECHANICAL
 ROOM ASIDE FROM GENERIC DETAIL FOR A WATER HEATER. IS
 THE MECHANICAL ROOM A CONFINED SPACE? IF SO, PROVIDE
 COMBUSTION AIR FOR A TOTAL OF 335,000 BTU/H PER FBC,FG
 304.5 AND SHOW SPECIFIC MEANS AND LOCATION OF VENTING
 PER FBC,FG 503.2.
  
 20. M4-101: ROOF EQUIPMENT SUPPORT DETAIL, PROVIDE
 COMPLETE DETAIL FOR FASTENING OF CURBS AND SUPPORTS TO
 STRUCTURE AS WELL AS ATTACHMENTS OF EQUIPMENT TO CURBS
 AND SUPPORTS. PROVIDE WIND LOAD CALCULATIONS FOR
 BUILDING PLAN REVIEW SHOWING THAT ALL ATTACHMENTS ARE
 DESIGNED TO THE 140 MPH WIND ZONE PER FBC,M 301.13 AND
 FBC CH.16.
  
 21.M4-101: IF PATE CURBS ARE USED AS SUPPORTS, AND
 ROOFING MATERIAL EXTENDS UNDER THE EQUIPMENT (INCLUDING
 DUCTWORK), CLEARANCES ABOVE FINISHED ROOF SHALL BE IN
 ACCORDANCE WITH FBC TABLE 1509.7, NOT NECESSARILY 14"
 AS SHOWN ON DETAIL.
  
 22. M4-101: FIRE DAMPERS SHALL BE INSTALLED IN
 ACCORDANCE WITH THEIR LISTING AND MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. FBC 607.2
  
 23. M4-102: PIPE PENETRATIONS OF RATED FLOOR/CEILING
 ASSEMBLIES SHALL COMPLY WITH FBC 712.4. PIPE
 PENETRATIONS OF RATED WALLS SHALL COMPLY WITH 712.3.
 PROVIDE UL ASSEMBLY DETAILS AS REQUIRED.
  
 24. BOTH OUTDOOR AIR SUPPLY AND EXHAUST SYSTEMS SHALL
 BE EQUIPPED WITH MOTORIZED DAMPERS THAT WILL
 AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES SERVED
 ARE NOT IN USE. VENTILATION OUTSIDE AIR DAMPERS SHALL
 BE CAPABLE OF AUTOMATICALLY SHUTTING OFF DURING
 PREOCCUPANCY BUILDING WARMUP, COOLDOWN, AND SETBACK,
 EXCEPT WHEN VENTILATION REDUCES ENERGY COSTS (E.G.,
 NIGHT PURGE) OR WHEN VENTILATION MUST BE SUPPLIED TO
 MEET CODE REQUIREMENTS. FBC 13-409.1.ABC.3.3
  
 25. NO INFORMATION WAS PROVIDED REGARDING EMERGENCY
 GENERATOR AS SHOWN ON E-301. PLEASE PROVIDE PLANS,
 SPECIFICATIONS, LOCATION ON SITE PLAN FOR GENERATOR AND
 FUEL TANK. SHOW DISTANCE FROM PROPERTY LINES, ADJACENT
 BUILDINGS AND ANY OPENINGS INTO BUILDINGS WITHIN 10' OF
 GENERATOR EXHAUST. ALL ABOVE GROUND FUEL TANKS OF 550
 GALLONS OR MORE REQUIRE PALM BEACH COUNTY DERM APPROVAL
 PRIOR TO PERMITTING BY THE CITY OF WEST PALM BEACH. FOR
 MORE INFORMATION CONTACT DERM DIRECTLY AT 561-233-2400
 OR VISIT WWW.PBCGOV.COM/ERM.
  
 NOTE: ADDITIONAL COMMENTS MAY BE GENERATED BASED ON THE
 NATURE AND COMPLETENESS OF INFORMATION WHICH IS TO BE
 PROVIDED IN RESPONSE TO THIS REVIEW.
  