| 2007-07-25 17:59:10 | --------------DENIED--------------- |
| | |
| | FBC 2004 CODE FAMILY WITH 2005 AND 2006 REVISIONS FBC |
| | CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | NOTE: LOCATIONS ON PLANS RELATED TO THE FOLLOWING |
| | COMMENTS WERE MARKED ON ONE SET OF PLANS, WHEN |
| | PRACTICAL, TO HELP CLARIFY THE NATURE AND LOCATION OF |
| | THE COMMENTS. |
| | |
| | 1. M0-101: GENERAL NOTE 1(M) REFERENCES ASHRAE 62-01. |
| | AS OF DECEMBER 8,2006 THE CORRECT STANDARD IS ASHRAE |
| | 62.1-2004. FBC,M CH.15. PLEASE CORRECT. |
| | |
| | 2. M0-101: GENERAL NOTE 7 IS IN CONFLICT WITH |
| | CONDENSATE DRAIN TRAP DETAIL ON M4-101. IS TRAP TO BE |
| | AT STATIC +1" OR STATIC +2"? CONDENSATE DRAINS SHALL BE |
| | TRAPPED AS REQUIRED BY THE EQUIPMENT OR APPLIANCE |
| | MANUFACTURER. FBC,M 307.2.4 |
| | |
| | 3. M0-101: HVAC LEGEND SHOWS AN "OPTION" FOR FIRE |
| | DAMPERS. FIRE DAMPER EXCEPTIONS HAVE CHANGED AND THE "5 |
| | FOOT RULE" NO LONGER APPLIES. SEE FBC,M 607.5 FOR |
| | REQUIREMENTS. THE UPDATED EXCEPTIONS DO NOT APPLY TO |
| | 2-HOUR ASSEMBLIES AS ARE INDICATED ON LIFE SAFETY PLAN. |
| | ALSO, PLANS SHALL CLEARLY INDICATE WHERE FIRE DAMPERS |
| | ARE TO BE INSTALLED PER FBC,M 607.8. PLEASE REMOVE |
| | "OPTIONAL" NOTES FROM PLANS AND INSTEAD SHOW ON PLANS |
| | WHERE FIRE DAMPERS ARE REQUIRED AND TO BE INSTALLED. |
| | ALSO SEE FBC 106.1.1. |
| | |
| | 4. M0-102: ASHRAE 62-2001 IS NOT CORRECT. SEE COMMENT |
| | #1. |
| | |
| | 5. M0-102: AH1-AH4 AND AH7, PLEASE PROVIDE MISSING |
| | INFORMATION ON SCHEDULES REGARDING ACTUAL REQUIRED |
| | QUANTITIES (CFM/PERSON OR CFM/SQ FT WITH TOTAL FOR EACH |
| | SPACE) OF OUTDOOR AIR, EVEN IF THE SYSTEM IS DESIGNED |
| | TO SUPPLY FAR IN EXCESS OF THE MINIMUM REQUIREMENT. THE |
| | SCHEDULES, AS SHOWN, DO OT CONTAIN ACCURATE |
| | INFORMATION. EXAMPLE: AH7 IN LOBBY 301, SCHEDULE |
| | INDICATES 8070 CFM OUTDOOR AIR IS REQUIRED. |
| | NOTE: 13-409.1.ABC.1.1 VENTILATION SYSTEMS SHALL BE |
| | DESIGNED TO BE CAPABLE OF REDUCING THE SUPPLY OF |
| | OUTDOOR AIR TO THE MINIMUM VENTILATION RATES REQUIRED |
| | BY SECTION 6.1.3 OF ASHRAE 62. SYSTEMS MAY BE DESIGNED |
| | TO SUPPLY OUTSIDE AIR QUANTITIES EXCEEDING MINIMUM |
| | LEVELS, BUT THEY SHALL BE CAPABLE OF OPERATING AT NO |
| | MORE THAN MINIMUM LEVELS THROUGH THE USE OF RETURN |
| | DUCTS, MANUALLY OR AUTOMATICALLY OPERATED CONTROL |
| | DAMPERS, FAN VOLUME CONTROLS, OR OTHER DEVICES. |
| | |
| | 6. PROVIDE ENERGY CALCULATIONS AND ALL REQUIRED |
| | ACCOMPANYING DOCUMENTATION. FBC 106.3.5, FBC |
| | 13-400.0.ABC, FBC 13-400.3.ABC.2 |
| | |
| | 7. PROVIDE ALL REQUIRED SUBMITTALS FOR LISTED AND |
| | LABELED EQUIPMENT AND MATERIALS SUCH AS AHUS, CHILLERS, |
| | VAVS, FANS, PUMPS, ERVS, VALVES, FITTINGS, HEAT COILS. |
| | PRODUCT APPROVAL IS REQUIRED FOR LOUVERS PER FAC RULE |
| | 9B-72. |
| | |
| | 8. M1-101: DUCT SIZES ARE MISSING ON TWO EXHAUST DROPS |
| | ON ERU 81. PLEASE CORRECT. |
| | |
| | 9. M1-101: ARE ERU81 AND ERU82 BOTH FEEDING AH7 THROUGH |
| | THE SAME DUCT? IT APPEARS THAT THE OA RISER DUCT FOR |
| | ERU82 IS INCORRECTLY MARKED AS THE RETURN/EXHAUST GRILL |
| | IN THE CEILING ABOVE THE RECEPTION DESK. |
| | |
| | 10. M1-101: ERU81 AND 82 ARE BOTH FEEDING AH7. |
| | ACCORDING TO CONTROL SEQUENCE DIAGRAM ON M5-101, AH AND |
| | ERU DESIGNATION NUMBERS SHOULD CORRELATE. IT IS UNCLEAR |
| | WHETHER AH7 AND AH* OR ERU81 AND ERU 82 ARE MISLABELED. |
| | CONTROL DIAGRAM IDENTIFIES AH8 AS A 100% OA UNIT IN ONE |
| | PLACE BUT INDICATES AH7 AS THE SAME IN ANOTHER. PLEASE |
| | COORDINATE ALL THESE ISSUES SO PLANS, SCHEDULES AND |
| | CONTROL DIAGRAMS CORRELATE. |
| | |
| | 11. M1-102: ON FLOOR PLANS, AH6 IS IN A MECHANICAL ROOM |
| | ON FIRST FLOOR AND AH8 IS IN A STORAGE ROOM. HOWEVER, |
| | ON EQUIPMENT SCHEDULE, BOTH ARE SHOWN TO BE ON THE |
| | MEZANNINE LEVEL. PLEASE COORDINATE FLOOR PLANS AND |
| | SCHEDULES. |
| | |
| | 12. M1-102: AH6 SUPPLY DUCT, LOCATION OF TRANSITION |
| | BETWEEN 34X18 AND 34X16 DUCT IS NOT SHOWN. PLEASE |
| | CLARIFY. |
| | |
| | 13. SMOKE DETECTORS ARE REQUIRED ON ALL SUPPLY, OUTSIDE |
| | AIR AND EXHAUST DUCTS RELATED TO AH1, AH2, AH3, AH4 AND |
| | AH7 PER FBC,M 607.2.2. ALSO ON SUPPPLY SIDE OF AH5, AH6 |
| | AND BC-1 PER FBC,M 606.2.1. SOME ARE SHOWN ON PLANS AND |
| | OTHERS ARE NOT. PLEASE SHOW LOCATION OF ALL DUCT SMOKE |
| | DETECTORS. FBC 106.1.1 |
| | |
| | 14. PROVIDE VENTILATION INFORMATION FOR AREA BEING |
| | SERVED BY BC-1 (DWELLING UNIT?) FBC 401.2. |
| | |
| | 15. SSHOW MEANS AND LOCATION OF DRYER EXHAUST PER FBC,M |
| | 504.4. ALSO, VERIFY IF MAKE-UP AIR IS REQUIRED PER |
| | FBC,M 504.5. |
| | |
| | 16. M1-102: EF 71 AND EF 73 SHALL BE INTERLOCKED WITH |
| | BC-1 PER FBC,M 403.2.1(3) AND WITH BATHROOM LIGHTS PER |
| | FBC,M 401.3. |
| | |
| | 17. PLEASE SHOW MEANS AND LOCATION OF ALL CONDENSATE |
| | DISPOSAL, INCLUDING THE LOCATION OF DRYWELLS. FBC |
| | 307.2.1 |
| | |
| | 18. "SALLY PORT" AREA SHALL BE VENTILATED PER FBC,M |
| | TABLE 403.3 AND SEC 404. |
| | |
| | 19. NO INFORMATION COULD BE FOUND ON PLANS FOR VENTING |
| | OR COMBUSTION AIR FOR GAS APPLIANCES IN THE MECHANICAL |
| | ROOM ASIDE FROM GENERIC DETAIL FOR A WATER HEATER. IS |
| | THE MECHANICAL ROOM A CONFINED SPACE? IF SO, PROVIDE |
| | COMBUSTION AIR FOR A TOTAL OF 335,000 BTU/H PER FBC,FG |
| | 304.5 AND SHOW SPECIFIC MEANS AND LOCATION OF VENTING |
| | PER FBC,FG 503.2. |
| | |
| | 20. M4-101: ROOF EQUIPMENT SUPPORT DETAIL, PROVIDE |
| | COMPLETE DETAIL FOR FASTENING OF CURBS AND SUPPORTS TO |
| | STRUCTURE AS WELL AS ATTACHMENTS OF EQUIPMENT TO CURBS |
| | AND SUPPORTS. PROVIDE WIND LOAD CALCULATIONS FOR |
| | BUILDING PLAN REVIEW SHOWING THAT ALL ATTACHMENTS ARE |
| | DESIGNED TO THE 140 MPH WIND ZONE PER FBC,M 301.13 AND |
| | FBC CH.16. |
| | |
| | 21.M4-101: IF PATE CURBS ARE USED AS SUPPORTS, AND |
| | ROOFING MATERIAL EXTENDS UNDER THE EQUIPMENT (INCLUDING |
| | DUCTWORK), CLEARANCES ABOVE FINISHED ROOF SHALL BE IN |
| | ACCORDANCE WITH FBC TABLE 1509.7, NOT NECESSARILY 14" |
| | AS SHOWN ON DETAIL. |
| | |
| | 22. M4-101: FIRE DAMPERS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THEIR LISTING AND MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. FBC 607.2 |
| | |
| | 23. M4-102: PIPE PENETRATIONS OF RATED FLOOR/CEILING |
| | ASSEMBLIES SHALL COMPLY WITH FBC 712.4. PIPE |
| | PENETRATIONS OF RATED WALLS SHALL COMPLY WITH 712.3. |
| | PROVIDE UL ASSEMBLY DETAILS AS REQUIRED. |
| | |
| | 24. BOTH OUTDOOR AIR SUPPLY AND EXHAUST SYSTEMS SHALL |
| | BE EQUIPPED WITH MOTORIZED DAMPERS THAT WILL |
| | AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES SERVED |
| | ARE NOT IN USE. VENTILATION OUTSIDE AIR DAMPERS SHALL |
| | BE CAPABLE OF AUTOMATICALLY SHUTTING OFF DURING |
| | PREOCCUPANCY BUILDING WARMUP, COOLDOWN, AND SETBACK, |
| | EXCEPT WHEN VENTILATION REDUCES ENERGY COSTS (E.G., |
| | NIGHT PURGE) OR WHEN VENTILATION MUST BE SUPPLIED TO |
| | MEET CODE REQUIREMENTS. FBC 13-409.1.ABC.3.3 |
| | |
| | 25. NO INFORMATION WAS PROVIDED REGARDING EMERGENCY |
| | GENERATOR AS SHOWN ON E-301. PLEASE PROVIDE PLANS, |
| | SPECIFICATIONS, LOCATION ON SITE PLAN FOR GENERATOR AND |
| | FUEL TANK. SHOW DISTANCE FROM PROPERTY LINES, ADJACENT |
| | BUILDINGS AND ANY OPENINGS INTO BUILDINGS WITHIN 10' OF |
| | GENERATOR EXHAUST. ALL ABOVE GROUND FUEL TANKS OF 550 |
| | GALLONS OR MORE REQUIRE PALM BEACH COUNTY DERM APPROVAL |
| | PRIOR TO PERMITTING BY THE CITY OF WEST PALM BEACH. FOR |
| | MORE INFORMATION CONTACT DERM DIRECTLY AT 561-233-2400 |
| | OR VISIT WWW.PBCGOV.COM/ERM. |
| | |
| | NOTE: ADDITIONAL COMMENTS MAY BE GENERATED BASED ON THE |
| | NATURE AND COMPLETENESS OF INFORMATION WHICH IS TO BE |
| | PROVIDED IN RESPONSE TO THIS REVIEW. |
| | |