| Date |
Text |
| 2007-09-04 23:47:02 | *****DENIED***** |
| | |
| | 01.ON SHEET G-001 UNDER APPLICABLE CODES, INCLUDE AS |
| | LIFE SAFETY CODE:NFPA 101 2003 EDITION. |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 03.NFPA 13, STANDARD FOR THE INSTALLATION OF |
| | SPRINKLER SYSTEMS, 2002 EDITION SHALL BE REFERENCED. |
| | SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE FIRE |
| | SPRINKLER SYSTEM INSTALLATION. |
| | |
| | 04.NFPA72, NATIONAL FIRE ALARM CODE, 2002 EDITION |
| | SHALL BE REFERENCED.SEPARATE PLANS AND PERMIT WILL BE |
| | REQUIRED FOR THE FIRE ALARM SYSTEM INSTALLATION. |
| | |
| | 05.FIRE ALARM SYSTEM TO BE CLASS A OR FULLY |
| | ADDRESSIBLE. |
| | |
| | 06.FIRE ALARM SYSTEM SHALL BE UL CERTIFIED FOR |
| | CENTRAL STATION SERVICE. |
| | |
| | 07.A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING. SHOW |
| | THE LOCATION OF THE KNOX BOX IN AN ACCESSIBLE LOCATION |
| | ON THE APPROPIATE EXTERIOR ELEVATION..FOR |
| | APPLICATIONS, CONTACT WPB FIRE PREVENTION BUREAU AT |
| | 561-804-4724. |
| | |
| | 08.FIRE DOORS AND FIRE WINDOWS TO COMPLY WITH NFPA |
| | 80. |
| | |
| | 09.SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| | MATERIALS FOR THE EXITS, EXIT CORRIDORS, AND OTHER |
| | AREAS IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | 10.SPECIFY THE INTERIOR FLOOR FINISHES IN TERMS OF |
| | CLASS I OR CLASS II. |
| | |
| | 11.ON THE APPROPIATE EXTERIOR ELEVATION, POST THE |
| | NUMERICAL ADDRESS ON THE BUILDING VISIBLE FROM NORTH |
| | MILITARY TRAIL.IT IS RECOMMENDED THAT THE FARTHER THE |
| | BUILDING IS FROM THE ROADSIDE, THAT ADDRESS NUMBERS BE |
| | LARGER THAN THE DIMENSION OF NO LESS THAN 6" IN HEIGHT |
| | AND NO LESS THAN 1" IN WIDTH (AS REQUIRED BY WEST PALM |
| | BEACH CODE) .IF A MONUMENT SIGN IS TO BE USED, |
| | ADDRESS NUMBERS SHALL BE POSTED. |
| | |
| | 12.ON SHEET A-400, INDICATE FRONT AND REAR |
| | ELEVATIONS. |
| | |
| | 13.UNABLE TO LOCATE ON SHEET A-500, THE OVERHEAD |
| | GARAGE DOOR(S) SHOWN ON SHEET A-400'S EAST EXTERIOR |
| | ELEVATION. |
| | |
| | 14.AS PER LOCAL REQUIREMENTS, DUCT SMOKE DETECTORS |
| | SHALL INITIATE A GENERAL FIRE ALARM. |
| | |
| | 15.IN ADDITION TO THE ELECTRONIC SWITCHES FOR THE |
| | DOUBLE CHECK DETECTOR ASSEMBLY (DCDA), CHAIN AND LOCK |
| | WILL BE REQUIRED. |
| | |
| | 16.FLOW TEST DATA (03/28/07) WAS GATHERED BY PALM |
| | BEACH COUNTY FIRE DEPARTMENT.IF THIS PROJECT IS TRULY |
| | IN THE JURISDICTION OF THE CITY OF WEST PALM BEACH, WHY |
| | WASN'T THE DATA SUPPLIED BY WEST PALM BEACH FIRE |
| | RESCUE'S PREVENTION DIVISION. |
| | |
| | 17.KNOX LOCKING CAPS WILL BE REQUIRED ON THE FIRE |
| | DEPARTMENT CONNECTIONS (FDC).CONTACT 561-804-4724 FOR |
| | APPLICATIONS. |
| | |
| | 18.PLEASE EXPLAIN THE USAGE OF THE GENERATOR, THE |
| | TYPE OF FUEL(S) THAT WILL BE UTILIZED, AND THE STORAGE |
| | OF SUCH FUEL(S) & QUANTITIES STORED.SEPARATE PLANS |
| | AND PERMIT WILL BE REQUIRED FOR ITS INSTALLATION. |
| | |
| | 19.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY |
| | POWER SHALL BE INSTALLED IN ACCORDANCE WITH NFPA110. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS |
| | ADDRESSED. |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |