| | *** UNSAT *** |
| | |
| | |
| | NEW GRACE PAVILION |
| | PEGGY ADAMS ANIMAL RESCUE LEAGUE. |
| | |
| | ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT YET |
| | SUBMITTED FOR REVIEW, WHEN PLANS AND DOCUMENTS ARE |
| | SUBMITTED FOR REVIEW ON THE NEXT RE-SUB THEY WILL BE |
| | THE FIRST TIME IN FOR REVIEW. THERE MAY BE NEW COMMENTS |
| | ONCE ADDITIONAL INFORMATION IS SUBMITTED. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE |
| | CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING |
| | ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED |
| | FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006 |
| | THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC. |
| | PLEASE SEE SOME OF THE CORRECT CODES ARE REFLECTED ON |
| | PLANS BUT NOT ALL. PLEASE SEE SOME PREVIOUS CODES NO |
| | LONGER IN EFFECT ARE STATED. PLEASE SEE SOME CODE |
| | SECTIONS WHICH ARE STATED ON PLANS ARE NOT FROM THE |
| | CURRENT NEC. |
| | PLEASE LIST THE FOLLOWING: |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | 2002 NFPA-110 |
| | |
| | 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS |
| | FOR THE CIVIL ENGINEERING FIRM PER FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES |
| | 471.023. |
| | PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION |
| | NUMBER. |
| | ** THIS IS REQUIRED FOR ALL *C* SHEETS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE MISSING TITLE BLOCK INFORMATION FOR |
| | LANDSCAPE ARCHITECTURAL FIRM AS REQUIRED PER FAC |
| | 61G1-16.004 AND FS 481.219. |
| | PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER |
| | ALSO KNOWN AS THE FIRM LICENSE NUMBER. |
| | ** PLEASE SEE THIS IS REQUIRED FOR ALL SHEETS WHETHER |
| | OR NOT COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 4) NOTE: PLEASE SEE THE ELECTRICAL SHEETS ARE MISSING |
| | TITLE BLOCKS FOR THE MEP FIRM AS SHOWN ON OTHER |
| | SHEETS. |
| | |
| | PLEASE COMPLETE THESE SHEETS WITH THE INFORMATION AS |
| | REQUIRED PER FAC 61G15-23.002. |
| | |
| | 5) NOTE: PLEASE SEE THE RAISED SEAL FROM THE ENGINEER |
| | ON THE ELECTRICAL AND FP SHEETS ARE EXTREMELY FAINT. |
| | THE INFORMATION ON SAID SEALS ARE NOT VISIBLE OR EASILY |
| | READ. PLEASE SEE FAC 61G15-23.001 WHICH REQUIRES ALL |
| | INFORMATION TO BE CLEAR AND VISIBLE. |
| | ** PLEASE SEE THIS IS REQUIRED OF ALL TRADES AND FOR |
| | ALL SHEETS, ALTHOUGH IT IS MAINLY ON THE E AND FP |
| | SHEETS. |
| | |
| | 6) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS FOR |
| | REVIEW. PLEASE SEE FBC CHAPTER 13, 13-415.1.AB.1.1, |
| | 13-415.1.C, AND PERFORMANCE CALCULATIONS PER 13-415.2. |
| | AS NO INFORMATION WAS SUBMITTED, NO REVIEW OF THESE |
| | COULD BE DONE. |
| | PLEASE BE SURE TO SEE 13-103.1.1.1 FOR SIGNED, DATED |
| | AND SEALED SHEETS. |
| | ** PLEASE CHECK WITH FLA-COM FOR LATEST VERSION AS |
| | EFFECTIVE DATE OF DECEMBER 8TH, 2006 WHEN THE LATEST |
| | CODE CHANGE WENT INTO EFFECT. |
| | |
| | 7) NOTE: PLEASE INDICATE THE WORST CASE SCENARIOS FOR |
| | VOLTAGE DROP OF CIRCUITS FOR FEEDERS AND BRANCH |
| | CIRCUIT(S). 13-413.1.ABC.1 |
| | |
| | 8) NOTE: PLEASE SEE THERE ARE AREAS WHICH DO NOT SHOW |
| | ANY AUTOMATED DEVICES FOR LIGHTING CONTROLS OR SHUT |
| | OFFS. PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 OF THE |
| | 2004 FBC W/2006 REVISIONS. |
| | PLEASE BE SURE ALL MAXIMUM TIMES ON DEVICES ARE NOTED |
| | AND SHOWN. |
| | PLEASE SEE AS THERE ARE AREAS WHICH DO NOT SHOW CONTROL |
| | AT THIS TIME INCLUDING UPPER LEVELS, SOME ITEMS CAN NOT |
| | BE REVIEWED AT THIS TIME. |
| | |
| | 9) NOTE: PLEASE KNOW ALL LOW VOLTAGE SYSTEMS WILL BE |
| | REQUIRED TO BE UNDER SEPARATE PERMITS. THESE SUBMITTED |
| | PLANS MAY BE USED TO REFERENCE HOWEVER SEPARATE PERMIT |
| | APPLICATIONS, AND FEES WILL BE DUE FOR THAT SCOPE OF |
| | WORK SUCH AS LV CATV< PHONE, DATA, ETC. IF THESE ARE |
| | ALL DONE BY THE SAME CONTRACTOR, ALL CAN BE ON ONE |
| | PERMIT. |
| | PLEASE KNOW THAT LOW VOLTAGE PERMITS FOR FIRE ALARM |
| | SYSTEMS ARE SEPARATE AND REQUIRE PLANS ALONG WITH |
| | PERMIT APPLICATION. |
| | ** NO CHANGES NEED TO BE MADE TO PLANS; THIS IS BEING |
| | NOTED FOR INFORMATIONAL PURPOSE ONLY. |
| | |
| | 10) NOTE: PLEASE SEE THE MAIN ELECTRICAL ROOM SHOWS THE |
| | MDF WHICH IS PART OF THE IT EQUIPMENT. PLEASE SEE THIS |
| | ROOM IS A HIGH VOLTAGE ELECTRICAL ROOM AND ACCESS TO |
| | THIS ROOM SHOULD BE LIMITED TO *QUALIFIED PERSONNEL* AS |
| | STATED IN THE NEC. PLEASE SEE THAT MANY TIME THIS |
| | EQUIPMENT ON THE MDF REQUIRES ACCESS TO OTHER THAN |
| | *QUALIFIED PERSONNEL*. PLEASE SEE THAT CONSIDERATION TO |
| | THE LOCATION OF THIS EQUIPMENT SHOULD BE TAKEN AND |
| | RELOCATED OR SEPARATE FROM THE MAIN ELECTRICAL ROOM AND |
| | EQUIPMENT. |
| | 110.26, 110.27, 110.16, 110.18 |
| | |
| | 11) NOTE: PLEASE SUBMIT WIND LOAD CALCULATIONS FOR THE |
| | SITE LIGHTING POLES. PLEASE KNOW THESE ARE ALREADY |
| | STATED ON SITE PLANS MEETING THE FBC FOR WIND |
| | REQUIREMENTS HOWEVER THE CALCULATIONS ARE STILL NEEDED |
| | FOR REVIEW. THESE ARE REQUIRED TO CONTAIN THE TITLE |
| | BLOCKS FROM THE DESIGN PROFESSIONAL AND TO BE SIGNED, |
| | DATED AND SEALED. |
| | FBC 106.1.2 |
| | |
| | 12) NOTE: PLEASE CLARIFY LIGHTING FIXTURES ON PLANS. |
| | THE FIXTURE SCHEDULE DOES NOT INDICATE ANY BATTERY BACK |
| | UP LIGHT FIXTURES EVEN THOUGH MANY OF THE FIXTURES ARE |
| | HALF SHADED WHICH TYPICALLY STANDS FOR BATTERY BACK UP |
| | LIGHT FIXTURES. |
| | PLEASE ADJUST AND INDICATE BATTERY BACK UP FIXTURES ARE |
| | THE MINIMUM AMOUNT OF BATTERY BACK UP FIXTURES WILL BE |
| | REQUIRED TO MEET THE MINIMUM FOOT CANDLES IN EGRESS |
| | PATHS TO THE PUBLIC RIGHT OF WAY OUTSIDE OF THE |
| | BUILDING. PLEASE SEE NFPA-101 7.8 AND 7.9. |
| | PLEASE ALSO SEE THE MAIN ELECTRICAL ROOM WILL ALSO BE |
| | REQUIRED TO CONTAIN AN BATTERY BACK UP LIGHT OF SOME |
| | KIND. |
| | PLEASE SEE 700.12F FOR CIRCUITING AND 700.16. |
| | |
| | 13) NOTE: PLEASE BE SURE TO STATE ALL ROOM AND AREA |
| | DESIGNATIONS ON PLANS AND BE SURE THESE CORRELATE WITH |
| | THE PANEL SCHEDULES AS SUBMITTED ON PLANS. MOST ARE |
| | DONE HOWEVER SOME ARE MISSING. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | NEC 408.4 |
| | |
| | 14) NOTE: PLEASE CLARIFY UPPER LEVEL PLANS FOR LIGHTING |
| | AND POWER. PLEASE SEE THERE ARE ELECTRICAL AND |
| | MECHANICAL ON PLANS HOWEVER NO CIRCUITING, NO ROOM |
| | DESIGNATIONS, ETC. PLEASE SEE THE SHADED AREAS ON THE |
| | LOWER RIGHT HAND CORNER OF PLANS ON E104 AND 204 WHICH |
| | INDICATES THE AREA OF THE BUILDING IN WHICH THESE AREAS |
| | ARE LOCATED HOWEVER THE SHADED ARE ENCOMPASSES THE |
| | ENTIRE BUILDING AS SHOWN. AS THESE AREAS ARE CLEAR OF |
| | USE, HOW AREA IS ACCESSED, CIRCUITING, LIGHTING |
| | CONTROLS ETC REVIEW FOR MANY ITEMS CAN NOT BE DONE AT |
| | THIS TIME. |
| | PLEASE SE FBC ADMIN SECTION 106.1.2 AND 106.3.5.1.2 FOR |
| | ADDITIONAL INFORMATION NEEDED. |
| | PLEASE SEE NEC 408.4, AND THE FOLLOWING WHICH IS TAKEN |
| | FROM THE NEC COMMENTARY. |
| | |
| | 15) NOTE: PLEASE CLARIFY ANY ROOF-TOP GFI RECEPTACLES |
| | REQUIRED FOR A/C EQUIPMENT. PLEASE SEE 210.63, 210.8B3. |
| | AT THIS TIME THE LOCATION OF ALL EQUIPMENT IS NOT |
| | CERTAIN. |
| | |
| | 16) NOTE: PLEASE SEE THE APARTMENT/RESIDENTIAL UNIT AS |
| | SHOWN ON PLANS WILL BE REQUIRED TO MEET THE NEC FOR A |
| | DWELLING UNIT. |
| | PLEASE SEE MISSING THE TWO MINIMUM REQUIRED SMALL |
| | APPLIANCE CIRCUITS. 210.52B1, 210.11C1, 220.52 PLEASE |
| | SEE THE DINGING ROOM RECEPTACLES ARE SHOWN CIRCUITED TO |
| | THE LIVING ROOM WHICH IS NOT PERMITTED. SAME CODE |
| | SECTION. |
| | PLEASE SEE THE MINIMUM VA FOR THESE REQUIRED CIRCUITS. |
| | PLEASE SEE THE MINIMUM REQUIRED FOR WASHER IS NOT |
| | CORRECT.210.11C2, 220.52 |
| | PLEASE SEE THE MINIMUM FOR THE DRYER IS NOT CORRECT. |
| | 220.54 |
| | PLEASE SEE MISSING ARC FAULT PROTECTION PER 210.12 TO |
| | BE LISTED ON PANEL SCHEDULE. |
| | PLEASE SEE MISSING THE REQUIRED DEDICATED BATH |
| | CIRCUIT(S) PER 210.11C3.(THESE ARE SHOWN SHARING WITH |
| | OTHER DEVICES IN OTHER ROOMS AS LISTED ON PANEL |
| | SCHEDULE. |
| | PLEASE SEE MISSING GFI RECEPTACLE/PROTECTION REQUIRED |
| | FOR WASHING MACHINE. THIS IS NOW WITHIN 6FT OF A |
| | LAUNDRY TUB. IT DOES NOT MATTER IF THIS DEDICATED |
| | DEVICE/OUTLET UNDER THE NEW CODE. 210.8A7 |
| | PLEASE VERIFY THE LOAD SHOWN FOR THE RANGE AS IT |
| | APPEARS LOW. |
| | PLEASE SUBMIT LOAD CALCULATIONS FOR A DWELLING FOR THIS |
| | PANEL. |
| | PLEASE SEE THE CODE SECTION AS REFLECTED TO 220.13 IS |
| | NOT UNDER THE 2005 NEC AND WOULD NOT APPLY. |
| | PLEASE SEE NEC 220, FBC 106.3.5.4 |
| | |
| | 17) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE GENERATOR, ATS, SUB-BASE FUEL TANK ETC |
| | FOR REVIEW. |
| | PLEASE SEE THE MECHANICAL REVIEW AS THE PLANS WILL BE |
| | REQUIRED TO BE REVIEWED AND STAMPED BY DERM DUE TO THE |
| | SIZE OF THE TANK. |
| | ** PLEASE SEE THE SITE, SURVEY, CIVIL, LANDSCAPE AND |
| | OTHER PLANS DO NOT INDICATE ANY GENERATOR UNIT. THIS |
| | NOTE WILL BE FORWARDED TO OTHER TRADES AS THERE WILL BE |
| | COMMENTS FROM OTHER TRADES SUCH AS ELEVATION, LOCATION, |
| | SETBACKS, ETC. |
| | 110.3, 90.7 |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 18) NOTE: PLEASE SEE THE SERVICE IS BEING SHOWN AS GFI |
| | PROTECTED ALONG WITH GFI PROTECTION ON THE GENERATOR? |
| | PLEASE SEE THE REQUIRED PROTECTION PER 230.95, 240.13 |
| | ETC IS FOR *GFP* PROTECTION WHICH IS NOT THE SAME AS |
| | CLASS A GFI PROTECTION FOR PERSONNEL. |
| | PLEASE ADJUST THE DESIGNATION. |
| | PLEASE ALSO SEE THE FOLLOWING AS GFP ON THE EMERGENCY |
| | SECONDARY SIDE IS NOT REQUIRED AND IN FACT ON ANY |
| | SYSTEMS WHICH ARE CONSIDERED LEGALLY REQUIRED OR |
| | EMERGENCY SYSTEMS ARE NOT RECOMMENDED BY THE CODE TO |
| | CONTAIN SUCH PROTECTION. PLEASE KNOW BASED ON THE |
| | INTEREST OFLIFE SAFETY THIS AHJ WILL NOT PERMIT THIS |
| | AS IT CREATES THIS HAZARD TO OCCUPANTS. |
| | PLEASE ALSO SEE THE ATS IS BEING SHOWN AS 3-POLE AND |
| | NOT 4-POLE WHEN A 4-POLE SWITCH WOULD BE NEED WHEN |
| | THERE IS GFP PROTECTION ON THE MAIN. |
| | PLEASE SEE NFPA-110 6.2.15** ISOLATION OF NEUTRAL |
| | CONDUCTORS. PROVISIONS SHALL BE INCLUDED FOR ENSURING |
| | CONTINUITY, TRANSFER, AND ISOLATION OF THE PRIMARY AND |
| | THE EPS NEUTRAL CONDUCTORS WHEREVER THEY ARE SEPARATELY |
| | GROUNDED TO ACHIEVE GROUND-FAULT SENSING. |
| | PLEASE SEE AN ATTACHED BRIEF EXPLANATION FROM "ASCO" |
| | WHITE PAPER: THERE ARE NUMEROUS OTHER NOTED DOCUMENTS |
| | FROM MULTIPLE MANFACTURES WHICH STATE ROUGHLY THE |
| | SAME: |
| | * WHERE GROUND FAULT PROTECTION IS TRIGGERED BY THE |
| | CODE AND AN ALTERNATE POWER SUPPLY IS INCLUDED, |
| | SWITCHING OF THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT |
| | SHOWN ABOVE ILLUSTRATES SUCH A CIRCUMSTANCE. THE |
| | SERVICE IS LARGER THAN 1,000 AMPS. CONSEQUENTLY, GROUND |
| | FAULT PROTECTION IS REQUIRED AT THE MAIN SERVICE |
| | DISCONNECT AT A MINIMUM. IF IT IS INSTALLED THERE AND |
| | THE GENERATOR NEUTRAL GROUNDING WAS THROUGH A SOLID |
| | CONNECTION TO THE MAIN SERVICE NEUTRAL, A GROUND FAULT |
| | WHEN THE GENERATOR IS FEEDING THE LOAD WILL CAUSE THE |
| | MAIN SERVICE DISCONNECT TO OPEN. THIS WILL NOT |
| | DISCONNECT THE ARCING FAULT FROM THE GENERATOR. |
| | COORDINATION IS THUS LOST.* |
| | PLEASE KNOW BASED ON THE INFORMATION FROM SEVERAL |
| | MANUFACTURES AND THE CODE PLEASE ADJUST AS REQUIRED. |
| | PLEASE ALSO SEE GENERATOR GROUNDING DETAIL WILL BE |
| | REQUIRED TO BE REVISED. |
| | PLEASE SEE 250.20, 250.30, 250.66, 240.13, 230.95, |
| | 700.7D, 700.26 |
| | |
| | 19) NOTE: PLEASE INDICATE ALL TRANSFORMER GROUNDING |
| | ATTACHMENTS ON THE RISER AND SIZES OF CONDUCTORS. |
| | 250.20, 250.50, 250.66, 250.58 |
| | |
| | 20) NOTE: PLEASE PROVIDE AN ENLARGED VIEW OF THE MAIN |
| | ELECTRICAL ROOM WITH EXACT SCALE FOR REVIEW OF |
| | ELECTRICAL EQUIPMENT. |
| | 110.26 |
| | FBC 106.1.2 |
| | |
| | 21) NOTE: PLEASE CORRELATE PLANS AND RISER FOR THE |
| | SIZES OF THE TRANSFORMER. PLEASE SEE RISER SHOWS 30KVA |
| | AND THE PLAN SHOWS 45 KVA. |
| | PLEASE SEE THIS MAY BE THE REASON FOR THE FOLLOWING |
| | COMMENT IS THE TRANSFORMER IS INDEED A 45KVA UNIT. FBC |
| | 106.1.2 COORDINATION. |
| | |
| | 22) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION SHOWN |
| | FOR THE BREAKER TO THE 30KW TRANSFORMER ON RISER IS TOO |
| | HIGH AS LISTED IN THE MSB PANEL SCHEDULE AND RISER. |
| | PLEASE SEE 450.3 AND THE MAXIMUM OF 125%.(UNLESS |
| | MEETING EXCEPTION, IF SO, PLEASE PROVIDE ALL |
| | INFORMATION FOR THE TRANSFORMER. |
| | |
| | 33) NOTE: PLEASE SEE THERE ARE SEVERAL PANELS ON RISER |
| | AND PANEL SCHEDULES WHICH INDICATE 60AMP MLO AND PANEL |
| | BEING ACTUALLY A HIGHER RATED PANEL. PLEASE KNOW IF |
| | PANEL HAS A 60AMP/100AMP FEED ETC AND THE PANEL IS A |
| | 100AMP/150AMP OR 200AMP RATED PANEL PLEASE INDICATE THE |
| | ACTUAL PANEL RATING. THERE IS NO 60AMP RATED PANELS |
| | WHICH ARE 30CIRCUIT KNOWN TO THIS OFFICE. |
| | PLEASE SEE SEVERAL COMMENTS BELOW FOR COORDINATION OF |
| | PANELS, RISER, AMPERAGES, AND WHETHER OR NOT PANELS |
| | CONTAIN MLO OR MCB. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 34) NOTE: PLEASE SEE H3 WHICH IS SHOWN AS 60AMP MLO ON |
| | RISER AND SHOWN AS 400AMP MCB ON PANEL SCHEDULE. PLEASE |
| | CORRELATE. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 35) NOTE: PLEASE SEE PANEL P4 WHICH IS SHOWN A S 60AMP |
| | MLO, YET CONTAINS 30CIRCUITS. |
| | PLEASE CORRELATE. |
| | FBC 106.1.2 |
| | |
| | 36) NOTE: PLEASE SEE PANEL C3 WHICH IS SHOWN AS 60AMP |
| | MCB ON PANEL SCHEDULE AND 60AMP MLO ON RISER. PLEASE |
| | CORRELATE. |
| | FBC 106.1.2 |
| | |
| | 37) NOTE: PLEASE SEE PANEL C1 WHICH IS SHOWN AS 100AMP |
| | MCB ON RISER AND 60AMP MCB ON PANEL SCHEDULE. PLEASE |
| | CORRELATE. |
| | FBC 106.1.2 |
| | |
| | 38) NOTE: PLEASE SEE C2 AS THIS IS SHOWN AS 60AMP MCB |
| | AND MLO ON RISER. |
| | PLEASE CORRELATE. |
| | FBC 106.1.2 |
| | |
| | 39) NOTE: PLEASE SEE RISER INDICATES BOTH PANEL C2 AND |
| | C3 BEING FED FROM PANEL C1, HOWEVER PANEL C1 SCHEDULE |
| | DOES NOT INDICATE EITHER OF THESE TWO PANELS? PLEASE |
| | CORRELATE AND ADJUST LOAD CALCULATIONS ETC. THIS WILL |
| | AFFECT SEVERAL ITEMS. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | NEC 240.4, 310.16, 408.4, 215.5 ETC. |
| | |
| | 40) NOTE: PLEASE SEE PANEL H2 IS SHOWN AS 150AMP MLO ON |
| | RISER AND 200AMP MLO ON SCHEDULE. |
| | PLEASE ADJUST AND CORRELATE. |
| | FBC 106.1.2 |
| | |
| | 41) NOTE: PLEASE SEE CODE SECTION NOTED BELOW ALL PANEL |
| | SCHEDULES WHICH INDICATES NEC 220.13? PLEASE SEE ANY |
| | SECTIONS OF THE NEC TO BE NOTED MUST BE FROM THE 2005 |
| | NEC> |
| | PLEASE ADJUST. FBC 106.1.2 |
| | |
| | 42) NOTE: PLEASE SEE LOAD CALCULATIONS WILL NEED |
| | ADJUSTMENTS ONCE OTHER CALCULATIONS HAVE BEEN |
| | CORRECTED. |
| | PLEASE SEE THE CONTINUOUS LOADS WHICH ARE NOTED ON MANY |
| | OF THE PANEL SCHEDULES ARE NOT SHOWN FIGURED INTO THE |
| | MAIN SERVICE AND THE MSB DOES NOTE OR SHOW ANY |
| | CONTINUOUS LOADS AT 125%. |
| | 215.3, 230.42, 220 ETC. |
| | |
| | 43) NOTE: PLEASE KNOW PLANS WILL BE ROUTED TO |
| | ADDRESSING AS THIS IS A NEW BUILDING WHICH IS NOT THE |
| | SAME AS THE EXISTING BUILDING ON THE SAME SITE. BOTH |
| | BUILDINGS CAN NOT HAVE THE SAME ADDRESS. |
| | PLEASE ADJUST TITLE BLOCKS AS NEEDED ONCE THE ADDRESS |
| | HAS BEEN DETERMINED. |
| | FAC 61G1-16.004, 61G15-23.002. |
| | |
| | ** PLEASE SEE ONE SET OF PLANS CONTAINS MANY AREAS |
| | NOTED AND REDLINED IN AREAS OF NOTES. |
| | |
| | *** PLEASE KNOW AS THERE ARE SEVERAL DESIGN CHANGES |
| | REQUIRED AND THERE ARE NUMEROUS ITEMS ON PLANS WHICH |
| | ARE NOT COMPLETE THERE MAY VERY WELL BE NEW COMMENTSON |
| | THE FOLLOWING REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY |
| | ONE SET OF THE OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| 2007-07-03 07:01:40 | 2007-02-03 07:01:40 |
| | REVIEW CONTINUED. |
| 2007-07-02 20:03:30 | 2007-07-02 20:03:30 |
| | REVIEW STOPPED, REVIEW TO CONTINUE AND NOTES TO FOLLOW. |
| 2007-07-02 18:38:37 | 2007-07-02 18:38:37 |
| | PLANS REMOVED FROM INCOMING AND ONE ROLL IN ELEC FOR |
| | REVIEW. PLANS WILL BE RETURNED BACK TO INCOMING WAITING |
| | FOR COMM BOARD ONCE REVIEW HAS BEEN COMPLETED. |