| 2007-08-06 21:32:27 | PEGGY ADAMS ANIMAL |
| | RESCUE LEAGUE |
| | 3200 N MILITARY TRAIL |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07060707 |
| | ADD: 3200 N MILITARY TRAIL |
| | CONT: ANDERSON MOORE |
| | TEL: (561)662-1819 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) SHEET G-001 THE CIVIL ENGINEER CIVIL DESIGN, INC. IS |
| | MISSING THEIR CERTIFICATE OF AUTHORIZATION. 471.023 |
| | F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK |
| | FOR ANY |
| | SHEET BEARING THE NAME OF AN ENGINEER PRACTICING UNDER |
| | A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP, |
| | OFFERING ENGINEERING SERVICES, SHALL INCLUDE THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER. ADD THE NUMBER TO |
| | EACH SHEET.THIS MAY BE ADDED BY HAND. |
| | |
| | 4) SHEET G-001 THE LANDSCAPE ARCHITECT ALSO IS MISSING |
| | THEIR CERTIFICATE OF AUTHORIZATION. ) 481.219 F.S. |
| | CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK FOR ANY |
| | SHEET BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER |
| | A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP, |
| | OFFERING ARCHITECTURAL SERVICES, SHALL INCLUDE THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER.ADD THE NUMBER TO |
| | EACH SHEET. THIS MAY BE ADDED BY HAND. |
| | |
| | 5) SHEET G-001 SITE BUILDING DATA INDICATES THIS |
| | PROJECT IS LOCATED IN A **FIRE ZONE**, |
| | THERE ARE NO LONGER FIRE ZONES IN THE BUILDING CODE. |
| | |
| | 6) PLEASE PROVIDE ORIGINAL SIGNATURE SOILS REPORTS. FBC |
| | 1802.2.1 QUESTIONABLE SOILS, WHERE THE SAFE-SUSTAINING |
| | POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING |
| | VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS |
| | CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE |
| | NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION |
| | SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4 |
| | THROUGH 1802.6 . |
| | |
| | 7) FBC* 105.3RESIDENT INSPECTOR. SUBMIT INSPECTOR |
| | RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA, |
| | DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT |
| | INSPECTORPROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO |
| | ONE OR MORE OF THE FOLLOWING: |
| | XX - BUILDINGS/ADDITIONS OF TYPE I OR II CONSTRUCTION - |
| | ANY MAJOR STRUCTURAL ALTERATIONS |
| | - STRUCTURES IN WHICH THE CONCRETE DESIGN IS |
| | BASED ON COMPRESSIVE |
| | STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| | - PILE DRIVING |
| | XX- BUILDINGS OVER 20,000 SQ FT IN AREA( 35,772 SQ |
| | FT) |
| | - BUILDINGS OVER 2 STORIES IN HEIGHT |
| | XX- BUILDING/STRUCTURES OF UNUSUAL DESIGN |
| | OR METHODS OF CONSTRUCTION |
| | |
| | 8) THIS PROJECT IS LOCATED IN A A-8FLOOD ZONE WITH |
| | THE FINISH FLOOR ELEVATION OF 16.5? MINIMUM FINISH |
| | FLOOR ELEVATION AND ANY MECHANICAL EQUIPMENT ON THE |
| | EXTERIOR OF THE BUILDING BE ABOVE THIS SAME ELEVATION. |
| | PROVIDE FLOOD ZONE ELEVATION CERTIFICATE FOR NEW |
| | CONSTRUCTION BEFORE A CERTIFICATE OF OCCUPANCY WILL BE |
| | ISSUED. |
| | |
| | 9) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| | ADJACENTPROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED |
| | TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS |
| | OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL |
| | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED |
| | TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE |
| | FINAL INSPECTION. |
| | |
| | 10) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE |
| | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS,EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| | CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| | HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| | SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION |
| | TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| | SECTION |
| | SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113 |
| | OF THIS CHAPTER. |
| | |
| | 11) LS-001 THE LIFE SAFETY PLAN FAILS TO IDENTIFYROOM |
| | TYPES, OCCUPANT LOADS FOR ROOMS, |
| | OCCUPANT LOADS FOR DOORWAYS. PLEASE SEE TABLE 1004.1& |
| | 1005.1. |
| | |
| | 10) SHEET C-3.1 THE COVERED ENTRY INDICATES THE DRIVE |
| | TO BE AT 20.80? WHEREAS THE INTERIOR FINISH FLOOR OF |
| | THE LOBBY IS 21.00?. PLEASE PROVIDE A SECTION THROUGH |
| | THIS AREA TO PROVIDE THE FOLLOWING: |
| | 10A) COMPLIANCE WITH 11-4.6.5 VERTICAL CLEARANCE FOR |
| | PASSENGER LOADING ZONE. |
| | 10B) PROVIDE A CURB DETAIL INDICATING COMPLIANCE WITH |
| | 11-4.6.6 PASSENGER LOADING ZONE. |
| | 10C) DEPENDING ON THE 2? CHANGE IN ELEVATION FROM THE |
| | PASSENGER LOADING ZONE TO FINISH FLOOR ELEVATIONS CURB |
| | CUTS 11-4.7. |
| | |
| | 11) PLEASE SEE A-100 AND A-101 THE MAIN LOBBY (101) & |
| | SURRENDER LOBBY (180) PROVIDE DETAILS SHOWING |
| | COMPLIANCE WITH 11-7.2(1) SERVICE COUNTERS WITH |
| | ELEVATIONS OF 36?.SEE DETAILS ON SHEET A-713 DETAILS |
| | 103-105. |
| | |
| | 12) COMMENT DELETED. |
| | |
| | 13)SHEET A-100 & A-103 INDICATES 2 SHOWERS (153 & 155) |
| | BOTH ARE TO BE HANDICAPPED ACCESSIBLE. SHOW COMPLIANCE |
| | WITH 11-4.21(1-8). |
| | |
| | 14) SHEET A-101 DOOR 102B IS MISSING THE 18? ON THE |
| | PULL SIDE AT LATCH.11-4.13.6 MANEUVERING |
| | CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARANCES AT |
| | DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE |
| | AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH IN |
| | THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL. |
| | |
| | 15) THE LIFE SAFETY PLAN INDICATES THERE ARE TWO (2) |
| | AREAS WITH 2HR FIRE RATED WALLS: |
| | 15A)(1) SALLY PORT, SHEET A-100 & A-103 BOTH ARE |
| | MISSING THE WALL TAGS INDICATING THEY ARE 2HR FIRE |
| | RATED WALLS. SEE TABLE 303.3.2. BETWEEN S-2 CLOSED |
| | GARAGE AND BUSINESS OCCUPANCY. PLEASE PROVIDE THE |
| | EQUIVALENT THICKNESS FOR CONCRETE BLOCK FROM THE |
| | MANUFACTURER INDICATING THE EQUIVALENT THICKNESS |
| | 721.3.2. |
| | 15A) (2) SALLY PORT THERE APPEARS TO BE 6 VEHICLES IN |
| | THE GARAGE AND 2 LARGE OBJECTS, NOT CLEAR AS TO WHAT |
| | THIS IS POSSIBLY STORAGE? |
| | |
| | |
| | 15B) THE LIFE SAFETY PLAN ALSO INDICATES AROUND THE |
| | KENNEL OCCUPANCY WHEREAS NEITHER OF THE SHEETS A-100 OR |
| | A-101 PROVIDE ANY WALL TAGS INDICATING A 2HR |
| | SEPARATION. PLEASE PROVIDE THE EQUIVALENT THICKNESS FOR |
| | CONCRETE BLOCK FROM THE MANUFACTURER INDICATING THE |
| | EQUIVALENT THICKNESS 721.3.2. |
| | |
| | 15C) THE LIFE SAFETY SHEET AS WELL AS SHEET A-100 AND |
| | A-104 DO NOT INDICATE A 2HR FIRE RATING ON THE MASONRY |
| | WALLTABLE 303.3.2 INDICATES BETWEEN A BUSINESS AND |
| | R-2 OCCUPANCY WALLS ARE TO BE RATED. THE DOOR SCHEDULE |
| | ALSO NEEDS CORRECTING IN THIS MANNER , SEE OPENING |
| | PROTECTIVE. TABLE 715.3 |
| | |
| | 16) SHEET A-100 ROOM 166 INDICATES THIS IS A FREEZER |
| | BUT THERE IS A PORTION OF THE WALL THAT IS MISSING, IS |
| | THIS A DOORWAY, NEED MORE INFORMATION. 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 17) ROOM 142 INDICATES THIS IS TO BE USED FOR X-RAYS |
| | PLEASE PROVIDE COMPLIANCE WITH: |
| | 435.5.1 SHIELDING. |
| | 435.5.2 X-RAY FILM PROCESSING FACILITIES. |
| | |
| | 18A) SHEET A-105 MEZZANINE # 1THE PLANS INDICATE THIS |
| | TO HAVE A PULL DOWN STAIRWAY LEADING FROM ROOM 133 OR |
| | THE TECH AREA. THIS MEZZANINE HAS AN OCCUPANT LOAD OF |
| | THREE(3). |
| | 505.3 EGRESS WILL ALLOW FOR A SINGLE MEANS OF EGRESS |
| | BUT THE CODE DOESN?T INDICATE THAT A PULL DOWN STAIRWAY |
| | MEETS EGRESS REQUIREMENTS. THE SECOND ISSUE WITH THE |
| | PULL DOWN STAIR IT BLOCKS THE CORRIDOR BELOW. |
| | |
| | 18B) THE FLOOR HATCH WILL ALSO NEED A GUARD AROUND WHAT |
| | EVER ACCESS WILL BE CREATED IN THE FLOOR. 1012.2 |
| | HEIGHT. GUARDS SHALL FORM A PROTECTIVE BARRIER NOT LESS |
| | THAN 42 INCHES |
| | 1012.3 EXCEPTION(2)AT ELEVATED WALKING SURFACES FOR |
| | ACCESS TO AND USE OF ELECTRICAL, MECHANICAL OR PLUMBING |
| | SYSTEMS OR EQUIPMENT, GUARDS SHALL HAVE BALUSTERS OR BE |
| | OF SOLID MATERIALS SUCH THAT A SPHERE WITH A DIAMETER |
| | OF 21 INCHES (533 MM) CANNOT PASS THROUGH ANY OPENING. |
| | |
| | |
| | 19A) SHEET A-105 MEZZANINE # 2 INDICATES THE USE OF A |
| | VERTICAL SHIPS LADDER. PLEASE SEE MEZZANINE MEANS OF |
| | EGRESS, THIS MEZZANINE IS LARGER AND AN OCCUPANT LOAD |
| | OF 8. |
| | 505.3 EGRESS. |
| | 505.3EACH OCCUPANT OF A MEZZANINE SHALL HAVE ACCESS TO |
| | AT LEAST TWO INDEPENDENT MEANS OF EGRESS WHERE THE |
| | COMMON PATH OF EGRESS TRAVEL EXCEEDS THE LIMITATIONS OF |
| | SECTION 1013.3 . WHERE A STAIRWAY PROVIDES A MEANS OF |
| | EXIT ACCESS FROM A MEZZANINE, THE MAXIMUM TRAVEL |
| | DISTANCE INCLUDES THE DISTANCE TRAVELED ON THE STAIRWAY |
| | MEASURED IN THE PLANE OF THE TREAD NOSING. |
| | |
| | 19B) PLANS INDICATE THE GUARD RAIL TO BE 34? TALL, |
| | PLEASE SEE. 1012.2 HEIGHT. GUARDS SHALL FORM A |
| | PROTECTIVE BARRIER NOT LESS THAN 42 INCHES |
| | 1012.3 EXCEPTION(2)AT ELEVATED WALKING SURFACES FOR |
| | ACCESS TO AND USE OF ELECTRICAL, MECHANICAL OR PLUMBING |
| | SYSTEMS OR EQUIPMENT, GUARDS SHALL HAVE BALUSTERS OR BE |
| | OF SOLID MATERIALS SUCH THAT A SPHERE WITH A DIAMETER |
| | OF 21 INCHES (533 MM) CANNOT PASS THROUGH ANY OPENING. |
| | |
| | 20) SHEET A-200 IS THE REFLECTED CEILING PLAN, THE PLAN |
| | IS MISSING EXIT LIGHTS, AND DIRECTIONAL, PLEASE UPDATE |
| | PLAN SECTION 1006. 1006.1.1 |
| | ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED IN |
| | ACCORDANCE WITH THIS SECTION FOR EVERY BUILDING AND |
| | STRUCTURE. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT |
| | ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS AND PASSAGEWAYS LEADING TO |
| | AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT |
| | DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS, WALKWAYS AND EXIT |
| | PASSAGEWAYS LEADING TO A PUBLIC WAY. |
| | |
| | 21) SHEET A-300 ROOF DRAINAGE: |
| | 21A) THE GARAGE ROOF INDICATES THAT THERE WILL BE |
| | THROUGH THE WALL SCUPPERS AND COLLECTORS AND DOWN |
| | SPOUTS (R15) THE SAME MARKINGS ARE USED FOR THE |
| | EMERGENCY OVERFLOW SCUPPERS. THE EMERGENCY OVERFLOW |
| | SCUPPERS ARE NOT TO BE AT THE SAME HEIGHT AS THE |
| | SCUPPERS. |
| | 1503.4.3 OVERFLOW SCUPPERS. |
| | WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT |
| | PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR |
| | PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 |
| | INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND |
| | SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED |
| | VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET |
| | SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING. |
| | |
| | 21B) PLEASE PROVIDE A DETAIL INDICATING THE FOLLOWING: |
| | 1503.6 PROTECTION AGAINST DECAY AND TERMITES. |
| | CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT |
| | LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR |
| | SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON |
| | ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) |
| | HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON |
| | A ROOF ABOVE ANOTHER ROOF. |
| | |
| | 21C) SHEET A-300 INDICATES R9 & R11 EMERGENCY OVERFLOWS |
| | BUT THE WIDTH IS NOT PROVIDED, AN OVERFLOW SCUPPER |
| | SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, PLUMBING. 1503.4.3.PLEASE PROVIDE SIZES OF THE |
| | OVERFLOW SCUPPERS. |
| | |
| | 22)1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE |
| | DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2. GLAZED OPENINGS LOCATED MORE THAN |
| | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE PROVISIONS |
| | OF THE SMALL MISSILE TEST. |
| | |
| | 23) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 24) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL AREREQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 25) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) |
| | OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A)FIXED FRAME, STOREFRONT WINDOWS |
| | B) HORIZONTAL OR PASS THRU WINDOWS |
| | C) MULLIONS HORIZONTAL OR VERTICAL |
| | D) LOUVERS |
| | E) GLAZED DOORS |
| | F) HOLLOW EXTERIOR METAL DOORS SINGLE AND PAIRS |
| | G) OVERHEAD DOORS |
| | H) SKYLIGHTS |
| | I) ROOFING ASSEMBLIES FLAT ROOFS BUILT UP OR MODIFIED, |
| | TILE ROOF AND UNDERLAYMENTS |
| | K) PRE-ENGINEERED A/C STANDS |
| | |
| | 26) THESE ARE THE MOST OFTEN REASONS FOR ROOFING REPORT |
| | FAILURES, THIS ROOF IS MISSING OR NOT INCOMPLIANCE |
| | WITH THE FOLLOW ITEMS: |
| | |
| | ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT. |
| | |
| | ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. |
| | |
| | ___ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO |
| | BE INSTALLED. |
| | |
| | ___ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE |
| | ___ . |
| | |
| | ___ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD |
| | THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS |
| | DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER |
| | SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA |
| | REGISTERED PROFESSIONAL ENGINEER, REGISTERED ARCHITECT |
| | OR REGISTERED ROOF CONSULTANT MAY BE SUBMITTED. |
| | |
| | ___THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO |
| | ENHANCED FASTENING ALLOWED. |
| | |
| | 27) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | |
| | |
| | BUILDING PLAN REVIEW II |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |