| 2007-07-10 17:01:47 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | ** FBC-2004 CHAPTER 11. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. PLEASE INDICATE ON THE FLOOR PLAN OF THE PROPOSED |
| | HANDICAP BATHROOMS THEIR ROOM DEMENSIONS ON THE |
| | RESUBMITTAL. |
| | |
| | 2. AN UNOBSTRUCTED TURNING SPACE (FIVE FEET, 5') |
| | COMPLYING WITH SECTION 11-4.2.3 SHALL BE PROVIDED |
| | WITHIN AN ACCESSIBLE TOILET ROOM. |
| | NOTE: PLEASE INDICATE THIS TURNING SPACE ON THE |
| | RESUBMITTED BATHROOM FLOOR PLANS. |
| | |
| | 3. DETAIL OF THE ACCESSIBLE LAVATORIES WITH THE |
| | FOLLOWING INFORMATION IS REQUIRED ON THE RESUBMITTAL. |
| | A} 11-4.19.2, HEIGHT AND CLEARENCES [SEE FIGURE 31]. B} |
| | 11-4.19.3, CLEAR FLOOR SPACE [SEE FIGURE 32]. C} |
| | 11-4.19.4, EXPOSED PIPES AND SURFACES. D} 11-4.19.5, |
| | FAUCETS. |
| | |
| | 4. DETAIL OF THE ACCESSIBLE WATER CLOSETS WITH THE |
| | FOLLOWING INFORMATION IS REQUIRED ON THE RESUBMITTAL. |
| | A} 11-4.16.2, CLEAR FLOOR SPACE [SEE FIGURE 28]. B} |
| | 11-4.16.4, GRAB BARS [SEE FIGURE 29]. C} 11-4.16.6 |
| | DISPENSERS [SEE FIGURE 29(B)]. |
| | |
| | 5. DETAIL OF THE ACCESSIBLE DRINKING FOUNTAIN WITH THE |
| | FOLLOWING INFORMATION IS REQUIRED ON THE RESUBMITTAL. |
| | A} 11-4.15.2, SPOUT HEIGHT [SEE FIGURE 27(A)]. B} |
| | 11-4.15.3, SPOUT LOCATION. C} 11-4.15.4, CONTROLS. D} |
| | 11-4.15.5, CLEARENCES. |
| | NOTE: SHOW COMPLIANCE WITH 11-4.15.(10)(A) PROVISIONS |
| | FOR THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| | |
| | 6. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3 |
| | PLUMBING THE FOLLOWING IS REQUIRED ON THE RESUBMITTAL. |
| | (3) WATER SUPPLY PIPING (RISER DIAGRAM INDICATING PIPE |
| | SIZES, VALVE LOCATIONS, WATER HAMMER ARRESTORS). (5) |
| | WATER HEATERS. (8) BACK FLOW PREVENTION. (10) LOCATION |
| | OF THE WATER SUPPLY LINE. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS EXAMINER |