| Plan Review Notes For Permit 07060684 |
| Permit Number |
07060684 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-09-12 16:44:11 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH | | | A SEALACCEPTABLETO THE BOARD PER 61G15-23.001, AND | | | ILLUSTRATED IN SAME. SEE BUILDING REVIEW COMMENT. | | | | | | 2} WHEN RESUBMITTING ASSEMBLE THE SETS TOGETHER. THE | | | ELECTRICAL SHEETS WERE SEPARATE FROM THE REST OF THE | | | RESUBMITTED SETS. PLEASE STAPLE BOTH SETS IN ORDER. | | | | | | ASIDE FROM THE OUTDATED SEAL ON THE COMPLIANCE FORM, | | | THE ELECTRICAL PLANS ARE CODE COMPLIANT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|