| 2007-09-08 16:17:03 | BUILDING PLAN REVIEW |
| | PERMIT: 07060684 |
| | ADD: 4047 OKEECHOBEE BLVD |
| | CONT: CB BOVENKAMP, INC. |
| | TEL: (305)233-4438 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 3RD |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. LOOSE SHEETS ARE NOT |
| | ACCEPTABLE. SUBMIT THE TWO COMPLETE NEW SETS WITH NEW |
| | INFORMATION AND ONE OLD SET, THE ENERGY CALCUALTIONS |
| | INCLUDED. |
| | |
| | 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. ****THE |
| | NOC HAS TO BE FILED AT THE COURT HOUSE AND THEN |
| | SUBMITTED TO OUR OFFICE. SEE NOC APPLICATION FORM IN |
| | PACKAGE. |
| | |
| | 3)OK |
| | |
| | 4)FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTION 303, 304 AND 305 OF THIS |
| | CODE. |
| | **** NOTE: ALTERATION LEVEL 2 AND 3 INCLUDES THE |
| | RECONFIGURATION OF SPACE. IF ANY WALLS ARE REMOVED OR |
| | ADDED,THE SPACE IS CONSIDERED RECONFIGURED. SEE |
| | SHEET G100. |
| | **THIS IS NOT A LEVE 1 ALTERATION. ONCE AGAIN SEE THE |
| | CODE SECTIONS MENTIONED ABOVE. |
| | |
| | 5)INDICATE THE TYPE OF BACKING FOR THE GRAB BARS |
| | WHICH WILL MEET THE REQUIREMENTS OF 250LBS. |
| | SEC.11-4.26.3(1) |
| | ****** THE NOTE ON SHEET A200 ADDRESSING THE GRAB BAR |
| | BACKING DOES NOT STATE WHAT TYPE OF MATERIAL WILL BE |
| | USED. WHAT IS THE GAUGE OF THE METAL STUD? WILL THERE |
| | BE ADDITIONAL WOOD BACKING? IF SO, STATE WHAT TYPE WILL |
| | BE USED.THE INFORMATION SHALL BE SPECIFIC, AND THE |
| | TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN |
| | PART, NOR SHALL THE TERM ?LEGAL? OR ITS EQUIVALENT BE |
| | USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION. |
| | |
| | **NEW** |
| | A)THE SEAL ON THE ENERGY CALCULATIONS HAS BEEN |
| | OBSOLETE SINCE DECEMBER 31ST 2005. THE WORD |
| | ?CERTIFICATE? WAS CHANGED TO ?LICENSE?. THE ENGINEER |
| | NEEDS TO UP-DATE HIS SEAL. SEE F.A.C 61G15-23.001 NEW |
| | SEAL INFORMATION. THE INFORMATION IN THE PACKAGE SHALL |
| | MATCH WHAT IS ON THE PLANS IN REFERENCE TO THE WALLS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |