Plan Review Notes
Plan Review Notes For Permit 07060684
Permit Number 07060684
Review Stop E
Sequence Number 2
Notes
Date Text
2007-08-17 11:56:08 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE
 SHOWN ON THE PLAN.
 COMMENT TO THE RESPONSES DATED JULY 16, 2007: INDICATE
 COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR SPACE CONTROLS
 FOR LIGHTING." STANDARD SWITCHES ARE SHOWN ON THE PLAN.
 NOTE #1 ADDRESSING THIS ISSUE STATES THAT THE "SPACES
 LESS THAN 5000 SF". PLEASE SEE 13-101.1.4. S "SPACE" IS
 NOT A "BUILDING", THE "BUILDING" IS MORE THAN 5000 SF,
 THE "SPACE" MUST COMPLY.
  
 2} PAGE #2 OF THE ENERGY GAUGE INPUT DATA REPORT, DOES
 NOT INDICATE THE CORRECT NUMBER OF FIXTURES AS SHOWN ON
 THE PLAN, THE WATTAGES PER LUMINAIRE ARE INCORRECT, AND
 THE CONTROL TYPE MUST BE PER 13-415.1ABC.1.2. THIS
 REVIEW} THE CONTROL TYPE IS NOT IN COMPLIANCE, SEE
 COMMENT #1.
  
 3} PER 13-103.1.1, THE PERSON PREPARING THE COMPLIANCE
 CERTIFICATION MUST SIGN AND SEAL SAME.SEE SHEET #3.
 THIS REVIEW} SHEET #3 IS NOT SEALED.
  
 NEW COMMENT #4} THE WATTAGES GIVEN IN THE LIGHTING
 SECTION OF THE INPUT DATA REPORT, PAGES 2 AND 3, SEEM
 TO BE IN EXCESS OF THE ALLOWED WATTAGES. IG: TECH ROOM
 107 @ 285 SQ FT X 1.1 (ALLOWED TABLE 13-415.2B ENCLOSED
 SPACE) = 313.5. THE POWER GIVEN FOR THAT SPACE IS 510
 WATTS. PLEASEREVIEW THE CALCULATIONS
  
 NEW COMMENT #5} THIS REVIEW WAS DONE UNDER THESE
 CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS,2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1. PLEASE CORRECT SHEET G100.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718