Plan Review Notes
Plan Review Notes For Permit 07060684
Permit Number 07060684
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-27 11:24:40 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE
 SHOWN ON THE PLAN.
  
 2} PAGE #2 OF THE ENERGY GAUGE INPUT DATA REPOR, DOES
 NOT INDICATE THE CORRECT NUMBER OF FIXTURES AS SHOWN ON
 THE PLAN, THE WATTAGES PER LUMINAIRE ARE INCORRECT, AND
 THE CONTROL TYPE MUST BE PER 13-415.1ABC.1.2..
  
 3} PER 13-103.1.1, THE PERSON PREPARING THE COMPLIANCE
 CERTIFICATION MUST SIGN AND SEAL SAME. SEE SHEET #3.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718