| 2007-08-27 19:06:55 | 2007-08-27 19:06:55 |
| | |
| | *** DENIED REVIEW *** |
| | |
| | 1) NOTE: PLEASE SEE THAT PLANS ARE BEING SUBMITTED WITH |
| | THE ADDITIONAL WHIRLPOOL CIRCUITS BEING ADDED TO UNIT |
| | AND PANEL SCHEDULE HOWEVER NO LOADS WERE INCREASED ON |
| | THE LOAD CALCULATIONS OR SERVICE. PLEASE KNOW THAT |
| | BASED ON THE EXISTING LOAD SHOWN THIS SERVICE PANEL, |
| | MAIN AND FEEDERS WILL BE OVER LOADED. PLEASE SUBMIT |
| | REVISED PLANS TO INCREASED THE SERVICE TO UNIT. PLEASE |
| | ALSO CONFIRM THE LOAD ON THE INSTA-HOT AS THIS OFFICE |
| | HAS NOT SEEN ONE AT 600VA. (PLEASE SUBMIT SPEC SHEETS) |
| | PLEASE SEE NEC 2005 AS THERE ARE TOO MANY SECTIONS TO |
| | LIST AL OF THE ITEMS FOR THE OVER LOADED SERVICE AND |
| | PANEL. |
| | 220, 215.5, 240.4, 310.16, 220.83B, |
| | 230.90,240.6,230.76,230.79,230.70, ETC. |
| | |
| | 2) NOTE: PLEASE SEE THAT IN NO CASE MAY PLANS WHICH ARE |
| | SIGNED, DATED AND SEALED BY AN ARCHITECT OR ENGINEER |
| | HAVE HAND DRAWN CHANGES ON PLANS OR WHITE-OUT. THIS IS |
| | NOT PERMITTED EVEN WHEN PLANS ARE NOT SIGNED AND SEALED |
| | BY A DESIGN PROFESSIONAL. |
| | FS 481, 471, |
| | FBC 106.1.2, 106.3.1, ETC. |
| | |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |