Plan Review Notes
Plan Review Notes For Permit 07060675
Permit Number 07060675
Review Stop E
Sequence Number 3
Notes
Date Text
2007-08-27 19:06:552007-08-27 19:06:55
  
 *** DENIED REVIEW ***
  
 1) NOTE: PLEASE SEE THAT PLANS ARE BEING SUBMITTED WITH
 THE ADDITIONAL WHIRLPOOL CIRCUITS BEING ADDED TO UNIT
 AND PANEL SCHEDULE HOWEVER NO LOADS WERE INCREASED ON
 THE LOAD CALCULATIONS OR SERVICE. PLEASE KNOW THAT
 BASED ON THE EXISTING LOAD SHOWN THIS SERVICE PANEL,
 MAIN AND FEEDERS WILL BE OVER LOADED. PLEASE SUBMIT
 REVISED PLANS TO INCREASED THE SERVICE TO UNIT. PLEASE
 ALSO CONFIRM THE LOAD ON THE INSTA-HOT AS THIS OFFICE
 HAS NOT SEEN ONE AT 600VA. (PLEASE SUBMIT SPEC SHEETS)
 PLEASE SEE NEC 2005 AS THERE ARE TOO MANY SECTIONS TO
 LIST AL OF THE ITEMS FOR THE OVER LOADED SERVICE AND
 PANEL.
 220, 215.5, 240.4, 310.16, 220.83B,
 230.90,240.6,230.76,230.79,230.70, ETC.
  
 2) NOTE: PLEASE SEE THAT IN NO CASE MAY PLANS WHICH ARE
 SIGNED, DATED AND SEALED BY AN ARCHITECT OR ENGINEER
 HAVE HAND DRAWN CHANGES ON PLANS OR WHITE-OUT. THIS IS
 NOT PERMITTED EVEN WHEN PLANS ARE NOT SIGNED AND SEALED
 BY A DESIGN PROFESSIONAL.
 FS 481, 471,
 FBC 106.1.2, 106.3.1, ETC.
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]