| 2007-06-24 11:13:08 | *** UNSAT *** |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| | NOT MADE BY OTHER TRADE(S). |
| | |
| | 2) NOTE: NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE |
| | INDICATE SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS |
| | THESE AS SMOKE DETECTORS. |
| | PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN |
| | SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY |
| | INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS |
| | ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN |
| | THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS |
| | OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE |
| | ALARMS. |
| | |
| | BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| | FOR OTHER NEW HOMES. |
| | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| | RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE*. |
| | PLEASE SEE NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | 3) NOTE: PLEASE COMPLETE PANEL SCHEDULE WITH THE |
| | CONDUCTOR SIZES PER 240.4, 310.16, 408.4. |
| | |
| | 4) NOTE: PLEASE SEE THE WATER HEATER UNDER THE NEW 2005 |
| | NEC IS REQUIRED TO BE SHOWN AT 125% IN LOAD |
| | CALCULATIONS. |
| | 422.13 |
| | |
| | 5) NOTE: PLEASE SEE PLANS APPEAR TO BE MISSING THE |
| | RECEPTACLE LOCATION FOR THE DISHWASHER. PLEASE ALSO SEE |
| | THE 210.4B IF BOTH THE DISH/ DISP ARE BEING FED TO THE |
| | SAME YOKE WHICH WILL REQUIRE A 2-POLE BREAKER. |
| | |
| | 6) NOTE: PLEASE SEE SOME RECEPTACLES MISSING PER 210.52 |
| | FOR 2FT OR MORE OF WALL SPACE. |
| | PLEASE SEE REDLINED PLANS AS SOME OF THESE ARE SHOWN. |
| | |
| | 7) NOTE: PLEASE SEE THE LOAD CALCULATIONS SEEM TO BE |
| | MISSING THE DEDICATED LOAD FOR THE DISPOSAL. |
| | PLEASE ADJUST LOAD CALCULATIONS. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 8) NOTE: PLEASE SEE THE OUTER BALCONY DOES NOT SHOW ANY |
| | GFI RECEPTACLE(S) OR LIGHTING. THIS IS ONLY NOTED AS |
| | THIS IS NOT REQUIRED BY CODE HOWEVER MAY BE PLACED ON |
| | PLANS IF ANY IS TO BE INSTALLED. |
| | ** ONLY NOTED ** |
| | |
| | 9) NOTE: PLEASE SEE ALL RECESSED LIGHTING LUMINARIES |
| | ARE REQUIRED TO MEET FBC 2004 13-606.1.ABC.1.2.4. |
| | PLEASE PLACE NOTE/INFORMATION FOR THIS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |