| 2007-09-19 14:00:42 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600C-04R (SEE |
| | ATTACHED FORMS), PER FBC 13-600.3.C. |
| | |
| | 2) WHEN SUBMITTING THE REVISED ENERGY CALCULATIONS MAKE |
| | SURE THEY ARE LEGIBLE NOT FADED, AND SIGNED BY |
| | OWNER/AGENT ALSO, SEE FBC 13-103.1.2. |
| | |
| | 3) AS NOTED IN LAST REVIEW 8-7-07 NOTE #4. THE BATHROOM |
| | IN THE ADDITION NEEDS AN EXHAUST FAN, SEE 2004 FBC/R |
| | R303.3. PLEASE SHOW ON MECHANICAL AND ELECTRICAL |
| | PLANS. |
| | |
| | 4) AS THE EXISTING HOUSE IS NOT PART OF THE WORK UNDER |
| | REVIEW PLEASE REMOVE THAT DUCT WORK AND EQUIPMENT FROM |
| | THE PLAN, SEE FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, |
| | NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN |
| | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| | CODE AND RELEVANT LAWS. |
| | |
| | 5) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER |
| | FBC 104.2.1 . (SEE PLANS PAGE MEP-1) PLEASE SIGN. |
| | |