| 2007-10-03 10:15:03 | 2004 FLORIDA BUILDING CODE WITH 2006 AMENDMENTS |
| | UN-PERMITTED ADDITION TO SINGLE FAMILY DWELLING |
| | CONNECTED EXISTING DETACHED GARAGE TO EXISTING DWELLING |
| | AND CONVERTED TO LIVING SPACE |
| | WOOD FRAME AND STUCCO CONSTRUCTION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) THE VALUE OF THE WORK FOR THE ADDITION HAS BEEN |
| | INCREASED TO $ 61515.00BASED ON ICC BUILDING |
| | VALUATION DATA. ADDITIONAL PERMIT FEES AND RADON FEES |
| | OF $1193.36 ARE DUE. THE PERMIT FEES ARE BASED ON THE |
| | COST OF CONSTRUCTION AT THE TIME THE PERMIT WAS APPLIED |
| | FOR WHICH IS $94.06 PER SQFT. |
| | |
| | 4) TWO SETS OF SIGNED AND SEALED PLANS ARE REQUIRED. |
| | SOME OF THE DRAWINGS DO NOT HAVE THE EMBOSSED SEAL AND |
| | SOME HAVE THE ENGINEER'S TITLE BLOCK BUT ARE NOT SIGNED |
| | AND SEALED. |
| | SEE FS 471 AND FAC 61G15-23.002. |
| | |
| | 5) SUBMIT ENERGY CALCULATIONS FOR THE ADDED LIVING |
| | SPACE AS REQUIRED BY 2004 FBC CHAPTER 13. THE ONES THAT |
| | WERE SUBMITTED ARE ON THE WRONG FORM, NEED TO BE SIGNED |
| | BY THE OWNER/AGENT AND ARE NOT LEGIBLE. SEE THE |
| | MECHANICAL REVIEW COMMENTS. |
| | |
| | 6) THE SECTION A-A ON A-1 SPECIFIES AN R-VALUE OF R-19 |
| | FOR THE SINGLE ASSEMBLY CEILING. WHICH IS SHOWN WITH 2 |
| | X 4 RAFTERS. R-19 INSULATION REQUIRES A MINIMUM 2 X 6 |
| | ASSEMBLY. SEE FBC CHAPTER 13. |
| | |
| | 7) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS. EXTERIOR |
| | WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) SHALL |
| | HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE RATING |
| | WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL NOT |
| | EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM AN |
| | ADJACENT PROJECTION OR WALL. |
| | EXCEPTION : DETACHED GARAGES ACCESSORY TO A DWELLING |
| | LOCATED WITHIN 2 FEET (610 MM) OF A LOT LINE SHALL BE |
| | PERMITTED TO HAVE ROOF EAVE PROJECTIONS NOT EXCEEDING 4 |
| | INCHES (102 MM). |
| | PROJECTIONS EXTENDING INTO THE 6-FOOT (1829 MM) |
| | SEPARATION DISTANCE SHALL HAVE NOT LESS THAN 1-HOUR |
| | FIRE-RESISTIVE CONSTRUCTION ON THE UNDERSIDE. THE ABOVE |
| | PROVISIONS SHALL NOT APPLY TO WALLS WHICH ARE |
| | PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM |
| | WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING |
| | AND PARALLEL TO THE PROPERTY LINE. |
| | EXCEPTION: TOOL AND STORAGE SHEDS, PLAYHOUSES AND |
| | SIMILAR STRUCTURES ARE NOT REQUIRED TO PROVIDE WALL |
| | PROTECTION BASED ON LOCATION ON THE LOT. BECAUSE THE |
| | DISTANCE TO THE PROPERTY LINES IS LESS THAN 6 FEET, |
| | SHOW THAT THE DISTANCE TO STRUCTURES ON ADJACENT |
| | PROPERTY IS NOT LESS THAN 6 FEET. |
| | |
| | 8 ) SHOW COMPLIANCE WITH R403.1.4 MINIMUM FOOTING |
| | DEPTH, R404.1.6 FOUNDATION HEIGHT ABOVE FINISH GRADE |
| | AND R319.1(5) PROTECTION AGAINST DECAY. PROVIDE |
| | DIMENSIONS FROM GRADE ON THE FOUNDATION SECTION THAT |
| | SHOWS COMPLIANCE. SEE PREVIOUS COMMENTS. |
| | |
| | 9) SHOW COMPLIANCE WITH R301.1 DESIGN. |
| | BUILDINGS AND STRUCTURES, AND ALL PARTS THEREOF, SHALL |
| | BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING |
| | DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS AND |
| | WIND LOADS AS PRESCRIBED BY THIS CODE. THE CONSTRUCTION |
| | OF BUILDINGS AND STRUCTURES SHALL RESULT IN A SYSTEM |
| | THAT PROVIDES A COMPLETE LOAD PATH CAPABLE OF |
| | TRANSFERRING ALL LOADS FROM THEIR POINT OF ORIGIN |
| | THROUGH THE LOAD -RESISTING ELEMENTS TO THE FOUNDATION. |
| | PROVIDE DETAILS THAT SPECIFY THE CONNECTIONS USED TO |
| | COMPLY. SPECIFY THE CONNECTORS AT THE ROOF RIDGE IF |
| | ROOF IS FRAMED WITH RAFTERS RATHER THAN ENGINEERED |
| | TRUSSES AS SHOWN ON SECTION A-A ON SHEET A-1. |
| | |
| | 10) PLEASE CLARIFY THE FRAMING OF THE ROOF ASSEMBLY FOR |
| | THE ADDITION AND THE GARAGE. ARE THESE 2 X 4 RAFTERS AT |
| | 2' O.C. OR ENGINEERED TRUSSES? IF THESE ARE 2 X 4 |
| | RAFTERS WITH THE CEILING ATTACHED DIRECTLY TO THE |
| | BOTTOMS OF THE RAFTERS, THE SPANS APPEAR TO BE TOO |
| | MUCH. SEE FBC TABLE R802.2.3.1(2). SPECIFY THE SPANS |
| | AND RAFTER LUMBER SPECIES AND GRADE. PROVIDE AN |
| | ANALYSIS SHOWING THAT THE ROOF SYSTEM IS CAPABLE OF |
| | WITHSTANDING THE UNIFORM AND LIVE LOADS. |
| | |
| | 11) THE CONNECTORS SPECIFIED FOR THE RAFTERS (SIMPSON |
| | MST) DO NOT PROVIDE ANY LATERAL LOAD RESISTANCE AND |
| | WITH CATHEDRAL CEILINGS THERE IS NO CEILING DIAPHRAM. |
| | SPECIFY HOW THE STRUCTURE WILL RESIST THE LATERAL |
| | WINDLOADS. SEE FBC R801.2 AND CITY OF WPB AMENDMENTS TO |
| | FBC 106.1.2 |
| | |
| | 12) THE WINDOWS BESIDE THE FRONT AND REAR SWING DOORS |
| | ARE REQUIRED TO BE SAFETY GLAZING PER R308.1(6). |
| | |
| | 13) SPECIFY THE EXTERIOR SOFFIT COVERING AT THE |
| | OVERHANGS. IF SOFFIT MATERIALS ARE VINYL OR ALUMINUM |
| | PRODUCT APPROVALS WILL BE REQUIRED. |
| | |
| | 14) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE |
| | EXTERIOR SWING DOORS, THEWINDOW MULLIONS, THE ROOF |
| | COVERING MATERIAL, STORM PANELS AND ANY OTHER ITEMS |
| | REGULATED BY FAC RULE 9B-72. |
| | |
| | 15) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE |
| | STORM PANELS. SPECIFY THE MOUNT TYPE, THE ANCHOR TYPE, |
| | THE ANCHOR SPACING, EDGE DISTANCE, SPANS, ETC. |
| | |
| | 16)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. |
| | |
| | 17)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 18) THE DETACHED GARAGE THAT IS CONVERTED TO LIVING |
| | SPACE IS REQUIRED TO COMPLY WITH EXISTING BUILDING CODE |
| | SECTION 807.2 FOR WINDLOADS. SUBMIT 2 COPIES OF A |
| | SIGNED AND SEALED WINDLOAD ANALYSIS OF THE GARAGE FROM |
| | FLORIDA LICENSED ENGINEER. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |