Plan Review Notes
Plan Review Notes For Permit 07060640
Permit Number 07060640
Review Stop M
Sequence Number 1
Notes
Date Text
2007-07-22 09:50:35--------------DENIED----------------
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
 NFPA 37-02
  
 1. PROVIDE MANUFACTURER'S SPECS INDICATING MINIMUM
 REQUIRED CLEARANCES FOR MAINTENANCE; AIRFLOW FOR
 COMBUSTION, COOLING AND VENTILATION. NFPA 37-02 SEC.
 4.1.1
  
 2. PROVIDE INFORMATION ON WEATHERPROOF ENCLOSURE WHICH
 IS BEING PROVIDED AS INDICATED ON PLANS. NFPA 37-02 SEC
 4.1.4
  
 3. NO INFORMATION IS PROVIDED REGARDING GENERATOR
 EXHAUST. PLEASE SHOW COMPLIANCE WITH ALL APPLICABLE
 SECTIONS OF NFPA 37-02 CH. 8.
  
 4. PROVIDE INFORMATION RELATING TO WIND RESISTANCE IN
 ACCORDANCE WITH FBC,M 301.13 AND FBC CH.16. SEE
 BUILDING PLAN REVIEW COMMENT #4.
  