| Plan Review Notes For Permit 07060640 |
| Permit Number |
07060640 |
|
| Review Stop |
FUEL |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-22 10:43:04 | -------------DENIED-------------- | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS FBC | | | CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. SHEET 1 OF 1 INDICATES 500 GALLON TANK, SHEET E-1 | | | INDICATES 550 GALLONS. PLEASE COORDINATE DRAWINGS PER | | | FBC 106.1.1. | | | | | | 2. ABOVE GROUND STORAGE TANKS OF 550 GALLONS OR MORE | | | REQUIRE APPROVAL BY PALM BEACH COUNTY DERM PRIOR TO | | | PERMITTING BY THE CITY OF WEST PALM BEACH. FOR | | | ADDITIONAL INFORMATION, PLEASE CONTACT DERM AT | | | 561-233-2400 OR WWW. PBCGOV.COM/ERM | | | | | | 3.SHEET 1 OF 1 HAS BEEN MODIFIED BY HAND. SIGNED AND | | | SEALED DRAWINGS SHALL NOT BE MODIFIED. FS 471.025 | | | | | | 4. ABOVE GROUND TANKS REQUIRE EMERGENCY RELIEF VENTING | | | FOR FIRE EXPOSURE. PLEASE SHOW SITE SPECIFIC MEANS OF | | | EMERGENCY RELIEF VENTING IN COMPLIANCE WITH NFPA 30-00 | | | SEC. 2.2.5.2. EMERGENCY RELIEF VENT PIPING SHALL BE IN | | | CONFORMANCE WITH NFPA 30-00 CHAPTER 3. | | | | | | RONALD J REGUEIRO | | | 561.805-6719 | | | [email protected] | | | |
|