Plan Review Notes
Plan Review Notes For Permit 07060640
Permit Number 07060640
Review Stop E
Sequence Number 1
Notes
Date Text
2007-07-02 13:20:302007-07-02 13:20:30
  
 *** UNSAT ***
  
  
 *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE
 REVIEWED AT THIS TIME.
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE
 CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING
 ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED
 FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006
 THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC
 AND THE 2005 NFPA-70. PLEASE LIST THE FOLLOWING: SOME
 ARE ALREADY SHOWN ON PLANS.
  
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 2002 NFPA-110.
  
 2) NOTE: PLEASE SEE THE APPLIED VALUE FOR COMPLETE
 SCOPE OF WORK AS APPLIED ON PERMIT APPLICATION SHALL
 INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COST
 ETC. THIS APPLIES EVEN IS ANY IS SUPPLIED BY THE OWNER
 AND NO COST TO CONTRACTOR.
 PLEASE SEE FBC 108.3 AS THIS VALUE MAY BE ADJUSTED BY
 THE ADOPTED GUIDES UNDER THE FLORIDA BUILDING CODE.
  
 3) NOTE: PLEASE SEE THE RESPONSE LETTER FROM THE
 PREVIOUS EXPIRED PERMIT APPLICATION ADDRESSES THE
 LETTER TO A *MIKE HIRTANZO* AS THE ELECTRICAL PLAN
 REVIEWER. PLEASE SEE THE PREVIOUS REVIEW NOTES UNDER
 PREVIOUS APPLIED PERMIT WAS GIVEN BY MYSELF AND THE
 ABOVE PERSON DOES NOT WORK FOR THE CITY OF WEST PALM
 BEACH.
  
 4) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT
 SHEETS FOR ALL EQUIPMENT WHICH INDICATE LISTINGS FROM A
 NRTL. THE LISTINGS AS SHOWN FOR THE GENERATOR AS
 SUBMITTED DO NOT MEET ANY NRTL AS LISTED.
 PLEASE SUBMIT THE SPECS FOR THE WP ENCLOSURE ETC.
 PLEASE COORDINATE ALL.
 PLEASE BE SURE TO HIGH-LIGHT ALL EQUIPMENT SPECIFIC TO
 WORK.
 NEC 110.3, 90.7 ETC
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE THE PLANS HAVE HAND-DRAWN CHANGES
 WHICH ARE NOT PERMITTED TO PLANS WHICH ARE SIGNED,
 DATED AND SEALED BY AN ENGINEER. FS 471.025
 PLEASE SEE 1 OF 1.
  
 6) NOTE: PLEASE SEE TWO DIFFERENT SIZE TANKS ARE BEING
 INDICATED ON PLANS. ONE 500 AND THE OTHER 550 GALS.
 PLEASE COORDINATE.
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE THE ADDRESS ON PLANS NEEDS TO
 COORDINATE WITH THE SITE. THE ADDRESS IS NOT NE 36TH
 ST.
 FA C61G1-16.004
  
 8) NOTE: PLEASE SEE MISSING MEANS OF DISCONNECT AT
 BUILDING. THE BREAKER DOES NOT MEET 702.11,
 225.31-225.39
 PLEASE KNOW THIS DISCONNECTING MEANS ONLY NEEDS TO BE
 RATED FOR THE LOAD SERVED AND DOES NOT NEED TO CONTAIN
 OCP AS THE BREAKER IN THE GENERATOR CONTAINS THE OCP.
  
 9) NOTE: PLEASE SEE PERMIT APPLICATION REQUEST TO
 PROVIDE IN DETAIL THE SCOPE OF WORK. PLEASE INCLUDE THE
 SIZE OF THE GENERATOR.
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE RISER SHOWS THE CAPACITY PROVIDED
 AS 1041AMPS, YET THE GENERATOR ONLY INDICATES
 1000AMPS?
 PLEASE COORDINATE ALL EQUIPMENT, LOADS ETC.
  
 11) NOTE: PLEASE SEE SITE PLANS WHICH WERE SUBMITTED DO
 NOT SHOW ALL SETBACKS ELEVATIONS OF EQUIPMENT, FLOOD
 ZONES?
 PLEASE SEE COMMENTS FROM OTHER TRADES FOR THIS
 INFORMATION. IF IN A FLOOD ZONE, THE UNIT WILL NEED TO
 MEET HEIGHT AND A FLOOD CERTIFICATE WILL BE REQUIRED
 BEFORE FINAL.
  
 ** PLEASE KNOW THERE MAY BE NEW COMMENTS ONCE
 ADDITIONAL INFORMATION IS SUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-02 11:09:41PLANS REMOVED FROM INCOMING. WILL BE ROUTED BACK TO
 INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW
 IS COMPLTETED.