| Date |
Text |
| 2007-07-02 13:20:30 | 2007-07-02 13:20:30 |
| | |
| | *** UNSAT *** |
| | |
| | |
| | *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET |
| | SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE |
| | REVIEWED AT THIS TIME. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE |
| | CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING |
| | ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED |
| | FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006 |
| | THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC |
| | AND THE 2005 NFPA-70. PLEASE LIST THE FOLLOWING: SOME |
| | ARE ALREADY SHOWN ON PLANS. |
| | |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | 2002 NFPA-110. |
| | |
| | 2) NOTE: PLEASE SEE THE APPLIED VALUE FOR COMPLETE |
| | SCOPE OF WORK AS APPLIED ON PERMIT APPLICATION SHALL |
| | INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COST |
| | ETC. THIS APPLIES EVEN IS ANY IS SUPPLIED BY THE OWNER |
| | AND NO COST TO CONTRACTOR. |
| | PLEASE SEE FBC 108.3 AS THIS VALUE MAY BE ADJUSTED BY |
| | THE ADOPTED GUIDES UNDER THE FLORIDA BUILDING CODE. |
| | |
| | 3) NOTE: PLEASE SEE THE RESPONSE LETTER FROM THE |
| | PREVIOUS EXPIRED PERMIT APPLICATION ADDRESSES THE |
| | LETTER TO A *MIKE HIRTANZO* AS THE ELECTRICAL PLAN |
| | REVIEWER. PLEASE SEE THE PREVIOUS REVIEW NOTES UNDER |
| | PREVIOUS APPLIED PERMIT WAS GIVEN BY MYSELF AND THE |
| | ABOVE PERSON DOES NOT WORK FOR THE CITY OF WEST PALM |
| | BEACH. |
| | |
| | 4) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT |
| | SHEETS FOR ALL EQUIPMENT WHICH INDICATE LISTINGS FROM A |
| | NRTL. THE LISTINGS AS SHOWN FOR THE GENERATOR AS |
| | SUBMITTED DO NOT MEET ANY NRTL AS LISTED. |
| | PLEASE SUBMIT THE SPECS FOR THE WP ENCLOSURE ETC. |
| | PLEASE COORDINATE ALL. |
| | PLEASE BE SURE TO HIGH-LIGHT ALL EQUIPMENT SPECIFIC TO |
| | WORK. |
| | NEC 110.3, 90.7 ETC |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SEE THE PLANS HAVE HAND-DRAWN CHANGES |
| | WHICH ARE NOT PERMITTED TO PLANS WHICH ARE SIGNED, |
| | DATED AND SEALED BY AN ENGINEER. FS 471.025 |
| | PLEASE SEE 1 OF 1. |
| | |
| | 6) NOTE: PLEASE SEE TWO DIFFERENT SIZE TANKS ARE BEING |
| | INDICATED ON PLANS. ONE 500 AND THE OTHER 550 GALS. |
| | PLEASE COORDINATE. |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE THE ADDRESS ON PLANS NEEDS TO |
| | COORDINATE WITH THE SITE. THE ADDRESS IS NOT NE 36TH |
| | ST. |
| | FA C61G1-16.004 |
| | |
| | 8) NOTE: PLEASE SEE MISSING MEANS OF DISCONNECT AT |
| | BUILDING. THE BREAKER DOES NOT MEET 702.11, |
| | 225.31-225.39 |
| | PLEASE KNOW THIS DISCONNECTING MEANS ONLY NEEDS TO BE |
| | RATED FOR THE LOAD SERVED AND DOES NOT NEED TO CONTAIN |
| | OCP AS THE BREAKER IN THE GENERATOR CONTAINS THE OCP. |
| | |
| | 9) NOTE: PLEASE SEE PERMIT APPLICATION REQUEST TO |
| | PROVIDE IN DETAIL THE SCOPE OF WORK. PLEASE INCLUDE THE |
| | SIZE OF THE GENERATOR. |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: PLEASE SEE RISER SHOWS THE CAPACITY PROVIDED |
| | AS 1041AMPS, YET THE GENERATOR ONLY INDICATES |
| | 1000AMPS? |
| | PLEASE COORDINATE ALL EQUIPMENT, LOADS ETC. |
| | |
| | 11) NOTE: PLEASE SEE SITE PLANS WHICH WERE SUBMITTED DO |
| | NOT SHOW ALL SETBACKS ELEVATIONS OF EQUIPMENT, FLOOD |
| | ZONES? |
| | PLEASE SEE COMMENTS FROM OTHER TRADES FOR THIS |
| | INFORMATION. IF IN A FLOOD ZONE, THE UNIT WILL NEED TO |
| | MEET HEIGHT AND A FLOOD CERTIFICATE WILL BE REQUIRED |
| | BEFORE FINAL. |
| | |
| | ** PLEASE KNOW THERE MAY BE NEW COMMENTS ONCE |
| | ADDITIONAL INFORMATION IS SUBMITTED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-07-02 11:09:41 | PLANS REMOVED FROM INCOMING. WILL BE ROUTED BACK TO |
| | INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW |
| | IS COMPLTETED. |