| 2007-07-26 10:48:22 | BUILDING REVISION CHECKLIST: |
| | 1- ROOF VENT: |
| | A) ARCHITECT APPROVED ROOF VENT NOA 01-0614.05. THIS |
| | NOA EXPIRED ON 08/16/2006.DADE COUNTY NOA'S SHALL |
| | NOT BE VALID AFTER EXPIRATION DATE.SEE SECOND |
| | PARAGRAPH ON COVER PAGE OF NOA SUBMITTED. |
| | |
| | B)ARCHITECT'S NOTE: "CONTRACTOR RESPONSIBLE FOR |
| | PROVIDING REQ'D VENTING PER CALCULATIONS ON DRAWINGS". |
| | IT'S THE ARCHITECT'S RESPONSIBILITY TO VERIFY IFTHE |
| | NUMBER OFVENTS SHOWN ON PLANSMEET THE VENTING |
| | CALCULATIONS USING THE REVISED VENT,NOT THE |
| | CONTRACTOR.CONTRACTOR'SRESPONSIBILITYIS TO |
| | INSTALLNUMBER OF VENTS VENTSAS SPECIFIED ON PLANS. |
| | NOT TO MAKE CALCULATIONS.IF REVISEDVENT DOESN'T |
| | MEET THE VENTING CALCULATIONS, THEN REVISE PLANS AS |
| | REQUIRED. |
| | |
| | C) THERE ARE TWO DIFFERENT REVIEW STAMPS. ONE OF |
| | THEM IS CLEAR THAT IS THE ARCHITECT'S REVIEW STAMP. |
| | WHO'S REVIEW STAMP IS THE OTHER ONE.THE PURPOSE OF |
| | THE REVIEW STAMP IS TO DISCLOSE WHO REVIEW IT. |
| | OTHERWISE IT'S MEANINGLESS. |
| | |
| | ***NOTE: SAME COMMENT APPLIES TO SHINGLES PRODUCT |
| | APPROVAL. |
| | |
| | 2- REVISION FEES ARE $50.00PLUS $10.00 PER ADDITIONAL |
| | PAGE. OWES $80.00.INFORMATION SUBMITTED IS REVISED |
| | SHEET A705, PLUS PRODUCT APPROVAL FOR SHINGLES, PLUS |
| | PRODUCT APPROVAL FOR ROOF VENT. |
| | |
| | 3- PRODUCT APPROVAL FOR ROOF SHINGLES HAS THE |
| | ARCHITECT'S REVIEW STAMP, BUT NOBODY SIGNED IT AND |
| | DATED IT. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |