Plan Review Notes
Plan Review Notes For Permit 07060613
Permit Number 07060613
Review Stop B
Sequence Number 3
Notes
Date Text
2007-10-19 18:58:12 
 BUILDING PLAN REVIEW
 PERMIT: 07060613
 ADD: 2300 PRESIDENTIAL WAY
 CONT: GRUBER HALL CORP INC.
 TEL: (561)697-3401
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD 10/19-20/07
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)) 106.3.3* PRODUCT APPROVALS- 2004. THOSE PRODUCTS
 THAT ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. PROVIDE
 PRODUCT APPROVALS FOR ALL ROOFING MATERIALS/ BAHAMA
 SHUTTERS. **INDICATE WHICH ITEMS ARE RELEVANT TO THE
 INSTALLATION OF THE DOOR FROM THE FLEMING STEEL DOOR
 PACKAGE.
  
 ROOFING; ONLY CHECKED ITEMS APPLY
 ____1.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY:
 MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / AREA OF
 EACH ROOF TYPE
 ***NOTE***
 **FBC 1507.10.1 BUILT-UP ROOFS SHALL HAVE A DESIGN
 SLOPE OF A MINIMUM OF ? VERTICAL IN 12 HORIZONTAL FOR
 DRAINAGE, COAL-TAR BUILT-UP ROOFS SHALL A MINIMUM SLOPE
 LF 1/8 VERTICAL IN 12 HORIZONTAL. THE INFORMATION
 PROVIDED STATE A ?0? SLOPE.**
  
 ____2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
 _XX_ 3.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. FOR
 THE ROOF TILES INDICATE WHICH FASTEN METHOD WILL BE
 USED.
 _XX_4.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
 _XX5.)OK
  
 _XX 6.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.**PROVIDE
 THE RAS 117 CALCULATIONS TO MEET THE ENHANCED FASTENER
 DENSITIES FOR THE FLAT ROOF**.
  
 **NOTE** PAGE 16 OF THE PRODUCT APPROVAL INDICATE THE
 SPACING OF THE NAILS AND TIN CAPS AT 9 INCHES ON CENTER
 IN TWO STAGGERED ROWS TO ACHIEVE -52.5 PSF. THE
 INFORMATION SUBMITTED FOR THE ENHANCE FASTENING SHOW
 THE SPACING OF THE NAILS AT 12 INCHES ON CENTER FOR
 EACH ZONE AND THE PRESSURES INCREASES FORM -49.2 PSF IN
 ZONE 1 TO -82.6 PSF IN ZONE 2 AND-124.3 PSF IN ZONE
 3. IF THE SPACE IS INCREASED FROM 9 INCHES TO 12 INCHES
 HOW IS IT POSSIBLE TO ACHIEVE HIGHER PRESSURES?THE
 PRODUCT APPROVAL SHALL BE INCLUDED IN THE CALCULATIONS
 OF THE ENHANCED FASTENING.THE PRODUCT APPROVAL ALSO
 STATES THAT THE CALCULATIONS SHALL BE IN COMPLIANCE
 WITH RAS 117 NOT RAS 150.THE INFORMATION PROVIDED IS
 NON-COMPLIANT.
  
 3)OK
  
 4)2303.4.1 TRUSS DESIGN DRAWINGS.
 TRUSS CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL AND SHALL BE PROVIDED TO
 THE BUILDING OFFICIAL AND APPROVED PRIOR TO
 INSTALLATION. SUBMIT THE FLAT AND HIP ROOF INFORMATION.
 *****NOTED*****
  
 **NOTE** A SEPARATE PERMIT IS REQUIRED FOR EACH
 STRUCTURE LOCATED AT DIFFERENT LOCATIONS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]