| 2007-10-19 18:58:12 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07060613 |
| | ADD: 2300 PRESIDENTIAL WAY |
| | CONT: GRUBER HALL CORP INC. |
| | TEL: (561)697-3401 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 3RD 10/19-20/07 |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)) 106.3.3* PRODUCT APPROVALS- 2004. THOSE PRODUCTS |
| | THAT ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. PROVIDE |
| | PRODUCT APPROVALS FOR ALL ROOFING MATERIALS/ BAHAMA |
| | SHUTTERS. **INDICATE WHICH ITEMS ARE RELEVANT TO THE |
| | INSTALLATION OF THE DOOR FROM THE FLEMING STEEL DOOR |
| | PACKAGE. |
| | |
| | ROOFING; ONLY CHECKED ITEMS APPLY |
| | ____1.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| | INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY: |
| | MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / AREA OF |
| | EACH ROOF TYPE |
| | ***NOTE*** |
| | **FBC 1507.10.1 BUILT-UP ROOFS SHALL HAVE A DESIGN |
| | SLOPE OF A MINIMUM OF ? VERTICAL IN 12 HORIZONTAL FOR |
| | DRAINAGE, COAL-TAR BUILT-UP ROOFS SHALL A MINIMUM SLOPE |
| | LF 1/8 VERTICAL IN 12 HORIZONTAL. THE INFORMATION |
| | PROVIDED STATE A ?0? SLOPE.** |
| | |
| | ____2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| | SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG |
| | _XX_ 3.)FOR THE FLAT DECK, SELECT THE APPROVED |
| | ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| | IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. FOR |
| | THE ROOF TILES INDICATE WHICH FASTEN METHOD WILL BE |
| | USED. |
| | _XX_4.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES. |
| | _XX5.)OK |
| | |
| | _XX 6.)SEE PRODUCT LIMITATION #7.CALCULATIONS |
| | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| | CONSULTANT REQUIRED FOR ENHANCED FASTENING.**PROVIDE |
| | THE RAS 117 CALCULATIONS TO MEET THE ENHANCED FASTENER |
| | DENSITIES FOR THE FLAT ROOF**. |
| | |
| | **NOTE** PAGE 16 OF THE PRODUCT APPROVAL INDICATE THE |
| | SPACING OF THE NAILS AND TIN CAPS AT 9 INCHES ON CENTER |
| | IN TWO STAGGERED ROWS TO ACHIEVE -52.5 PSF. THE |
| | INFORMATION SUBMITTED FOR THE ENHANCE FASTENING SHOW |
| | THE SPACING OF THE NAILS AT 12 INCHES ON CENTER FOR |
| | EACH ZONE AND THE PRESSURES INCREASES FORM -49.2 PSF IN |
| | ZONE 1 TO -82.6 PSF IN ZONE 2 AND-124.3 PSF IN ZONE |
| | 3. IF THE SPACE IS INCREASED FROM 9 INCHES TO 12 INCHES |
| | HOW IS IT POSSIBLE TO ACHIEVE HIGHER PRESSURES?THE |
| | PRODUCT APPROVAL SHALL BE INCLUDED IN THE CALCULATIONS |
| | OF THE ENHANCED FASTENING.THE PRODUCT APPROVAL ALSO |
| | STATES THAT THE CALCULATIONS SHALL BE IN COMPLIANCE |
| | WITH RAS 117 NOT RAS 150.THE INFORMATION PROVIDED IS |
| | NON-COMPLIANT. |
| | |
| | 3)OK |
| | |
| | 4)2303.4.1 TRUSS DESIGN DRAWINGS. |
| | TRUSS CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A |
| | REGISTERED DESIGN PROFESSIONAL AND SHALL BE PROVIDED TO |
| | THE BUILDING OFFICIAL AND APPROVED PRIOR TO |
| | INSTALLATION. SUBMIT THE FLAT AND HIP ROOF INFORMATION. |
| | *****NOTED***** |
| | |
| | **NOTE** A SEPARATE PERMIT IS REQUIRED FOR EACH |
| | STRUCTURE LOCATED AT DIFFERENT LOCATIONS. |
| | |