| 2007-09-26 11:31:25 | BUILDING PLAN REVIEW |
| | PERMIT: 07060613 |
| | ADD: 2300 PRESIDENTIAL WAY |
| | CONT: GRUBER HALL CORP INC. |
| | TEL: (561)697-3401 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 2ND |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)) 106.3.3* PRODUCT APPROVALS- 2004 |
| | THOSE PRODUCTS THAT ARE RGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITTING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. PROVIDE PRODUCT APPROVALS FOR |
| | ALL ROOFING MATERIALS/ EXTERIOR DOORS/PRE-CAST |
| | LINTEL/BAHAMA SHUTTERS AND THE ROLING STEEL DOOR. |
| | **THE PRODUCT APPROVAL FOR THE PRE-CAST LINTEL IS |
| | MISSING FROM THE PACKAGE.** |
| | |
| | ROOFING ; ONLY CHECKED ITEMS APPLY |
| | ____1.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| | INFORMATION ON THE APPLICATION, SEE ATTACHED |
| | POLICY:MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / |
| | AREA OF EACH ROOF TYPE |
| | |
| | ____2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| | SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG |
| | |
| | _XX_ 3.)FOR THE FLAT DECK, SELECT THE APPROVED |
| | ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| | IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. FOR |
| | THE ROOF TILES INDICATE WHICH FASTEN METHOD WILL BE |
| | USED. |
| | |
| | _XX_4.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES. |
| | |
| | _XX5.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH |
| | METHOD OF ATTACHMENT YOU ARE USING. **ON PAGE #4 OR #5 |
| | OF THE ROOF TILE PRODUCT APPROVAL CIRCLE WHICH ITEM |
| | WILL BE USED**. |
| | |
| | _XX 6.)SEE PRODUCT LIMITATION #7.CALCULATIONS |
| | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| | CONSULTANT REQUIRED FOR ENHANCED FASTENING.**PROVIDE |
| | THE RAS 117 CALCULATIONS TO MEET THE ENHANCED FASTENER |
| | DENSITIES FOR THE FLAT ROOF**. |
| | |
| | 3)OK |
| | |
| | 4)2303.4.1 TRUSS DESIGN DRAWINGS. |
| | TRUSS CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A |
| | REGISTERED DESIGN PROFESSIONAL AND SHALL BE PROVIDED TO |
| | THE BUILDING OFFICIAL AND APPROVED PRIOR TO |
| | INSTALLATION. SUBMIT THE FLAT AND HIP ROOF |
| | INFORMATION. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |