Plan Review Notes
Plan Review Notes For Permit 07060613
Permit Number 07060613
Review Stop E
Sequence Number 1
Notes
Date Text
2007-07-02 16:52:552007-07-02 16:52:55
  
 *** UNSAT ***
  
  
 ** PLEASE KNOW THERE MAY BE NEW COMMENTS ONCE
 ADDITIONAL INFORMATION IS SUBMITTED.
  
 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE
 CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING
 ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED
 FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006
 THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC
 AND THE 2005 NFPA-70. PLEASE SEE THE PLANS DENOTE THE
 2005 REVISIONS.
 PLEASE LIST THE FOLLOWING:
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE NOTES FROM BUILDING AND ADDRESSING
 REVIEWER(S) AS EACH BUILDING MAY REQUIRE SEPARATE
 PERMIT APPLICATIONS. PLEASE ALSO SEE THE ADDRESSING OF
 EACH WILL BE CHANGED FOR EXTENSIONS UNDER THE COMMON
 AREA ADDRESS.
 PLEASE ADJUST TITLE BLOCKS WITH ANY NEW ADDRESS AT
 DETERMINED BY THIS OFFICE.
 PLEASE KNOW, IF EACH BUILDING IS UNDER SEPARATE
 PERMITS, TWO SETS OF PLANS WILL BE REQUIRED FOR EACH.
 FAC 61G1-16.004
 FBC 106.1
  
 3) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 FOR ARCHITECTURAL FIRM AS REQUIRED PER FAC 61G1-16.004,
 FS 481.219.
 PLEASE SEE MISSING THE CERTIFICATE OF AUTHORIZATION
 NUMBER ALSO KNOWN AS THE FIRM LICENSE NUMBER.
  
 4) NOTE: PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS ARE
 NOT OF SUFFICIENT SIZE PER 310.16, 240.4.
 PLEASE SEE MINIMUM SIZE REQUIRED FOR THE 100AMP MAIN AS
 SHOWN.
  
 5) NOTE: PLEASE SEE RISER INDICATES AN *EQUIPMENT
 GROUNDING CONDUCTOR* FROM FPL BEFORE THE FIRST MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED. PLEASE SEE 250.6 AND
 250.24.
 THE EQUIPMENT GROUNDING CONDUCTOR IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 6) NOTE: PLEASE SEE 2005 NEC AS OUTDOOR RECEPTACLES IN
 210.8B4 REQUIRE GFI PROTECTION EVEN FOR DEDICATE
 CIRCUITS/DEVICES/APPLIANCES.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-02 15:36:122007-07-02 15:36:12
 PLANS REMOVED FROM INCOMING. PLANS WILL RETURN TO
 INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW
 IS DONE.