| Date |
Text |
| 2007-07-02 16:52:55 | 2007-07-02 16:52:55 |
| | |
| | *** UNSAT *** |
| | |
| | |
| | ** PLEASE KNOW THERE MAY BE NEW COMMENTS ONCE |
| | ADDITIONAL INFORMATION IS SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE |
| | CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING |
| | ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED |
| | FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006 |
| | THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC |
| | AND THE 2005 NFPA-70. PLEASE SEE THE PLANS DENOTE THE |
| | 2005 REVISIONS. |
| | PLEASE LIST THE FOLLOWING: |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE NOTES FROM BUILDING AND ADDRESSING |
| | REVIEWER(S) AS EACH BUILDING MAY REQUIRE SEPARATE |
| | PERMIT APPLICATIONS. PLEASE ALSO SEE THE ADDRESSING OF |
| | EACH WILL BE CHANGED FOR EXTENSIONS UNDER THE COMMON |
| | AREA ADDRESS. |
| | PLEASE ADJUST TITLE BLOCKS WITH ANY NEW ADDRESS AT |
| | DETERMINED BY THIS OFFICE. |
| | PLEASE KNOW, IF EACH BUILDING IS UNDER SEPARATE |
| | PERMITS, TWO SETS OF PLANS WILL BE REQUIRED FOR EACH. |
| | FAC 61G1-16.004 |
| | FBC 106.1 |
| | |
| | 3) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS |
| | FOR ARCHITECTURAL FIRM AS REQUIRED PER FAC 61G1-16.004, |
| | FS 481.219. |
| | PLEASE SEE MISSING THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER ALSO KNOWN AS THE FIRM LICENSE NUMBER. |
| | |
| | 4) NOTE: PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS ARE |
| | NOT OF SUFFICIENT SIZE PER 310.16, 240.4. |
| | PLEASE SEE MINIMUM SIZE REQUIRED FOR THE 100AMP MAIN AS |
| | SHOWN. |
| | |
| | 5) NOTE: PLEASE SEE RISER INDICATES AN *EQUIPMENT |
| | GROUNDING CONDUCTOR* FROM FPL BEFORE THE FIRST MEANS OF |
| | DISCONNECT WHICH IS NOT PERMITTED. PLEASE SEE 250.6 AND |
| | 250.24. |
| | THE EQUIPMENT GROUNDING CONDUCTOR IS ONLY INSTALLED |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | |
| | 6) NOTE: PLEASE SEE 2005 NEC AS OUTDOOR RECEPTACLES IN |
| | 210.8B4 REQUIRE GFI PROTECTION EVEN FOR DEDICATE |
| | CIRCUITS/DEVICES/APPLIANCES. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-07-02 15:36:12 | 2007-07-02 15:36:12 |
| | PLANS REMOVED FROM INCOMING. PLANS WILL RETURN TO |
| | INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW |
| | IS DONE. |