Plan Review Notes
Plan Review Notes For Permit 07060613
Permit Number 07060613
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-17 12:58:26BUILDING PLAN REVIEW
 PERMIT: 07060613
 ADD: 2300 PRESIDENTIAL WAY
 CONT: GRUBER HALL CORP INC.
 TEL: (561)697-3401
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE PRODUCT APPROVALS FOR
 ALL ROOFING MATERIALS/ EXTERIOR DOORS/PRE-CAST
 LINTEL/BAHAMA SHUTTERS AND THE ROLING STEEL DOOR.
  
 ROOFING ; ONLY CHECKED ITEMS APPLY
 ____1.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED
 POLICY:MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE /
 AREA OF EACH ROOF TYPE
  
 ____2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 ____3.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS.
 FOR THE ROOF TILES INDICATE WHICH FASTEN METHOD WILL
 BE USED.
  
 ____4.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
  
 ____5.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.
  
 ____ 6.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  
  
 3)THE TITLE BLOCK IS MISSING THE FIRM LICENSE NUMBER.
 SEE FAC. 61G1-16.004.
  
 4)2303.4.1 TRUSS DESIGN DRAWINGS.
 TRUSS CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL AND SHALL BE PROVIDED TO
 THE BUILDING OFFICIAL AND APPROVED PRIOR TO
 INSTALLATION. SUBMIT THE FLAT AND HIP ROOF
 INFORMATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  