2007-06-28 14:32:03****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 COMMENTS FROM PREVIOUS LISTS:
  
  
  
 _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS.THIS ASSEMBLY WILL BE FOUND BETWEEN PAGES
 9 AND 31 OF THE PRODUCT APPROVAL.
  
 3RD REVIEW, CONTRACTOR WROTE "ROOF ASSEMBLY FROM PAGES
 9 - 20" ON THE RESUBMITTAL SHEET.CONTRACTOR IS TO
 SELECT ONE ASSEMBLY AND CLEARLY MARK IT.ASSEMBLY MUST
 REFER TO GENERAL LIMITATION #7, CANNOT REFER TO GENERAL
 LIMITATION #9.
  
 _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.YOUR
 RESPONSE WAS TO SPECIFY THE NAIL LENGTH AND TWO PLY. AS
 REQUESTED PLEASE SPECIFY ENHANCED FASTENING FOR THE
 CORNER AND PERMITER ZONES, ZONES 2 AND 3 IN ACCORDANCE
 WITH RAS117.
  
 3RD REVIEW, NOT ADDRESSED.THIS IS REQUIRED FOR PERMIT
 ISSUANCE.
  