Text |
| 2007-06-22 08:54:55 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC. |
| | THE ENGINEER HAVING DECLARED "STRUCTURAL ONLY" ON THIS |
| | SHEET, IS ASSUMED NOT RESPONSIBLE, AND SHOULD THEREFORE |
| | STRIKE OR REMOVE HIS SEAL AND SIGNATURE. |
| | |
| | 2} } PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 3}LOCATE THE SERVICE EQUIPMENT ON THE ELECTRICAL PLAN |
| | SO THAT COMPLIANCE WITH ARTICLE 230 CAN BE REVIEWED. |
| | INDICATE IF OVERHEAD OR UNDERGROUND ON THE RISER |
| | DIAGRAM. |
| | |
| | 4} LOCATE THE A/C CONDENSER ON THE PLAN AND COMPLIANCE |
| | WITH 210.63.ALSO 110.26 FOR THE DOSCONNECT. |
| | |
| | 5} PLEASE NOTE THAT THE DINING AREA IS REQUIRED TO BE |
| | ON A SMALL APPLIANCE CIRCUIT PER 210.52(B)(1). THE |
| | LIVING/DINING ROOMS MUST BE ON SEPERATE CIRCUITS. |
| | |
| | 6} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), SEE REVIEWED SET. |
| | |
| | 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1) |
| | AND 210.52 (A) (2), SEE FAMILY ROOM. |
| | |
| | 8} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING |
| | AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE |
| | LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT |
| | GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE |
| | GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE |
| | DWELLING. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |