| 2007-09-10 08:02:11 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 2.)SEE OPENING 1.SPAN OF 111 REQUIERS USE OF 10' |
| | ROW, -52.7 REQUIES USE OF -60PSF COLUMN.SEE THE |
| | PRODUCT APPROVAL WHICH I HAVE HIGHLIGHTED.9" REQUIRED |
| | FOR CONNECTION TYPE G, 7" REQUIRED FOR CONNECTION TYPE |
| | H.PLEASE SEE PRODUCT APPROVAL AND REVISE.OTHER |
| | OPENING ANCHOR SPACINGS ARE ALSO INCORRECT; PLEASE SEE |
| | PRODUCT APPROVAL WHICH I HAVE HIGHLIGHTED. |
| | |
| | 5TH REVIEW - CONTRACTOR HAS SENT A NOTE STATING THAT |
| | THE SHUTTER SPAN IS 96", NOT 10FEET.PLEASE SEE THE |
| | INSTALLATION SCHEDULE WHICH YOU HAVE COMPLETED.FOR |
| | SPAN, YOU STATE THAT IT IS 111" FOR OPENING 1.THE |
| | SPAN SHOULD BE THE BLADE LENGTH.ALL DIMENSIONS SHOULD |
| | ALWAYS BE WIDTH X HEIGHT, AS STATED ON THE INSTALLATION |
| | SCHEDULE AND AS IS INDUSTRY STANDARD FOR WINDOW AND |
| | DOOR OPENINGS.IT APPEARS THAT YOU ARE USING THE WIDTH |
| | TO STATE THE SPANS.AS SPAN IS BLADE LENGTH, THIS |
| | SHOULD ALWAYS CORRELATE WITH THE HEIGHT DIMENSION. |
| | PLEASE REVISE THE INSTALLATION SCHEDULE. |
| | |