Plan Review Notes
Plan Review Notes For Permit 07060569
Permit Number 07060569
Review Stop B
Sequence Number 5
Notes
Date Text
2007-09-10 08:02:11****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 2.)SEE OPENING 1.SPAN OF 111 REQUIERS USE OF 10'
 ROW, -52.7 REQUIES USE OF -60PSF COLUMN.SEE THE
 PRODUCT APPROVAL WHICH I HAVE HIGHLIGHTED.9" REQUIRED
 FOR CONNECTION TYPE G, 7" REQUIRED FOR CONNECTION TYPE
 H.PLEASE SEE PRODUCT APPROVAL AND REVISE.OTHER
 OPENING ANCHOR SPACINGS ARE ALSO INCORRECT; PLEASE SEE
 PRODUCT APPROVAL WHICH I HAVE HIGHLIGHTED.
  
 5TH REVIEW - CONTRACTOR HAS SENT A NOTE STATING THAT
 THE SHUTTER SPAN IS 96", NOT 10FEET.PLEASE SEE THE
 INSTALLATION SCHEDULE WHICH YOU HAVE COMPLETED.FOR
 SPAN, YOU STATE THAT IT IS 111" FOR OPENING 1.THE
 SPAN SHOULD BE THE BLADE LENGTH.ALL DIMENSIONS SHOULD
 ALWAYS BE WIDTH X HEIGHT, AS STATED ON THE INSTALLATION
 SCHEDULE AND AS IS INDUSTRY STANDARD FOR WINDOW AND
 DOOR OPENINGS.IT APPEARS THAT YOU ARE USING THE WIDTH
 TO STATE THE SPANS.AS SPAN IS BLADE LENGTH, THIS
 SHOULD ALWAYS CORRELATE WITH THE HEIGHT DIMENSION.
 PLEASE REVISE THE INSTALLATION SCHEDULE.
  