2007-08-28 09:47:53****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SEE PREVIOUS LISTS.TWO COMPLETE SETS OF PERMIT
 DOCUMENTS REQUIRED.ONLY ONE INSTALLATION SCHEDULE WAS
 SUBMITTED.DUE TO WORKLOAD, I AM UNABLE TO MAKE
 COPIES.A PHOTOCOPY MACHINE HAS BEEN PROVIDED IN THE
 LOBBY FOR THIS PURPOSE.
  
 2.)SEE OPENING 1.SPAN OF 111 REQUIERS USE OF 10'
 ROW, -52.7 REQUIES USE OF -60PSF COLUMN.SEE THE
 PRODUCT APPROVAL WHICH I HAVE HIGHLIGHTED.9" REQUIRED
 FOR CONNECTION TYPE G, 7" REQUIRED FOR CONNECTION TYPE
 H.PLEASE SEE PRODUCT APPROVAL AND REVISE.OTHER
 OPENING ANCHOR SPACINGS ARE ALSO INCORRECT; PLEASE SEE
 PRODUCT APPROVAL WHICH I HAVE HIGHLIGHTED.
  
  