| Plan Review Notes For Permit 07060569 |
| Permit Number |
07060569 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-08-28 09:47:53 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)SEE PREVIOUS LISTS.TWO COMPLETE SETS OF PERMIT | | | DOCUMENTS REQUIRED.ONLY ONE INSTALLATION SCHEDULE WAS | | | SUBMITTED.DUE TO WORKLOAD, I AM UNABLE TO MAKE | | | COPIES.A PHOTOCOPY MACHINE HAS BEEN PROVIDED IN THE | | | LOBBY FOR THIS PURPOSE. | | | | | | 2.)SEE OPENING 1.SPAN OF 111 REQUIERS USE OF 10' | | | ROW, -52.7 REQUIES USE OF -60PSF COLUMN.SEE THE | | | PRODUCT APPROVAL WHICH I HAVE HIGHLIGHTED.9" REQUIRED | | | FOR CONNECTION TYPE G, 7" REQUIRED FOR CONNECTION TYPE | | | H.PLEASE SEE PRODUCT APPROVAL AND REVISE.OTHER | | | OPENING ANCHOR SPACINGS ARE ALSO INCORRECT; PLEASE SEE | | | PRODUCT APPROVAL WHICH I HAVE HIGHLIGHTED. | | | | | | |
|