| Plan Review Notes For Permit 07060569 |
| Permit Number |
07060569 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-08-03 16:16:25 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)3" EDGE DISTANCE REQUIRES A FACTOR OF .83, SEE | | | SHEET 14 OF THE PRODUCT APPROVAL. | | | | | | 2.)PRESSURES DO NOT MATCH ENGINEERING. | | | | | | 3.)ANCHOR TYPE SHOULD BE ONE FROM THE PRODUCT | | | APPROVAL ANCHOR CHART, NOT "316 AISI".SEE PAGE 14. |
|