| 2007-06-29 07:16:57 | |
| | |
| | *** UNSAT *** |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS AND |
| | ARCHITECTURAL COVER SHEET FOR THIS REVIEWER AT A |
| | MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | ** PLEASE SEE COMMENTS FROM FIRE AND OTHER TRADES FOR |
| | OTHER CODES REFERENCED. |
| | |
| | 2) NOTE: PLEASE PROVIDE THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE MOTOR CONTROL EQUIPMENT . 110.3, 90.7 |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE BE SURE THE ADDRESS IS STATED ON PLANS. |
| | PLEASE KNOW THIS WILL BE ROUTED TO ADDRESSING FOR |
| | POSSIBLE ADDRESS EXTENSION TO SITE ADDRESS. THERE ARE |
| | MORE THAN ONEBUILDING LOCATED IN THE COMMON AREA AND |
| | EACH SHOULD HAVE AN EXTENSION WHICH IS SPECIFIC TO THAT |
| | BUILDING OR STRUCTURE. FAC 61G1-16.004 |
| | |
| | 4) NOTE: PLEASE BE SURE ALL ELECTRICAL WHICH IS ON THE |
| | SEPARATE ELECTRICAL RISER IS ON PLANS AND IDENTIFIED AT |
| | EACH LOCATION. (SOME MISSING). |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SEE NOTES FROM OTHER TRADES FOR SURVEY |
| | WHICH IS REQUIRED TO HAVE AN ORIGINAL SIGNATURE PER FS |
| | 472.025 |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-06-28 16:38:40 | PLANS REMOVED FROM INCOMING AND WILL BE SENT BACK TO |
| | INCOMING ONCE ELECTRICAL REVIEW IS DONE. |