| 2007-11-19 12:46:51 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1.IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R |
| | 301.2.1.2.THE APPLICATION STATES THE WINDOWS ARE |
| | IMPACT, PRODUCT APPROVALS ARE NON IMPACT.PLEASE |
| | ADDRESS. |
| | |
| | 2ND REVIEW - RESPONSE LETTER STATES THAT THE |
| | APPLICATION STATES NON IMPACT.IT APPEARS TO SAY "NEW |
| | IMPACT".REGARDLESS, IMPACT PROTECTION IS STILL |
| | REQUIRED REGARDLESS OF WHAT THE APPLICATION STATES, SEE |
| | FBC EB507.2. |
| | |
| | 2.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, |
| | FAC9B72, WWW.FLORIDABUILDING.ORG. |
| | |
| | 2ND REVIEW - NOT ADDRESSED; PLEASE GO TO THE WEBSITE |
| | AND PRINT THE FLORIDA STATE PRODUCT APPROVALS AS |
| | REQUIRED. |
| | 3RD REVIEW - THE WORD "LOCAL" WAS WRITTEN ON THE NOAS. |
| | I LOOKED UP TM, SINGLE HUNG WINDOW, AND FOUND A FLORIDA |
| | STATE PRODUCT APPROVAL.A LOCAL WILL NOT BE ISSUED IF |
| | A FLORIDA STATE PRODUCT APPROVAL HAS ALREADY BEEN |
| | ISSUED, PER BUILDING OFFICIAL. |
| | |
| | 3.PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, |
| | SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE EXISTING |
| | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR |
| | BEDROOMS, FBC R310, FBC EB 505.1. |
| | |
| | 2ND REVIEW - PLEASE ADDRESS.CONTRACTOR WROTE A |
| | STATEMENT THAT THERE WILL BE A CASEMENT IN EACH |
| | BEDROOM.YOU ARE TO PROVIDE ALL INFORMATION REQUIRED, |
| | INCLUDING BEDROOM LOCATIONS, WINDOW TYPES, AND SIZES. |
| | 3RD REVIEW - THE FLOOR PLAN WAS PROVIDED BUT ROOM |
| | DESIGNATIONS NOT SHOWN.PLEASE PROVIDE REQUIRED |
| | INFORMATION. |
| | |
| | NEW COMMENTS: |
| | |
| | 4.THE INSTALLATION SCHEDULE IS INCOMPLETE. |
| | |
| | 5.PROVIDE THE COMPLETE PRODUCT APPROVAL INCLUDING |
| | EVALUATION REPORT AND INSTALLATION INSTRUCTIONS FOR THE |
| | SHUTTERS.ONLY THE FIRST FEW SHEETS WERE PROVIDED, BUT |
| | THE ENGINEERING DETAILS AND ANCHOR SCHEDULE CHARTS WERE |
| | NOT INCLUDED.THIS IS REQUIRED FOR PLAN REVIEW AND FOR |
| | INSPECTIONS. |
| | |
| | |