| 2007-11-01 17:18:34 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEWS: |
| | |
| | A. GAS PERMIT INFORMATION REQUIRED AS FOLLOWS: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN |
| | SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED. |
| | ******RESPONSE NOTED, BUT THE CORRESPONDING LENGHTS ARE |
| | NOT INDICATED ON THE ISOMETRIC FOR ALL CUT SECTIONS AS |
| | REQUESTED. ALL INFORMATION IS REQUIRED TO DO A COMPLETE |
| | PLAN REVIEW. |
| | |
| | 2. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). - INDICATE TOTAL BTU LOAD INCLUDING |
| | EXISTING. |
| | ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN |
| | SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED. |
| | ******RESPONSE NOTED, BUT THE BTU LOAD OF EACH |
| | APPLIANCE AND THE TOTAL BTU LOAD OF THE SYSTEM HAVE NOT |
| | BEEN INDICATED AS REQUESTED. ALL INFORMATION IS |
| | REQUIRED TO DO A COMPLETE PLAN REVIEW. |
| | |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN |
| | SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED. |
| | ******RESPONSE NOTED, BUT THE DISTANCE FROM THE METER |
| | TO THE MOST REMOTE OUTLET AS REQUESTED HAS NOT BEEN |
| | INDICATED. ALL INFORMATION IS REQUIRED TO DO A COMPLETE |
| | PLAN REVIEW. |
| | |
| | |
| | 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. SHEETS SHALL |
| | INDICATE MAXIMUM BTU LOAD AT 100%. |
| | ****RESPONSE NOTED, BUT THE LISTING AND INSTALLATION |
| | INSTRUCTIONS FOR THE GENERATOR ARE NOT INDICATED. SEE |
| | COMMENT #3 OF THE ELECTRICAL PLAN REVIEW CONCERNING THE |
| | ORIGINAL LISTING AND THE REQUIREMENT OF RELISTING THE |
| | GENERATOR. PLEASE SUBMIT THE CERTIFICATION PAPERS FOR |
| | RELISTING THE GENERATOR AS WELL AS THE MANUF. |
| | INSTALLATION INSTRUCTIONS SHOWING ALL CLEARANCES. |
| | ******RESPONSE NOTED AND THIS CAN BE A PROVISO AS |
| | INDICATED IN THE ELECTRICAL PLAN REVIEW, BUT SINCE THE |
| | GENERATOR HAS BEEN INSTALLED ALREADY, THIS SHALL BE |
| | DONE AS SOON AS POSSIBLE AS TO NOT DELAY ANY |
| | INSPECTIONS. |
| | |
| | B. OK |
| | |
| | C. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS |
| | REGULATORS. SECTION 106.1.2. |
| | ****RESPONSE NOTED, BUT THE MANUF. SPEC. SHEETS FOR THE |
| | REGULATORS WERE NOT SUBMITTED. |
| | ******NO RESPONSE, NOT ADDRESSED. WHEN SUBMITTING THE |
| | REGULATOR INFORMATION, INDICATE THE MODEL NUMBER AND |
| | THE TOTAL BTU LOAD ON EACH LOW PRESSURE SYSTEM |
| | DOWNSTREAM OF THE REGULATOR. |
| | |
| | D. OK |
| | E. OK |
| | |
| | ********NEW COMMENT******** |
| | |
| | 1B. OK |
| | 2B. OK |
| | |
| | REVIEW BY KEN STEVENS |