| 2007-10-11 15:06:10 | ***DENIED*** | | | | | | THE RESPONSE LETTER IS DATED TWO (2) DAYS BEFORE THE | | | FIRST FIRE PLAN REVIEW WAS COMPLETED. IT DOES NOT | | | APPEAR THAT THE FIRE COMMENTS WERE CONSIDERED FOR THIS | | | SUBMITTAL. PLEASE SEE THE FOLLOWING COMMENTS TAKEN | | | DIRECTLY FROM THE FIRST FIRE REVIEW: | | | | | | 1) STATIONARY GENERATORS FOR EMERGENCY USE OR STAND BY | | | POWER SHALL BE INSTALLED WITH COMPLIANCE WITH NFPA | | | 110. | | | | | | 2) ABOVE GROUND FUEL TANKS SHALL BE PERMITTED TO BE | | | INSTALLED THAT MEET THE REQUIREMENTS OF NFPA 30. NFPA | | | 704 LABELS WILL BE REQUIRED. | | | | | | 3) SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE | | | GENERATOR. | | | | | | 4) PROVIDE PROPER SETBACKS TO PROPERTY LINES AND AT | | | LEAST 10' DISTANCE TO BUILDING OPENINGS. | | | | | | 5) PROVIDE MANUFACTURE SPEC SHEETS FOR THE | | | EQUIPMENT.-OK | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | | ADDRESSED. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|